Plan Review Details - Permit 21061748
Plan Review Stops For Permit 21061748
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status N Date 2021-09-17 Cont ID  
Sent By rmcphers Date 2021-09-17 Time 08:07 Rev Time 0.00
Received By rmcphers Date 2021-09-17 Time 08:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-08-09 Cont ID  
Sent By rmcphers Date 2021-08-09 Time 10:34 Rev Time 0.00
Received By rmcphers Date 2021-08-09 Time 10:34 Sent To  
Notes
2021-08-09 10:35:25NEW AC EQUIPMENT ON ROOF TOP
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE A STATEMENT ON THE DRAWINGS THAT THE
 STRUCTURAL ROOF FRAMING COMPONENTS ARE ADEQUATE FOR THE
 ADDITIONAL LOADS PER FBC EXISTING BUILDING 707.2
 ADDITION OR REPLACEMENT OF ROOFING OR REPLACEMENT OF
 EQUIPMENT. WHERE ADDITION OR REPLACEMENT OF ROOFING OR
 REPLACEMENT OF EQUIPMENT RESULTS IN ADDITIONAL DEAD
 LOADS, STRUCTURAL COMPONENTS SUPPORTING SUCH REROOFING
 OR EQUIPMENT SHALL COMPLY WITH THE GRAVITY LOAD
 REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-07-23 Cont ID  
Sent By rmcphers Date 2021-07-23 Time 08:01 Rev Time 0.00
Received By rmcphers Date 2021-07-22 Time 15:44 Sent To  
Notes
2021-07-22 15:52:15NEW AC EQUIPMENT ON ROOF TOP
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE A STATEMENT ON THE DRAWINGS THAT THE
 STRUCTURAL ROOF FRAMING COMPONENTS ARE ADEQUATE FOR THE
 ADDITIONAL LOADS PER FBC EXISTING BUILDING 707.2
 ADDITION OR REPLACEMENT OF ROOFING OR REPLACEMENT OF
 EQUIPMENT. WHERE ADDITION OR REPLACEMENT OF ROOFING OR
 REPLACEMENT OF EQUIPMENT RESULTS IN ADDITIONAL DEAD
 LOADS, STRUCTURAL COMPONENTS SUPPORTING SUCH REROOFING
 OR EQUIPMENT SHALL COMPLY WITH THE GRAVITY LOAD
 REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-08-10 Cont ID  
Sent By jleahy Date 2021-08-10 Time 11:45 Rev Time 0.00
Received By jleahy Date 2021-08-10 Time 11:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-11-30 Cont ID  
Sent By lmarchan Date 2021-11-30 Time 08:49 Rev Time 0.00
Received By lmarchan Date 2021-11-15 Time 16:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-09-27 Cont ID  
Sent By lcrespo Date 2021-09-27 Time 07:29 Rev Time 0.00
Received By lcrespo Date 2021-09-07 Time 10:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-08-10 Cont ID  
Sent By lcrespo Date 2021-08-10 Time 14:20 Rev Time 0.00
Received By lcrespo Date 2021-08-03 Time 13:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-07-23 Cont ID  
Sent By rmcphers Date 2021-07-23 Time 08:12 Rev Time 0.00
Received By rmcphers Date 2021-06-30 Time 08:18 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2021-11-16 Cont ID  
Sent By medwards Date 2021-11-16 Time 09:11 Rev Time 0.00
Received By medwards Date 2021-11-16 Time 09:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2021-09-07 Cont ID  
Sent By medwards Date 2021-09-07 Time 11:06 Rev Time 0.00
Received By medwards Date 2021-09-07 Time 11:05 Sent To  
Notes
2021-09-07 11:06:36PLEASE RESPOND TO 1ST CYCLE COMMENTS.
  
 THIS APPEARS TO BE CHANGING THE WAREHOUSE INTO RETAIL
 SPACE. I DO NOT SEE ANY BATHROOMS FOR THIS NEW CHANGE
 OF OCCUPANCY. I WOULD NEED TO SEE THE VENTILATION FO
 RTHE NEW BATHROOMS IF THEY WILL BE REQUIRED. FBC
 107.2.1 FBC M TABLE 403.3.1.1 BATHROOM EXHAUST.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-08-09 Cont ID  
Sent By medwards Date 2021-08-09 Time 08:38 Rev Time 0.00
Received By medwards Date 2021-08-06 Time 11:35 Sent To  
Notes
2021-08-09 08:45:35THIS APPEARS TO BE CHANGING THE WAREHOUSE INTO RETAIL
 SPACE. I DO NOT SEE ANY BATHROOMS FOR THIS NEW CHANGE
 OF OCCUPANCY. I WOULD NEED TO SEE THE VENTILATION FO
 RTHE NEW BATHROOMS IF THEY WILL BE REQUIRED. FBC
 107.2.1 FBC M TABLE 403.3.1.1 BATHROOM EXHAUST.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-07-02 Cont ID  
Sent By medwards Date 2021-07-02 Time 16:49 Rev Time 0.00
Received By medwards Date 2021-07-02 Time 14:26 Sent To  
Notes
2021-07-02 16:49:561ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21061748
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE CODE COMPLIANT DRAWINGS FOR THIS
 BUILDING SHOWING THE SPACES BEING CONDITIONED. FBC
 107.2.1
  
 2) AS THE SPACE BEING CONDITIONED IS A WAREHOUSE PLEASE
 PROVIDE THE ENERGY CALCULATIONS. FBC EC C402
  
 3) PLEASE SHOW THE ROOF ACCESS TO THE NEW RTU?S. FBC M
 306.5
  
 4) PLEASE PROVIDE AN OUTDOOR AIR CALCULATION FOR EACH
 USE OF SPACE BASED ON THE FBC M 403.3.1.1 AND TABLE
 403.3.1.1
  
 5) PLEASE SHOW THE CONDENSATION PIPING AND THE
 TERMINATION LOCATION. FBC M 307
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2021-11-29 Cont ID  
Sent By lcrespo Date 2021-11-29 Time 10:13 Rev Time 0.00
Received By lcrespo Date 2021-11-29 Time 10:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2021-09-27 Cont ID  
Sent By lcrespo Date 2021-09-27 Time 07:29 Rev Time 0.00
Received By lcrespo Date 2021-09-24 Time 12:30 Sent To  
Notes
2021-09-24 12:34:1009/24/21 3RD PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. IT APPEARS TO BE CHANGING THE WAREHOUSE INTO RETAIL
 SPACE. WE DO NOT SEE ANY BATHROOMS FOR THIS NEW CHANGE
 OF OCCUPANCY. I WOULD NEED TO SEE THE NEW BATHROOMS IF
 THEY WILL BE REQUIRED. PROVIDE PLUMBING FIXTURE
 CALCULATIONS. PROVIDE A SCHEDULE ON THE PLAN SHOWING
 THE REQUIRED AND PROVIDE A NUMBER OF FIXTURES PER TABLE
 403.3 FBC P.
  
 2. IF UNDER THE SEPARATE PERMIT, PLEASE CLARIFY PER THE
 WPB AMENDMENTS TO THE FBC SEC. 105.1.
  
 3 PLEASE REFER TO MECHANICAL COMMENTS
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-08-10 Cont ID  
Sent By lcrespo Date 2021-08-10 Time 14:03 Rev Time 0.00
Received By lcrespo Date 2021-08-10 Time 14:03 Sent To  
Notes
2021-08-10 14:20:02 
 08/10/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. IT APPEARS TO BE CHANGING THE WAREHOUSE INTO RETAIL
 SPACE. WE DO NOT SEE ANY BATHROOMS FOR THIS NEW CHANGE
 OF OCCUPANCY. I WOULD NEED TO SEE THE NEW BATHROOMS IF
 THEY WILL BE REQUIRED. PROVIDE PLUMBING FIXTURE
 CALCULATIONS. PROVIDE A SCHEDULE ON THE PLAN SHOWING
 THE REQUIRED AND PROVIDE A NUMBER OF FIXTURES PER TABLE
 403.3 FBC P.
  
 2. IF UNDER THE SEPARATE PERMIT, PLEASE CLARIFY PER THE
 WPB AMENDMENTS TO THE FBC SEC. 105.1.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-08-05 Cont ID  
Sent By lcrespo Date 2021-07-08 Time 13:59 Rev Time 0.00
Received By lcrespo Date 2021-07-08 Time 13:59 Sent To  
Notes
2021-07-08 14:00:35PLEASE ADDRESS CONDENSATE COMMENTS #5 ON MECHANICAL
 REVIEW,

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-11-16 Cont ID  
Sent By mpeterso Date 2021-11-16 Time 07:58 Rev Time 0.00
Received By mpeterso Date 2021-11-16 Time 07:58 Sent To  
Notes
2021-11-16 07:58:33REVIEW OF SIGNATURE AND SEAL ON PAPER PLANS APPROVED,
 ROUTED TO STORAGE

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-09-07 Cont ID  
Sent By medwards Date 2021-09-07 Time 11:07 Rev Time 0.00
Received By medwards Date 2021-09-07 Time 11:07 Sent To  
Notes
2021-09-07 11:08:37CANNOT SEE THE SIGNATURE OR SEAL OF THE ENGINEERS ON
 THE ROOF LOAD EVALUATION.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-08-03 Cont ID  
Sent By ccole Date 2021-08-03 Time 16:21 Rev Time 0.00
Received By ccole Date 2021-08-03 Time 16:21 Sent To  
Notes
2021-08-03 16:22:04REVIEW OF SIGNATURE AND SEAL ON PAPER PLANS APPROVED
 AND PLANS ROUTED TO STORAGE.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-07-01 Cont ID  
Sent By medwards Date 2021-07-01 Time 15:45 Rev Time 0.00
Received By medwards Date 2021-07-01 Time 15:45 Sent To  
Notes
2021-07-01 16:00:37ORIGINAL SIGNED AND SEALED PAPER DRAWING ROUTED TO
 STORAGE.ME