Plan Review Details - Permit 21061864
Plan Review Stops For Permit 21061864
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2021-10-18 Cont ID  
Sent By rmcdouga Date 2021-10-18 Time 10:11 Rev Time 0.00
Received By rmcdouga Date 2021-10-18 Time 10:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-08-23 Cont ID  
Sent By ppetty Date 2021-08-23 Time 12:43 Rev Time 0.00
Received By ppetty Date 2021-08-23 Time 12:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-10-22 Cont ID  
Sent By lcrespo Date 2021-10-22 Time 10:34 Rev Time 0.00
Received By lcrespo Date 2021-10-20 Time 09:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-10-18 Cont ID  
Sent By kalexand Date 2021-08-31 Time 13:14 Rev Time 0.00
Received By rmcdouga Date 2021-08-16 Time 11:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-10-22 Cont ID  
Sent By lcrespo Date 2021-10-22 Time 10:34 Rev Time 0.00
Received By lcrespo Date 2021-10-22 Time 10:34 Sent To  
Notes
2021-10-22 10:34:4910/22/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING/POOL)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-08-30 Cont ID  
Sent By lcrespo Date 2021-08-30 Time 14:06 Rev Time 0.00
Received By lcrespo Date 2021-08-30 Time 13:52 Sent To  
Notes
2021-08-30 14:06:1508/30/21 1ST POOL PLUMBING REVIEW**DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. WOULD YOU PLEASE SUBMIT TOTAL DYNAMIC HEAD
 CALCULATIONS FOR THE MAXIMUM SYSTEM FLOW COMPONENTS. IT
 REQUIRES THAT THE MAXIMUM SYSTEM FLOW RATE DOES NOT
 EXCEED THE LISTED MAXIMUM FLOW RATE OF THE SUCTION
 OUTLET FITTING ASSEMBLY (DRAIN COVER). THE TDH
 CALCULATIONS MUST INCLUDE ALL THE SYSTEM COMPONENTS,
 INCLUDING SUCTION AND RETURN PIPING, FITTINGS, VALVES,
 HEATER, FILTER, AND CHLORINATOR. ALL SYSTEM COMPONENTS
 EXCEPT THE PUMP PER THE ANSI/APSP/ICC 7 - 2015 SECS.
 4.4.9, 4.4.9.1 MAXIMUM SYSTEM FLOW RATE-UNSECURED
 CONTROL SYSTEMS.
  
 2. INDICATE ON THE PUMP CURVE WHICH CURVE KEY IS FOR
 THE PUMP BEING INSTALLED ON THIS SYSTEM PER THE WPB
 AMEND. TO FBC SEC. 107.2.1.
  
 3. HEAT PUMP POOL HEATERS SHALL HAVE A MINIMUM COP OF
 4.0 WHEN TESTED IN ACCORDANCE WITH AHRI 1160, TABLE 2,
 STANDARD RATING CONDITIONS - LOW AIR TEMPERATURE. A
 TEST REPORT FROM AN INDEPENDENT LABORATORY IS REQUIRED
 TO VERIFY PROCEDURE COMPLIANCE PER THE 2020 FBC-ENERGY
 - SEC. R 403.10.5.
  
 4. WOULD YOU PLEASE SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE MAIN DRAIN, THE PUMP, HEAT PUMP,
 FILTER AND CHLORINATOR PER THE WPB AMENDMENTS TO FBC
 SEC. 107.2.1.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-10-21 Cont ID  
Sent By rmcdouga Date 2021-10-21 Time 14:35 Rev Time 0.00
Received By rmcdouga Date 2021-10-21 Time 14:35 Sent To  
Notes
2021-10-21 14:37:23I UPLOADED THE DIGITALLY SIGNED PLANS THAT WERE EMAILED
 TO ME FROM THE ENGINEER. RM

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-10-18 Cont ID  
Sent By rmcdouga Date 2021-10-18 Time 12:49 Rev Time 0.00
Received By rmcdouga Date 2021-10-18 Time 12:49 Sent To  
Notes
2021-10-18 12:51:33THE ENGINEER'S DIGITAL SIGNATURE COULD NOT BE VERIFIED.
 ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ARCHITECT OR ENGINEER'S DIGITAL SIGNATURE ON THEM.
 YOU ALSO HAVE THE OPTION TO SUBMIT THE SIGNED AND
 SEALED PAPER VERSION OF DRAWINGS. AFTER THE ELECTRONIC
 PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT THE
 CORRESPONDING PAPER DRAWINGS AT THE BUILDING DEPARTMENT
 TO BE VERIFIED. THE ARCHITECT OR ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE
 DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE
 SIGNATURE ARE ACCEPTABLE. FS 487 & 61G1 OR FS 471 &
 61G15

Review Stop Z ZONING
Rev No 1 Status P Date 2021-08-31 Cont ID  
Sent By kalexand Date 2021-08-31 Time 12:56 Rev Time 0.00
Received By kalexand Date 2021-08-31 Time 13:13 Sent To  
Notes
***NONE***