| 2021-07-26 13:55:04 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE ARE NO INDICATIONS THAT THE BUILDINGS WILL |
| | REMIAN OCCUPIED, OR NOT OCCUPIED, DURING THE ANY PART |
| | OR ENTIRE CONSTUCTION PROCESS. |
| | |
| | PLEASE PROVIDE A DETAILED LIFE SAFETY PLAN AND INCLUDE |
| | AN APPLICABLE NOTE AS TO THE INTENT TO OCCUPY OR VACATE |
| | UNTIL ALL FINAL INSPECTIONS. |
| | |
| | SHOULD THE INTENT BE TO OCCUPY THE LIFE SAFETY PLAN |
| | SHALL INCLUDE SPECIFIC DETAILS TO PROTECT THE OCCUPANTS |
| | AND THAT ALL EXITS SHALL ARE FUNCTIONAL OR ALTENATE |
| | EXITS ARE PROVIDE WITHIN THE REQUIRMENTS OF THE LIFE |
| | SAFETY CODE. |
| | |
| | PER NFPA 241 |
| | |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | 1.1* SCOPE. THIS STANDARD SHALL APPLY TO STRUCTURES IN |
| | THE |
| | COURSE OF CONSTRUCTION, ALTERATION, OR DEMOLITION, |
| | INCLUDING |
| | THOSE IN UNDERGROUND LOCATIONS. |
| | 1.2 PURPOSE. THIS STANDARD IS INTENDED TO PRESCRIBE |
| | MINIMUM |
| | SAFEGUARDS FOR CONSTRUCTION, ALTERATION, AND DEMOLITION |
| | OPERATIONS |
| | IN ORDER TO PROVIDE REASONABLE SAFETY TO LIFE AND |
| | PROPERTY |
| | FROM FIRE DURING SUCH OPERATIONS. |
| | 1.3 APPLICATION. |
| | 1.3.1* THIS STANDARD PROVIDES MEASURES FOR PREVENTING |
| | OR |
| | MINIMIZING FIRE DAMAGE DURING CONSTRUCTION, ALTERATION, |
| | AND |
| | DEMOLITION OPERATIONS. |
| | |
| | CHAPTER 7 FIRE PROTECTION |
| | |
| | 7.1 FIRE SAFETY PROGRAM. |
| | 7.1.1 AN OVERALL CONSTRUCTION OR DEMOLITION FIRE SAFETY |
| | PROGRAM |
| | SHALL BE DEVELOPED. |
| | 7.1.2 ALL OF THE FOLLOWING ITEMS SHALL BE ADDRESSED IN |
| | THE FIRE |
| | SAFETY PROGRAM: |
| | (1) GOOD HOUSEKEEPING |
| | (2) ON-SITE SECURITY |
| | (3) FIRE PROTECTION SYSTEMS |
| | (A) FOR CONSTRUCTION OPERATIONS, INSTALLATION OF NEW |
| | FIRE |
| | PROTECTION SYSTEMS AS CONSTRUCTION PROGRESSES |
| | (B) FOR DEMOLITION OPERATIONS, PRESERVATION OF EXISTING |
| | FIRE PROTECTION SYSTEMS DURING DEMOLITION |
| | (4) ORGANIZATION AND TRAINING OF AN ON-SITE FIRE |
| | BRIGADE |
| | (5) DEVELOPMENT OF A PREFIRE PLAN WITH THE LOCAL FIRE |
| | DEPARTMENT |
| | (6) RAPID COMMUNICATION |
| | (7) CONSIDERATION OF SPECIAL HAZARDS RESULTING FROM |
| | PREVIOUS |
| | OCCUPANCIES |
| | (8) PROTECTION OF EXISTING STRUCTURES AND EQUIPMENT |
| | FROM EXPOSURE |
| | FIRES RESULTING FROM CONSTRUCTION, ALTERATION, AND |
| | DEMOLITION OPERATIONS |
| | 7.2 OWNER?S RESPONSIBILITY FOR FIRE PROTECTION. |
| | 7.2.1* THE OWNER SHALL DESIGNATE A PERSON WHO SHALL BE |
| | RESPONSIBLE |
| | FOR THE FIRE PREVENTION PROGRAM AND WHO SHALL ENSURE |
| | THAT IT IS CARRIED OUT TO COMPLETION. |
| | |
| | 8.2* SCAFFOLDING, SHORING, AND FORMS. |
| | 8.2.1 ACCUMULATIONS OF UNNECESSARY COMBUSTIBLE FORMS OR |
| | FORM LUMBER SHALL BE PROHIBITED. |
| | 8.2.2 COMBUSTIBLE FORMS OR FORM LUMBER SHALL BE BROUGHT |
| | INTO THE STRUCTURE ONLY WHEN NEEDED. |
| | 8.2.3 COMBUSTIBLE FORMS OR FORM LUMBER SHALL BE REMOVED |
| | FROM THE STRUCTURE AS SOON AS STRIPPING IS COMPLETE. |
| | 8.2.4 THOSE PORTIONS OF THE STRUCTURE WHERE COMBUSTIBLE |
| | FORMS ARE PRESENT SHALL NOT BE USED FOR THE STORAGE OF |
| | OTHER |
| | COMBUSTIBLE BUILDING MATERIALS. |
| | |
| | CHAPTER 10 SAFEGUARDING DEMOLITION OPERATIONS |
| | 10.1 GENERAL. IN ADDITION TO THE SPECIFIC REQUIREMENTS |
| | OF THIS |
| | CHAPTER, THE PROVISIONS OF CHAPTER 1 AND CHAPTERS 3 |
| | THROUGH 7 |
| | SHALL BE FOLLOWED, AS APPLICABLE, FOR ALL DEMOLITION |
| | OPERATIONS. |
| | |
| | PLEASE REVIEW AND PROVIDE SPECIFIC DETAILS AS |
| | APPLICABLE. |
| | |
| | |
| | |
| | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |