Plan Review Details - Permit 21070007
Plan Review Stops For Permit 21070007
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-07-08 Cont ID  
Sent By tklarge Date 2021-07-08 Time 15:22 Rev Time 0.00
Received By tklarge Date 2021-07-02 Time 09:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-07-08 Cont ID  
Sent By tklarge Date 2021-07-12 Time 15:22 Rev Time 0.00
Received By tklarge Date 2021-07-08 Time 04:49 Sent To  
Notes
2021-07-08 09:47:021) SHT. P720 - SHOW THE SLOPE OF THE PIPE ON ALL PIPE
 SECTIONS. PIPE SIZING SHALL COMPLY WITH FBC-PLUMBING
 SEC.710 & TABLE 710.1(1).
 2)SHT. P720 - THERE IS AN 8 INCH SANITARY LINE WITH
 2,620 DFU'S DISCHARGING INTO IT. THE HORIZONTAL PORTION
 OF THIS DRAIN IS UNDERSIZED AT 1/8 PER FOOT SLOPE PER
 FBC-PLUMBING SEC. 710.1 AND TABLE 710.1 (1). SHOW THE
 SLOPE FOR THIS HORIZONTAL SECTION OF PIPE.
 3) SHT. P720 - THERE IS A 6 INCH HORIZONTAL SANITARY
 LINE SHOWING 218 DFU'S AND THEN THE DFU'S DECREASE TO
 192. THE FIXTURE LOAD SHOULD INCREASE SINCE THERE IS AN
 ADDITIONAL 4 INCH LINE CCONNECTED TO IT. CLARIFY.
 4) SHT. P720 - SHOW THE SLOPE OF THE SECTIONS OF 10
 INCH PIPE. THERE ARE NUMEROUS SECTIONS WITH NO SLOPE
 SHOWN. WPB AMEND. TO FBC SEC. 107.2.1.
 5) SHT. P720-THERE IS AN 8 INCH HORIZONTAL SANITARY
 LINE WITH 1,949 DFU'SS DISCHARGING INTO IT. THIS LINE
 IS UNDERSIZED AT 1/8 INCH SLOPE PER FBC-PLUMBING SEC.
 710.1 AND TABLE 710.1 (1). INDICATE THE SLOPE OF THE
 PIPE ON THE PLANS.WPB AMEND. TO FBC SEC. 107.2.1.
 6) SHT. P720 - THERE IS A 10 INCH SANITARY LINE ON THE
 PLANS THAT STATES " 10 INCH SANITARY UP, REFER TO CIVIL
 PLANS FOR CONT." IT APPEARS THIS IS AN UNDERGROUND LINE
 SO THE NOTE "10 INCH SANITARY UP" IS CONFUSING.
 CLARIFY. SHOW THE SLOPE OF THE PIPE ON THE PLANS. WPB
 AMEND. TO FBC SEC. 107.2.1.
 7) SHT. P720 - SHOW THE SHEET NUMBER ON RISER TAGS
 SS/P1 & SS/P60. ALSO, SHOW THE SLOPE OF THE 6 INCH
 HORIZONTAL SANITARY LINE WITH 126 DFU'S DISCHARGING
 INTO IT.WPB AMEND. TO FBC SEC. 107.2.1.
 8) SHT. P730 -THE 4 INCH HORIZONTAL STORM DRAIN FOR
 RISER RW/P7 THAT IS DRAINING 1,745 SQUARE FEET IS
 UNDERSIZED PER FBC-PLUMBING TABLE 1106.3. A MAXIMUM OF
 1,504 SQUARE FEET CAN BE COLLECTED ON A 4 INCH DRAIN AT
 1/8 OF AN INCH SLOPE.
 9) SHT. P730 - SHOW THE SLOPE OF THE HORIZONTAL STORM
 DRAIN PIPING ON ALL SECTIONS OF THE SYSTEM.WPB AMEND.
 TO FBC SEC. 107.2.1.
 10) SHT. P730 - THE 8 INCH HORIZONTAL STORM DRAIN FOR
 RISER RW/P4 THAT IS DRAINING 15,571 IS UNDERSIZED AT
 1/8 INCH SLOPE. A MAXIMUM OF 9,200 SQUARE FEET CAN BE
 DRAINED PER FBC-PLUMBING TABLE 1106.3.
 11) SHT. P730 - THE 12 INCH HORIZONTAL STORM DRAIN THAT
 IS DRAINING 28,931 IS UNDERSIZED AT A 1/8 INCH SLOPE. A
 MAXIMUM OF 26,650 SQUARE FEET CAN BE DRAINED AT AN 1/8
 INCH SLOPE PER FBC-PLUMBING TABLE 1106.3.
 12) SHT. P730 - 8 INCH RISER RW/R3 - IS THIS JUST FOR
 CONDENSATE? IT IS LABELED AS "RW" AND HAS FIXTURE FD-B
 ON IT. CLARIFY.
 13) SHT. P730 - SIZE THE HORIZONTAL STORM DRAIN FOR THE
 6 INCH RISER DRAINING 4,770 SQUARE FEET. A 6 INCH
 HORIZONTAL STORM DRAIN CAN DRAIN A MAXIMUM OF 4,280
 SQUARE FEET AT AN 1/8 INCH SLOPE SO THIS LINE IS
 UNDERSIZED PER FBC-PLUMBING TABLE 1106.3.
 14) SHT. P730 - THERE IS A 6 INCH HORIZONTAL DRAIN THAT
 IS DRAINING 2 RISERS THAT DRAIN 4,070 SQUARE FEET EACH.
 THIS LINE IS UNDERSIZED. A MAXIMUM OF 4,280 SQUARE FEET
 CAN BE DRAINED BY A 6 INCH LINE AT 1/8 INCH SLOPE.
 FBC-PLUMBING TABLE 1106.3.
 15) SHT. P730 - SHOW THE SLOPE OF THE PIPE FOR THE 12
 INCH HORIZONTAL DRAIN FOR RISER RW/P6. COMPLY WITH
 FBC-PLUMBING TABLE 1106.3.
 16) SHT. P730 - THE 6 INCH HORIZONTAL STORM DRAIN THAT
 IS DRAINING 5,585 SQUARE FEET IS UNDERSIZED. A MAXIMUM
 OF 4,280 SQUARE FEET CAN BE DRAINED AT 1/8 INCH SLOPE
 PER FBC-PLUMBING TABLE 1106.3. SHOW THE SLOPE OF THE
 DRAIN.
 17) THE RAINFALL RATE TO BE USED FOR TH DESIGN OF THE
 STORM DRAINAGE SYSTEM SHALL BE 5 INCHES PER
 FBC-PLUMBING FIGURE 1106.1. PLACE THIS INFORMATION ON
 THE PLAN.
 18) PLANS SHALLL BE DIGITALLY SIGNED AND SEALED PER FL.
 ADMIN. CODE RULE 61G15-223.004, 61G15-23.005.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-07-08 Cont ID  
Sent By tklarge Date 2021-07-08 Time 15:26 Rev Time 0.00
Received By tklarge Date 2021-07-08 Time 15:22 Sent To  
Notes
2021-07-08 15:27:22PLANS DO NOT APPEAR TO BEAR ELECTONIC SEAL AND SIGNAURE
 PERR FL. ADMIN. CODE RULE 61G15-223.004, 61G15-23.005.