| Plan Review Stops For Permit 21061748 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
N |
Date |
2021-09-17 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-09-17 |
Time |
08:07 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-09-17 |
Time |
08:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2021-08-09 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-08-09 |
Time |
10:34 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-08-09 |
Time |
10:34 |
Sent To |
|
|
| Notes |
| 2021-08-09 10:35:25 | NEW AC EQUIPMENT ON ROOF TOP | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE PROVIDE A STATEMENT ON THE DRAWINGS THAT THE | | | STRUCTURAL ROOF FRAMING COMPONENTS ARE ADEQUATE FOR THE | | | ADDITIONAL LOADS PER FBC EXISTING BUILDING 707.2 | | | ADDITION OR REPLACEMENT OF ROOFING OR REPLACEMENT OF | | | EQUIPMENT. WHERE ADDITION OR REPLACEMENT OF ROOFING OR | | | REPLACEMENT OF EQUIPMENT RESULTS IN ADDITIONAL DEAD | | | LOADS, STRUCTURAL COMPONENTS SUPPORTING SUCH REROOFING | | | OR EQUIPMENT SHALL COMPLY WITH THE GRAVITY LOAD | | | REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-07-23 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-07-23 |
Time |
08:01 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-07-22 |
Time |
15:44 |
Sent To |
|
|
| Notes |
| 2021-07-22 15:52:15 | NEW AC EQUIPMENT ON ROOF TOP | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE PROVIDE A STATEMENT ON THE DRAWINGS THAT THE | | | STRUCTURAL ROOF FRAMING COMPONENTS ARE ADEQUATE FOR THE | | | ADDITIONAL LOADS PER FBC EXISTING BUILDING 707.2 | | | ADDITION OR REPLACEMENT OF ROOFING OR REPLACEMENT OF | | | EQUIPMENT. WHERE ADDITION OR REPLACEMENT OF ROOFING OR | | | REPLACEMENT OF EQUIPMENT RESULTS IN ADDITIONAL DEAD | | | LOADS, STRUCTURAL COMPONENTS SUPPORTING SUCH REROOFING | | | OR EQUIPMENT SHALL COMPLY WITH THE GRAVITY LOAD | | | REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2021-08-10 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-08-10 |
Time |
11:45 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-08-10 |
Time |
11:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2021-11-30 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2021-11-30 |
Time |
08:49 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2021-11-15 |
Time |
16:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2021-09-27 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-09-27 |
Time |
07:29 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-09-07 |
Time |
10:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-08-10 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-08-10 |
Time |
14:20 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-08-03 |
Time |
13:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-07-23 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-07-23 |
Time |
08:12 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-06-30 |
Time |
08:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2021-11-16 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-11-16 |
Time |
09:11 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-11-16 |
Time |
09:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2021-09-07 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-09-07 |
Time |
11:06 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-09-07 |
Time |
11:05 |
Sent To |
|
|
| Notes |
| 2021-09-07 11:06:36 | PLEASE RESPOND TO 1ST CYCLE COMMENTS. | | | | | | THIS APPEARS TO BE CHANGING THE WAREHOUSE INTO RETAIL | | | SPACE. I DO NOT SEE ANY BATHROOMS FOR THIS NEW CHANGE | | | OF OCCUPANCY. I WOULD NEED TO SEE THE VENTILATION FO | | | RTHE NEW BATHROOMS IF THEY WILL BE REQUIRED. FBC | | | 107.2.1 FBC M TABLE 403.3.1.1 BATHROOM EXHAUST. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2021-08-09 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-08-09 |
Time |
08:38 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-08-06 |
Time |
11:35 |
Sent To |
|
|
| Notes |
| 2021-08-09 08:45:35 | THIS APPEARS TO BE CHANGING THE WAREHOUSE INTO RETAIL | | | SPACE. I DO NOT SEE ANY BATHROOMS FOR THIS NEW CHANGE | | | OF OCCUPANCY. I WOULD NEED TO SEE THE VENTILATION FO | | | RTHE NEW BATHROOMS IF THEY WILL BE REQUIRED. FBC | | | 107.2.1 FBC M TABLE 403.3.1.1 BATHROOM EXHAUST. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2021-07-02 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-07-02 |
Time |
16:49 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-07-02 |
Time |
14:26 |
Sent To |
|
|
| Notes |
| 2021-07-02 16:49:56 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21061748 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE CODE COMPLIANT DRAWINGS FOR THIS | | | BUILDING SHOWING THE SPACES BEING CONDITIONED. FBC | | | 107.2.1 | | | | | | 2) AS THE SPACE BEING CONDITIONED IS A WAREHOUSE PLEASE | | | PROVIDE THE ENERGY CALCULATIONS. FBC EC C402 | | | | | | 3) PLEASE SHOW THE ROOF ACCESS TO THE NEW RTU?S. FBC M | | | 306.5 | | | | | | 4) PLEASE PROVIDE AN OUTDOOR AIR CALCULATION FOR EACH | | | USE OF SPACE BASED ON THE FBC M 403.3.1.1 AND TABLE | | | 403.3.1.1 | | | | | | 5) PLEASE SHOW THE CONDENSATION PIPING AND THE | | | TERMINATION LOCATION. FBC M 307 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2021-11-29 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-11-29 |
Time |
10:13 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-11-29 |
Time |
10:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2021-09-27 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-09-27 |
Time |
07:29 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-09-24 |
Time |
12:30 |
Sent To |
|
|
| Notes |
| 2021-09-24 12:34:10 | 09/24/21 3RD PLUMBING REVIEW**DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. IT APPEARS TO BE CHANGING THE WAREHOUSE INTO RETAIL | | | SPACE. WE DO NOT SEE ANY BATHROOMS FOR THIS NEW CHANGE | | | OF OCCUPANCY. I WOULD NEED TO SEE THE NEW BATHROOMS IF | | | THEY WILL BE REQUIRED. PROVIDE PLUMBING FIXTURE | | | CALCULATIONS. PROVIDE A SCHEDULE ON THE PLAN SHOWING | | | THE REQUIRED AND PROVIDE A NUMBER OF FIXTURES PER TABLE | | | 403.3 FBC P. | | | | | | 2. IF UNDER THE SEPARATE PERMIT, PLEASE CLARIFY PER THE | | | WPB AMENDMENTS TO THE FBC SEC. 105.1. | | | | | | 3 PLEASE REFER TO MECHANICAL COMMENTS | | | | | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. | | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2021-08-10 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-08-10 |
Time |
14:03 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-08-10 |
Time |
14:03 |
Sent To |
|
|
| Notes |
| 2021-08-10 14:20:02 | | | | 08/10/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. IT APPEARS TO BE CHANGING THE WAREHOUSE INTO RETAIL | | | SPACE. WE DO NOT SEE ANY BATHROOMS FOR THIS NEW CHANGE | | | OF OCCUPANCY. I WOULD NEED TO SEE THE NEW BATHROOMS IF | | | THEY WILL BE REQUIRED. PROVIDE PLUMBING FIXTURE | | | CALCULATIONS. PROVIDE A SCHEDULE ON THE PLAN SHOWING | | | THE REQUIRED AND PROVIDE A NUMBER OF FIXTURES PER TABLE | | | 403.3 FBC P. | | | | | | 2. IF UNDER THE SEPARATE PERMIT, PLEASE CLARIFY PER THE | | | WPB AMENDMENTS TO THE FBC SEC. 105.1. | | | | | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. | | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2021-08-05 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-07-08 |
Time |
13:59 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-07-08 |
Time |
13:59 |
Sent To |
|
|
| Notes |
| 2021-07-08 14:00:35 | PLEASE ADDRESS CONDENSATE COMMENTS #5 ON MECHANICAL | | | REVIEW, |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2021-11-16 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2021-11-16 |
Time |
07:58 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2021-11-16 |
Time |
07:58 |
Sent To |
|
|
| Notes |
| 2021-11-16 07:58:33 | REVIEW OF SIGNATURE AND SEAL ON PAPER PLANS APPROVED, | | | ROUTED TO STORAGE |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2021-09-07 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-09-07 |
Time |
11:07 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-09-07 |
Time |
11:07 |
Sent To |
|
|
| Notes |
| 2021-09-07 11:08:37 | CANNOT SEE THE SIGNATURE OR SEAL OF THE ENGINEERS ON | | | THE ROOF LOAD EVALUATION. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2021-08-03 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-08-03 |
Time |
16:21 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-08-03 |
Time |
16:21 |
Sent To |
|
|
| Notes |
| 2021-08-03 16:22:04 | REVIEW OF SIGNATURE AND SEAL ON PAPER PLANS APPROVED | | | AND PLANS ROUTED TO STORAGE. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2021-07-01 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-07-01 |
Time |
15:45 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-07-01 |
Time |
15:45 |
Sent To |
|
|
| Notes |
| 2021-07-01 16:00:37 | ORIGINAL SIGNED AND SEALED PAPER DRAWING ROUTED TO | | | STORAGE.ME |
|
|