Plan Review Details - Permit 21061866
Plan Review Stops For Permit 21061866
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2021-12-27 Cont ID  
Sent By lcrespo Date 2021-12-27 Time 08:13 Rev Time 0.00
Received By lcrespo Date 2021-12-27 Time 08:13 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2021-07-23 Cont ID  
Sent By ccole Date 2021-07-23 Time 14:34 Rev Time 0.00
Received By ccole Date 2021-07-23 Time 13:11 Sent To  
Notes
2021-07-23 14:35:032ND REVIEW FBC-2020 RES. FUEL GAS
 PERMIT-21061866
 7/23/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED. THE 1ST REVIEW COMMENTS 1-
 14 COPIED BELOW WERE NOT ADDRESSED. IN RESPONSE A
 GENERIC TANKLESS WATER HEATER PIPING DIAGRAM AND PIPE
 SIZING TABLE FROM WHAT APPEARS TO BE A WH MANUAL WERE
 UPLOADED. PLEASE COMPLY WITH THE COMMENTS.IF YOU NEED
 FURTHER ASSISTANCE PLEASE CONTACT ME- SEE INFO BELOW.
  
 1- SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2020 FBC FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2020 FBC FUEL GAS RES
 SECS. G2413.4.1, G2413.4.2.
 2- SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 3- TYPE OF GAS (LP OR NATURAL). WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 4- SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2020 FBC FUEL GAS SEC.
 409.4, FBC FUEL GAS RES. SEC. G2420.4.
 5- INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2020 FBC FUEL GAS SEC. 402.2 OR 2020
 FBC FUEL GAS RES. SEC. G2413.2.
 6- SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2020 FBC
 FUEL GAS SEC. 402.4.1 OR 2017 FBC FUEL GAS RES. SEC.
 G2413.4.1.
 7- SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2020 FBC FUEL GAS SEC.305.1 OR
 2020 FBC FUEL GAS RES. SEC. G2408.1.
 8- SUBMIT MANUFACTURE'?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2020 FBC FUEL GAS SEC.410.1 OR 2020 FBC
 FUEL GAS RES. SEC. G2421.1.
 9- THE COPY OF GAS TABLE 000.00 IS FROM AN OUTDATED
 FUEL GAS CODE. THE FUEL GAS CODE IN EFFECT IS THE 2020
 FBC FUEL GAS. SUBMIT TWO COPIES OF THE CORRECT SIZING
 TABLE. WPB AMENDMENTS TO THE FBC SEC. 107.2.1.
 10- INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER
 IS THE ONLY GAS APPLIANCE IN THIS SYSTEM? IF NOT,
 SUBMIT A COMPLETE GAS RISER SHOWING ALL PIPE SIZES,
 TYPE OF PIPE, THE DEVELOPED LENGTH TO THE FURTHEST GAS
 OUTLET, THE BTU LOAD OF EACH APPLIANCE, THE PSI OF THE
 SYSTEM, THE TYPE OF GAS AND THE TOTAL BTU LOAD ON THE
 SYSTEM. THESE REQUIREMENTS ALSO APPLY TO A NEW GAS
 SYSTEM. WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12)
 RESIDENTIAL GAS
 11- A SUB ELECTRICAL PERMIT IS REQUIRED FOR THE SOURCE
 OF IGNITION, WPB AMENDMENTS TO THE FBC SEC. 105.1
 12- SUBMIT A COPY OF A HOUSE PLAN SHOWING THE LOCATION
 OF THE TANKLESS WATER HEATER AND THE LOCATION AND
 DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN RELATION
 TO THE WATER HEATER. THE LOCATION OF THE WATER HEATER
 SHALL COMPLY WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND DRAWN. WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 13- INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER
 IS REPLACING AN EXISTING TANKLESS WATER HEATER OR IS IT
 REPLACING A STORAGE TANK TYPE WATER HEATER OR IS IT
 BEING ADDED TO THE EXISTING HOT WATER SYSTEM? INDICATE
 ON THE APPLICATION IN THE DESCRIPTION OF WORK. WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON
 CONSTRUCTION DOCUMENTS
  
 14- WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS ST.
 WEST PALM BEACH, FL. 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-07-16 Cont ID  
Sent By abelisle Date 2021-07-16 Time 17:47 Rev Time 0.00
Received By abelisle Date 2021-07-16 Time 17:09 Sent To  
Notes
2021-07-16 17:47:211ST REVIEW FBC-2020 PLUMBING
 PERMIT-21061866
 7/16/2021
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020
 FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH
 EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
 1- SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2020 FBC FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2020 FBC FUEL GAS RES
 SECS. G2413.4.1, G2413.4.2.
 2- SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 3- TYPE OF GAS (LP OR NATURAL). WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 4- SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2020 FBC FUEL GAS SEC.
 409.4, FBC FUEL GAS RES. SEC. G2420.4.
 5- INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2020 FBC FUEL GAS SEC. 402.2 OR 2020
 FBC FUEL GAS RES. SEC. G2413.2.
 6- SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2020 FBC
 FUEL GAS SEC. 402.4.1 OR 2017 FBC FUEL GAS RES. SEC.
 G2413.4.1.
 7- SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2020 FBC FUEL GAS SEC.305.1 OR
 2020 FBC FUEL GAS RES. SEC. G2408.1.
 8- SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2020 FBC FUEL GAS SEC.410.1 OR 2020 FBC
 FUEL GAS RES. SEC. G2421.1.
 9- THE COPY OF GAS TABLE 000.00 IS FROM AN OUTDATED
 FUEL GAS CODE. THE FUEL GAS CODE IN EFFECT IS THE 2020
 FBC FUEL GAS. SUBMIT TWO COPIES OF THE CORRECT SIZING
 TABLE. WPB AMENDMENTS TO THE FBC SEC. 107.2.1.
 10- INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER
 IS THE ONLY GAS APPLIANCE IN THIS SYSTEM? IF NOT,
 SUBMIT A COMPLETE GAS RISER SHOWING ALL PIPE SIZES,
 TYPE OF PIPE, THE DEVELOPED LENGTH TO THE FURTHEST GAS
 OUTLET, THE BTU LOAD OF EACH APPLIANCE, THE PSI OF THE
 SYSTEM, THE TYPE OF GAS AND THE TOTAL BTU LOAD ON THE
 SYSTEM. THESE REQUIREMENTS ALSO APPLY TO A NEW GAS
 SYSTEM. WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12)
 RESIDENTIAL GAS
 11- A SUB ELECTRICAL PERMIT IS REQUIRED FOR THE SOURCE
 OF IGNITION, WPB AMENDMENTS TO THE FBC SEC. 105.1
 12- SUBMIT A COPY OF A HOUSE PLAN SHOWING THE LOCATION
 OF THE TANKLESS WATER HEATER AND THE LOCATION AND
 DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN RELATION
 TO THE WATER HEATER. THE LOCATION OF THE WATER HEATER
 SHALL COMPLY WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND DRAWN. WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 13- INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER
 IS REPLACING AN EXISTING TANKLESS WATER HEATER OR IS IT
 REPLACING A STORAGE TANK TYPE WATER HEATER OR IS IT
 BEING ADDED TO THE EXISTING HOT WATER SYSTEM? INDICATE
 ON THE APPLICATION IN THE DESCRIPTION OF WORK. WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON
 CONSTRUCTION DOCUMENTS
 14- WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-12-27 Cont ID  
Sent By lcrespo Date 2021-12-27 Time 08:14 Rev Time 0.00
Received By lcrespo Date 2021-12-17 Time 09:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-12-27 Cont ID  
Sent By lcrespo Date 2021-07-23 Time   Rev Time 0.00
Received By lcrespo Date 2021-07-20 Time 09:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-07-19 Cont ID  
Sent By lmarchan Date 2021-07-19 Time 08:40 Rev Time 0.00
Received By lmarchan Date 2021-07-13 Time 10:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2021-12-27 Cont ID  
Sent By lcrespo Date 2021-12-27 Time 08:14 Rev Time 0.00
Received By lcrespo Date 2021-12-27 Time 08:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2021-07-23 Cont ID  
Sent By ccole Date 2021-07-23 Time 14:35 Rev Time 0.00
Received By ccole Date 2021-07-23 Time 13:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-07-16 Cont ID  
Sent By abelisle Date 2021-07-16 Time 17:47 Rev Time 0.00
Received By abelisle Date 2021-07-16 Time 17:09 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved