Plan Review Details - Permit 21061761
Plan Review Stops For Permit 21061761
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-08-24 Cont ID  
Sent By rmcphers Date 2021-08-24 Time 10:28 Rev Time 0.00
Received By rmcphers Date 2021-08-24 Time 10:28 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-07-21 Cont ID  
Sent By rmcphers Date 2021-07-21 Time 10:56 Rev Time 0.00
Received By rmcphers Date 2021-07-21 Time 10:56 Sent To  
Notes
2021-07-21 10:57:45PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-09-27 Cont ID  
Sent By rmcphers Date 2021-09-27 Time 08:56 Rev Time 0.00
Received By rmcphers Date 2021-09-27 Time 08:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-08-24 Cont ID  
Sent By rmcphers Date 2021-08-24 Time 10:27 Rev Time 0.00
Received By rmcphers Date 2021-08-24 Time 10:20 Sent To  
Notes
2021-08-24 10:27:23STORE REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) SALES COUNTER APPEARS TO HAVE 2 END CABINETS THAT
 EXTEND OUT FROM THE SALES COUNTER AREA - A CLEAR FLOOR
 SPACE OF 30"X48" IS REQUIRED FOR A SIDE APPROACH SEE
 FBC ACCESSIBILITY 305.2
 904.4.1 PARALLEL APPROACH.
 A PORTION OF THE COUNTER SURFACE THAT IS 36 INCHES (915
 MM) LONG MINIMUM AND 36 INCHES (915 MM) HIGH MAXIMUM
 ABOVE THE FINISH FLOOR SHALL BE PROVIDED. A CLEAR FLOOR
 OR GROUND SPACE COMPLYING WITH 305 SHALL BE POSITIONED
 FOR A PARALLEL APPROACH ADJACENT TO THE 36 INCH (915
 MM) MINIMUM LENGTH OF COUNTER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-07-21 Cont ID  
Sent By rmcphers Date 2021-07-21 Time 10:58 Rev Time 0.00
Received By rmcphers Date 2021-07-21 Time 10:26 Sent To  
Notes
2021-07-21 11:05:22STORE REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) PLEASE SHOW THE SALES COUNTER HEIGHT TO COMPLY WITH
 FBC (A) 904.4.1 PARALLEL APPROACH.
 A PORTION OF THE COUNTER SURFACE THAT IS 36 INCHES (915
 MM) LONG MINIMUM AND 36 INCHES (915 MM) HIGH MAXIMUM
 ABOVE THE FINISH FLOOR SHALL BE PROVIDED.
 2) PLEASE PROVIDE A NOTE ON THE DRAWINGS FOR THE WALL
 AND CEILING FINISHES FIRE CLASSIFICATION PER FBC 803.11
 INTERIOR FINISH REQUIREMENTS BASED ON GROUP.
 INTERIOR WALL AND CEILING FINISH SHALL HAVE A FLAME
 SPREAD INDEX NOT GREATER THAN THAT SPECIFIED IN TABLE
 803.11 FOR THE GROUP AND LOCATION DESIGNATED.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-09-29 Cont ID  
Sent By jleahy Date 2021-09-29 Time 11:54 Rev Time 0.00
Received By jleahy Date 2021-09-29 Time 11:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-08-30 Cont ID  
Sent By jleahy Date 2021-08-30 Time 12:17 Rev Time 0.00
Received By jleahy Date 2021-08-30 Time 12:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-07-20 Cont ID  
Sent By jleahy Date 2021-07-20 Time 12:25 Rev Time 0.00
Received By jleahy Date 2021-07-20 Time 12:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-09-24 Cont ID  
Sent By   Date 2021-09-24 Time   Rev Time 0.00
Received By bdolan Date 2021-09-24 Time 09:17 Sent To  
Notes
2021-09-24 09:18:18PASS FIRE V. 3
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-08-20 Cont ID  
Sent By   Date 2021-08-20 Time   Rev Time 0.00
Received By bdolan Date 2021-08-20 Time 14:45 Sent To  
Notes
2021-08-20 14:46:27PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-07-09 Cont ID  
Sent By   Date 2021-07-09 Time   Rev Time 0.00
Received By bdolan Date 2021-07-09 Time 14:49 Sent To  
Notes
2021-07-09 15:30:31THIS PLAN WAS REVIEWED AND APPROVED BY THE FIRE
 DEPARTMENT, WITH THE FOLLOWING COMMENTS:
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-09-29 Cont ID  
Sent By jleahy Date 2021-09-29 Time 11:54 Rev Time 0.00
Received By jleahy Date 2021-09-17 Time 09:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-08-30 Cont ID  
Sent By jleahy Date 2021-08-30 Time 12:17 Rev Time 0.00
Received By jleahy Date 2021-08-13 Time 09:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-07-21 Cont ID  
Sent By rmcphers Date 2021-07-21 Time 11:08 Rev Time 0.00
Received By rmcphers Date 2021-07-02 Time 10:46 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-09-27 Cont ID  
Sent By rmcphers Date 2021-09-27 Time 08:57 Rev Time 0.00
Received By rmcphers Date 2021-09-27 Time 08:57 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-08-24 Cont ID  
Sent By rmcphers Date 2021-08-24 Time 10:31 Rev Time 0.00
Received By rmcphers Date 2021-08-24 Time 10:31 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-07-21 Cont ID  
Sent By rmcphers Date 2021-07-21 Time 11:08 Rev Time 0.00
Received By rmcphers Date 2021-07-21 Time 11:08 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2021-09-23 Cont ID  
Sent By eschneid Date 2021-09-23 Time 15:51 Rev Time 0.25
Received By eschneid Date 2021-09-23 Time 15:51 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2021-08-19 Cont ID  
Sent By eschneid Date 2021-08-19 Time 17:08 Rev Time 0.25
Received By eschneid Date 2021-08-19 Time 17:08 Sent To  
Notes
2021-08-19 17:08:42SIGNS REQUIRE SEPARATE PERMIT.
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-07-14 Cont ID  
Sent By eshneide Date 2021-07-14 Time 11:58 Rev Time 0.25
Received By eschneid Date 2021-07-14 Time 11:49 Sent To  
Notes
2021-07-14 11:58:50FAILED
  
 1) THE LANDLORD APPROVAL STAMP IS REQUIRED ON THE
 PLANS. ALTERNATIVELY, A LETTER FROM THE LANDLORD
 LISTING THE APPROVED PLANS IS ACCEPTABLE.
  
 2) SIGNS REQUIRE SEPARATE PERMIT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  