| 2021-07-08 09:48:19 | 07/08/21 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE CONTRACT STATES FUTURE GAS THAT CONSISTS OF |
| | RANGE AND BBQ. THESE APPLIANCES NEED TO BE ADDED TO THE |
| | SYSTEM AND CALCULATED TO SIZE THE MAIN FEED PROPERLY IN |
| | THE LONGEST RUN. WOULD YOU PLEASE SHOW THE TOTAL BTU'S |
| | ON ISOMETRIC GAS RISER? LIST THE BTU LOAD OF EACH |
| | APPLIANCE AND THE TOTAL BTU LOAD ON THE SYSTEM PER THE |
| | WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 2. PLEASE PROVIDE MANUFACTURES SPECIFICATIONS FOR RANGE |
| | AND BBQ. THEY MAY BE A GENERIC TYPE WITH MINIMUM SIZING |
| | FOR THE FUTURE PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 3. PLEASE SHOW ON ISOMETRIC DRAWING THE LENGTH OF ALL |
| | CUT SECTIONS OF PIPE TO THE RANGE AND GIVE THE TYPE OF |
| | PIPE (EHD NUMBER FOR CSST) PER THE WPB AMENDMENTS TO |
| | THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 4. THIS TANK-LESS UNIT CALL FOR A 10.5" WATER COLUMN |
| | AND THE SERVICE METER DISCHARGES IS A 12" WATER COLUMN |
| | REQUIRING A REGULATOR FOR THIS UNIT AS PER THE |
| | MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| | APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES. |
| | SEC. G2421.1. |
| | |
| | 5. INDICATE ON THE PLAN IF THE GRILL IS LOCATED UNDER A |
| | ROOF AND IT WILL BE IN A COVERED PATIO. WOULD YOU |
| | PLEASE PROVIDE THE MANUFACTURER'S RECOMMENDATION FOR A |
| | VENTILATION HOOD PER THE 2020 FBC RES. SEC? G2408.1. |
| | |
| | 6. PLEASE SHOW REGULATOR AND ALL UNIONS IN FRONT OF |
| | REGULATOR 1' OF EITHER SIDE PER THE 2020 FBC RES. SEC |
| | G2421.2. |
| | |
| | 7. PLEASE SHOW LABEL THE SHUTOFF VALVE ON GAS ISOMERIC |
| | PER THE 2020 FBC RES. SEC. G2420.5. THE SHUT OFF INSIDE |
| | SHALL BE ACCESSIBLE WITHOUT MOVING THE EQUIPMENT PER |
| | THE 2020 FBC SEC. G2403 (202) GD, ACCESS. |
| | |
| | 8. SHOW DRIP LEG ON EQUIPMENT INSTALLED, EXCEPT FOR |
| | APPLIANCES, RANGE, DRYERS & OD GRILLS PER THE 2020 FBC |
| | RES. SEC. G2419.2. |
| | |
| | 9. FUTURE GAS APPLIANCE CONNECTION CAPPED AND SHUT OFF |
| | VALVE INSTALLED PER THE 2020 RES. SECS. G2415, G2422 |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |
| | |