Plan Review Details - Permit 21070015
Plan Review Stops For Permit 21070015
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-02-07 Cont ID  
Sent By cpuell Date 2022-02-07 Time 14:58 Rev Time 0.00
Received By cpuell Date 2022-02-07 Time 14:58 Sent To  
Notes
2022-02-07 14:58:33ADDRESS APPROPRIATE FOR PROJECT.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2023-01-23 Cont ID  
Sent By mpeterso Date 2023-01-23 Time 09:35 Rev Time 0.00
Received By mpeterso Date 2023-01-23 Time 09:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-05-20 Cont ID  
Sent By mpeterso Date 2022-05-20 Time 08:07 Rev Time 0.00
Received By mpeterso Date 2022-05-20 Time 08:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-04-18 Cont ID  
Sent By mpeterso Date 2022-04-18 Time 11:36 Rev Time 0.00
Received By mpeterso Date 2022-04-18 Time 11:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-02-25 Cont ID  
Sent By mpeterso Date 2022-02-25 Time 14:56 Rev Time 0.00
Received By mpeterso Date 2022-02-25 Time 14:56 Sent To  
Notes
2022-02-25 15:00:26ELECTRIC REVIEW FAILED
 1) NO CONDUIT, CONDUCTORS, OR OVERCURRENT PROTECTION
 DETAILED. FBC 107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2022-03-22 Cont ID  
Sent By shill Date 2022-03-22 Time 07:05 Rev Time 0.00
Received By shill Date 2022-03-22 Time 07:05 Sent To  
Notes
2022-03-22 07:05:51PER ES/AA, IMPROVEMENT IS ENTIRELY ON PRIVATE PROPERTY.
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-02-01 Cont ID  
Sent By aoliver Date 2023-02-01 Time 13:26 Rev Time 0.00
Received By aoliver Date 2023-01-23 Time 07:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-05-20 Cont ID  
Sent By mpeterso Date 2022-05-20 Time 09:27 Rev Time 0.00
Received By mpeterso Date 2022-05-12 Time 06:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-04-21 Cont ID  
Sent By jgomez Date 2022-04-21 Time 15:31 Rev Time 0.00
Received By jgomez Date 2022-03-28 Time 06:32 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-03-22 Cont ID  
Sent By shill Date 2022-03-22 Time 07:05 Rev Time 0.00
Received By shill Date 2022-02-06 Time 08:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date 2021-07-13 Cont ID  
Sent By shill Date 2021-07-13 Time 11:56 Rev Time 0.00
Received By shill Date 2021-07-13 Time 11:04 Sent To  
Notes
2021-07-13 11:56:13****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 SCOPE OF WORK IS NOT CLEAR.
  
 THREE APPLICATIONS WERE SUBMITTED, STATING THE WORK IS
 IN THE ROW. 21070174, 21070015, 21070017. IT IS NOT
 CLEAR WHERE THE WORK IS TO BE DONE. THE WORK IS SHOWN
 IN THE RIGHT OF WAY (ONE PERMIT REQUIRED FOR ROW WORK),
 AT 303 BANYAN (BUT THAT APPLICATION GIVES THE PARCEL ID
 FOR 345 BANYAN, SO NOT CLEAR WHERE YOU ARE WORKING).
 THERE IS AN ISSUED BUILDING PERMIT FOR 345 BANYAN, BUT
 WORK IS SHOWN AT THAT LOCATION. IS THAT WORK SHOWN ON
 THE BUILDING PERMIT PLANS? IF NOT, THAT SHOULD BE A
 REVISION TO THE BUILDING PERMIT. WORK IS SHOWN AT 303
 BANYAN, AS WELL AS THE ROW. HAS A PERMIT BEEN APPLIED
 FOR AT THAT LOCATION?
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-01-23 Cont ID  
Sent By mpeterso Date 2023-01-23 Time 09:35 Rev Time 0.00
Received By mpeterso Date 2023-01-23 Time 09:35 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-05-20 Cont ID  
Sent By mpeterso Date 2022-05-20 Time 09:21 Rev Time 0.00
Received By mpeterso Date 2022-05-20 Time 09:12 Sent To  
Notes
2022-05-20 09:27:23SIGNATURE REVIEW FAILED
 1) PLAN LABELED E1.0.1 WITH TITLE BLOCKS OF MCVEGH &
 MAN GUM ENGINEERS AND KEITH SPINA ACHITECT HAVE TITLE
 BLOCKS WITH NO DIGITAL SIGNATURE
 2) REPORT LABLED STRUCTURAL REVIEW LETTER HAS A SEAL
 AND DIGITAL SIGNATURE BY CHELSEA MARAJH ENGINEER WITH A
 DIGITAL SIGNATURE THAT IS CORRUPTED AND CANNOT BE
 CERTIFIED
  
 PLEASE FOLLOW THE DIRECTIONS OUTLINED BELOW TO CORRECT
 THIS ISSUE.
  
 FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS OR DIGITALLY SEALED AND
 SIGNED.
  
 EITHER UPLOAD A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO THE SIGNATURE FOLDER WITH YOUR RESUBMITTAL (IF
 APPLICABLE) AND COMPLETE THE UPLOAD TASK IN PROJECTDOX,
 OR YOU CAN SUBMIT ONE ORIGINAL SIGNED AND SEALED PAPER
 ORIGINAL WITH A WET SIGNATURE TO THE BUILDING
 DEPARTMENT.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SIGNATURE DOCUMENTS ARE TYPICALLY REVIEWED WITHIN TWO
 BUSINESS DAYS AFTER SUBMITTAL; DIGITALLY SIGNED
 DOCUMENTS ARE PREFERRED.
 PLEASE EMAIL [email protected] AND CC TO
 [email protected] WITH ANY QUESTIONS
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-04-21 Cont ID  
Sent By jgomez Date 2022-04-21 Time 15:21 Rev Time 0.00
Received By jgomez Date 2022-04-21 Time 15:08 Sent To  
Notes
2022-04-21 15:31:06SIGNATURE REVIEW
  
 1- DRAWINGS WERE NOT SIGNED AND SEALED BY THE ENGINEER
 OF RECORD SHOWN ON THETTITLE BLOCK. DRAWINGS NEED TO BE
 SIGNED AND SEALED AS REQUIRED BY CHAPTER 471 F.S. WHEN
 SUBMITTING DRAWINGS/DOCUMENTS FOR PUBLIC RECORDS.
  
 NOTE: SUBMIT DRAWINGS ELECTRONICALLY WITH DIGITAL
 SIGNATURE OR PROVIDE HARD COPY WITH ORIGINAL SEAL AND
 SIGNATURE.
  
 2- WIND LOADING CALCULATIONS HAVE A COPY OF A DIGITAL
 SIGNATURE. DIGITAL SIGNATURES ARE NOT ALLOWED TO BE
 PRINTED. ALL DOCUMENTS PREPARED BY A LICENSED ENGINEER
 NEED TO HAVE THE ORIGINAL SEAL AND SIGNATURE OF THE
 ENGINEER OF RECORD AS REQUIRED BY SEC. 61G15-23.003 FAC
 AND CHAPTER 471 F.S. WHEN SUBMITTING PLANS/DOCUMENTS
 FOR PUBLIC RECORDS.
  
 NOTE: SUBMIT DRAWINGS ELECTRONICALLY WITH DIGITAL
 SIGNATURE OR PROVIDE HARD COPY WITH ORIGINAL SEAL AND
 SIGNATURE.
  
 ENGINEERS
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2023-02-01 Cont ID  
Sent By ckimmerl Date 2023-02-01 Time 09:30 Rev Time 0.00
Received By ckimmerl Date 2023-02-01 Time 09:30 Sent To  
Notes
2023-02-01 09:30:30PROVISO: SLIPFITTER SHALL BE SFX AND FIXTURE AND POLE
 SHALL BE BLACK.

Review Stop Z ZONING
Rev No 2 Status P Date 2022-04-20 Cont ID  
Sent By aaponte Date 2022-04-20 Time 11:14 Rev Time 0.00
Received By aaponte Date 2022-04-20 Time 11:14 Sent To  
Notes
2022-04-20 11:15:19PROVISO: SLIPFITTER SHALL BE SFX AND FIXTURE AND POLE
 SHALL BE BLACK.

Review Stop Z ZONING
Rev No 1 Status F Date 2022-03-04 Cont ID  
Sent By aaponte Date 2022-03-04 Time 10:42 Rev Time 0.00
Received By aaponte Date 2022-03-04 Time 10:41 Sent To  
Notes
2022-03-04 10:50:371. SPEC FOR POLE AND FIXTURE SHALL MATCH DOWNTOWN CITY
 STANDARD AS FOLLOWS: (S55-007)
 -35W32LED4K-T-GL-LE3-UNIV-DMG-SFX-RCD7-TN3-COLTX.
 2. POLE SHALL BE A MINIMUM OF 18 INCHES AWAY FROM THE
 FACE OF CURB.
 3. PLEASE CALL FOR FULL SPEC SHEET.
 FOR ADDITIONAL QUESTIONS PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439
  