Plan Review Details - Permit 21061741
Plan Review Stops For Permit 21061741
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2021-09-22 Cont ID  
Sent By jwitmer Date 2021-09-22 Time 13:44 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-09-24 Cont ID  
Sent By pvalenti Date 2021-09-24 Time 10:01 Rev Time 0.00
Received By pvalenti Date 2021-09-23 Time 09:12 Sent To  
Notes
2021-09-24 10:17:38 
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW APPROVED WITH PROVISOS:
 ALL SUB-PERMITS ARE REQUIRED PRIOR TO WORK UNDER THOSE
 PERMITS INCLUDING ROOFING.
 ALL SEPERATE PERMITS ARE REQUIRED PRIOR TO WORK UNDER
 THOSE PERMITS INCLUDING: PARKING/STRIPING, EXTERIOR
 SIGNAGE, EXTERIOR CANOPIES, DUMPSTER ENCLOSURES &
 GENERATOR.
 ALL SHOP DRAWINGS AND PRODUCT APPROVALS ARE REQUIRED TO
 BE SUBMITTED AS DEFERRED SUBMITTALS AND WILL HAVE TO BE
 REVIEW STAMP APPROVED BY DESIGNER OF RECORD.
 SPECIAL INSPECTOR WILL BE REQUIRED.
  
 FOR ALL WELDING CONNECTIONS PLEASE SEE NOTE BELOW:
 AWS D1.1 CLAUSE 5.2 & 6.7: AT TIME OF INSPECTION PLEASE
 PROVIDE A WELD PROCEDURE SPECIFICATION; THE W.P.S.
 SPECIFIES THE REQUIRED ESSENTIAL VARIABLES INCLUDING:
 BASE MATERIALS, JOINTS, PROCESS, AND FILLER METALS TO
 BE USED.
 AWS D1.1 CLAUSE 6.16: AT TIME OF INSPECTION PLEASE
 PROVIDE A WELDER PERFORMANCE QUALIFICATION RECORD; THE
 W.P.Q.R. PROVIDES INFORMATION WHICH CAN BE USED TO
 VERIFY THE WELDER?S QUALIFICATION AND CERTIFICATION AS
 IT RELATES TO THE WELDING REQUIREMENTS OF THE PROJECT.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-08-17 Cont ID  
Sent By pvalenti Date 2021-08-17 Time 16:07 Rev Time 0.00
Received By pvalenti Date 2021-08-12 Time 10:23 Sent To  
Notes
2021-08-17 16:09:08****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW DENIED:
  
 1) PROVIDE NOTES THAT INDICATE, DETAILS FOR THE
 PEDESTRIAN BRIDGE CAN BE FOUND ON THE PEDESTRIAN BRIDGE
 PERMIT # 21070960.
 IS THERE AN APPROVED PLAN/SUBMITTAL, FOR THE BRIDGE, BY
 A STATE OR FEDERAL AGENCY RELATED TO THE TRAIN SYSTEM?
  
 2) THE CORRIDOR ON THE LIFE SAFETY SHEET (B101) DOES
 NOT HAVE INDICATIONS OF WIDTHS/LENGTHS. THE CORRIDOR IS
 MISSING IDENTIFICATION ON THE PLAN SHEETS AS AN EXIT
 PASSAGEWAY. THIS WILL BE REQUIRED IF IT IS AN EXIT
 PASSAGEWAY, PENDING CLASSIFICATION OF SPACES AND
 REVISION OF THIS SHEET.
  
 3) THE LIFE SAFETY SHEET (B101) NEEDS TO BE REVISED.
 THE INFORMATION APPEARS TO HAVE CHANGED FROM MERCANTILE
 & WAREHOUSES TO RESTAURANTS AND OR ASSEMBLY. IN ORDER
 TO MOVE FORWARD, THIS NEEDS TO BE CLARIFIED AS TO WHAT
 IS THE INTENDED USE OF EACH SPACE.
  
 4) PROVIDE ALL SHOP DRAWINGS/PRODUCT APPROVALS
 INCLUDING:
 THE STEEL FRAMING AT THE PRESS ROOM, THE ROOFING
 SYSTEM, WINDOWS/DOORS, STOREFRONTS, ...
  
 5) A SUB-PERMIT IS REQUIRED FOR ROOFING.
  
 6) SEPARATE PERMITS ARE REQUIRED FOR: PARKING/STRIPING
 AT PARKING LOT, EXTERIOR SIGNAGE, EXTERIOR CANOPIES,
 DUMPSTER ENCLOSURES & GENERATOR.
  
 7) A DETAIL FOR THE REINFORCEMENT OF THE LOADING DOCK
 AREA ABOVE THE INTERCEPTORS IS REQUIRED AS THIS APPEARS
 TO BE AN AREA FOR VEHICLE TRAFFIC.
  
 8) A THOROUGH REVIEW COULD NOT BE COMPLETED AT THIS
 TIME AS MORE INFORMATION IS REQUIRED.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-10-12 Cont ID  
Sent By jleahy Date 2021-10-12 Time 15:26 Rev Time 0.00
Received By jleahy Date 2021-10-12 Time 15:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-08-11 Cont ID  
Sent By jleahy Date 2021-08-11 Time 13:07 Rev Time 0.00
Received By jleahy Date 2021-08-10 Time 16:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-07-20 Cont ID  
Sent By jleahy Date 2021-07-20 Time 15:20 Rev Time 0.00
Received By jleahy Date 2021-07-20 Time 15:16 Sent To  
Notes
2021-07-20 15:21:28 
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO ELECTRICAL PLANS INCLUDED.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2021-10-06 Cont ID  
Sent By rrossano Date 2021-10-06 Time   Rev Time 0.00
Received By rrossano Date 2021-10-06 Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2021-07-19 Cont ID  
Sent By rrossano Date 2021-07-19 Time   Rev Time 0.00
Received By rrossano Date 2021-07-19 Time   Sent To  
Notes
2021-07-19 12:31:10UNDER FORMAL ENGINEERING REVIEW (E20100035).
  
 THANKS,
 RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR, WEST PALM BEACH, FL
 33401
 DIRECT: (561) 494-1098, FAX: (561) 494-1116, MOBILE:
 (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-07-13 Cont ID  
Sent By pleduc Date 2021-07-13 Time   Rev Time 0.00
Received By pleduc Date 2021-07-08 Time 14:59 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2021-09-27 Cont ID  
Sent By lcrespo Date 2021-09-27 Time 09:41 Rev Time 0.00
Received By lcrespo Date 2021-09-27 Time 09:41 Sent To  
Notes
2021-09-27 09:42:1209/27/21 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2021-08-16 Cont ID  
Sent By lcrespo Date 2021-08-16 Time 18:14 Rev Time 0.00
Received By lcrespo Date 2021-08-16 Time 18:14 Sent To  
Notes
2021-08-16 18:14:5308/13/21 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-10-12 Cont ID  
Sent By lcrespo Date 2021-10-12 Time 16:07 Rev Time 0.00
Received By lcrespo Date 2021-09-21 Time 09:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-09-20 Cont ID  
Sent By lmarchan Date 2021-09-20 Time 10:16 Rev Time 0.00
Received By lmarchan Date 2021-07-01 Time 16:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-10-01 Cont ID  
Sent By medwards Date 2021-10-01 Time 09:10 Rev Time 0.00
Received By medwards Date 2021-10-01 Time 09:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-08-12 Cont ID  
Sent By medwards Date 2021-08-12 Time 16:27 Rev Time 0.00
Received By medwards Date 2021-08-11 Time 13:06 Sent To  
Notes
2021-08-12 16:27:352ND REVIEW FBC-2020 MECHANICAL
 PERMIT-21061741
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THIS IS A CHANGE OF USE FROM F-2 TO MERCANTILE.
 PLEASE PROVIDE THE ENERGY CALCULATIONS FOR THIS
 PROJECT. FBC EC C402.1
  
 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FOR THIS PROJECT. FBC EC C403.2.1
  
 3) SHEET M-001: THERE ARE 7 OUTDOOR UNITS BUT ONLY 5
 INDOOR UNITS LISTED. WHY ARE AHU-JS-05 AND AHU-JS-06
 MISSING FROM THE SHEET?
  
 4) PLEASE SHOW THE CONDENSATION PIPING FOR THE AHU?S
 AND THE RTU-21. PLEASE SHOW THE TERMINATION LOCATION
 FOR EACH. FBC M 307
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-07-13 Cont ID  
Sent By medwards Date 2021-07-13 Time 17:00 Rev Time 0.00
Received By medwards Date 2021-07-13 Time 17:00 Sent To  
Notes
2021-07-13 17:03:45I DO NOT SEE ANY DRAWINGS LABELED MECHANICAL NOR DO I
 SEE SHEETS NUMBERED 109, 110, 111, 112, 113, 114, 115.
 PLEASE EITHER EXPLAIN WHERE THESE DRAWINGS ARE LOCATED
 OR PROVIDE THESE DRAWINGS. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-10-12 Cont ID  
Sent By lcrespo Date 2021-10-12 Time 16:05 Rev Time 0.00
Received By lcrespo Date 2021-10-12 Time 14:00 Sent To  
Notes
2021-10-12 16:07:4510/12/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-08-16 Cont ID  
Sent By lcrespo Date 2021-08-16 Time 18:13 Rev Time 0.00
Received By lcrespo Date 2021-08-11 Time 16:00 Sent To  
Notes
2021-08-16 18:13:2108/16/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET G-103;
 A. UNDER THE PLUMBING SYSTEM, PLEASE PROVIDE THE
 OCCUPANCY LOAD AND REQUIRED NUMBER OF FIXTURES FOR THE
 STRUCTURE PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. IF A MOP SINK IS REQUIRES THE SURROUNDING THE WALL
 SHALL BE NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE
 2017 FBC BUILDING SEC. 1210.2.2 AND 2017 FBC SEC. P
 310.3. PLEASE MAKE A NOTE ON THIS SHEET.
  
 2. PLEASE NOTE THAT THE CITY OF WEST PALM BEACH
 REQUIRES A SEPARATE PERMIT FOR A GREASE INTERCEPTOR
 ALONG WITH AN ENGINEERING REVIEW. UNDER GREASE
 INTERCEPTOR, IT SAYS NOT NEEDED, BUT ON CIVIL AND
 ARCHITUAL, IT SHOWS TWO INTERCEPTORS. YOU MAY SUBMIT
 THE CALCULATION AT THIS TIME OR HAVE THE VERBIAGE OF
 HOW IT WILL BE DONE. WOULD YOU PLEASE CLARIFY PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 3. ON SHEET G-104;
  
 A. ON THE LABORATORY AND MIRRORS. WOULD YOU PLEASE SHOW
 THE REFLECTIVE PART OF THE MIRROR TO BE THE OF 40
 INCHES TO THE REFLECTIVE SIDE PER THE 2017 FBC ACC SEC.
 603.3.
  
 B. WOULD YOU PLEASE SHOW THE BOTTOM ON THE LAV AT A
 MINIMUM OF 27 INCHES KNEE CLEARANCE PER THE 2017 FBC
 SEC. 306.3.
  
 4. THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE ON THE WATER CLOSET PER THE 2017 FBC
 ACC SEC. 609.4.
  
 5. ON SHEET A-400;
  
 A. WOULD YOU PLEASE GIVE DIMENSIONS FOR FIXTURE
 CLEARANCES FOR LAV, WATER CLOSET PER FLORIDA BUILDING
 CODE AND FLORIDA ACCESSIBILITY CODE.
  
 B. WOULD YOU PLEASE SHOW THE 30 INCHES BY 48 INCHES
 INSIDE THE RUNNING RADIUS PER THE 2017 FBC ACC SEC. 305
 CLEAR FLOOR OR GROUND SPACE.
  
 C. WOULD YOU PLEASE PROVIDE A NOTE FOR DETAIL OF THE
 ACCESSIBLE ELEVATIONS DIMENSION ON G-104 PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 6. ON SHEET P-107;
  
 A. THIS MAY CHANGE DUE TO SIZING CALCULATION IN FUTURE
 SPACES. A. A SEPARATE PERMIT APPLICATION AND REVIEW ARE
 REQUIRED FROM ENGINEERING FOR THE GREASE INTERCEPTOR.
 AT THAT TIME, PLEASE PROVIDE GREASE INTERCEPTOR
 SPECIFICATIONS.
  
 B. TWO SAMPLING PORTS CANNOT BE SHARED PER THE CITY OF
 WEST PALM BEACH PUBLIC WORKS DEPARTMENT.
  
 C. ON THE ISOMETRIC, IT SHOWS A WATER CLOSET ON A TRUNK
 LINE WITHOUT BEING VENTED, AND THE END OF THE TRUCK
 LINE HAS A FUTURE LABELED. THE WATER CLOSET NEEDS TO BE
 VENTED FROM THE LAVS PER THE 2017 FBC SEC. 901.2.
  
 D. ON THE TWO WATER CLOSETS ON THE SECOND FLOOR, ONE
 NEEDS TO HAVE A VENT PER THE 2017 FC 901.2.1 VENTING
 REQUIRED.
  
 7. WOULD YOU PLEASE PROVIDE LISTED FIRE-STOPPING
 DETAILS FOR THE PIPPING THROUGH RATED WALLS AND THE
 FLOORS? WOULD YOU PLEASE SUBMIT THE COMPLETE ASSEMBLY
 DETAILS FOR THE SYSTEMS PER THE WPB AMENDMENTS TO FBC
 SEC. 107.2.1?
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-07-20 Cont ID  
Sent By tlarge Date 2021-07-20 Time 10:48 Rev Time 0.00
Received By lcrespo Date 2021-07-16 Time 08:18 Sent To  
Notes
2021-07-20 10:49:0107/20/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE PAGES FOR PLUMBING:- 057, 058, 059 ARE NOT
 PRESENT AS STATED ON THE REVISION 06 CHANGE DESCRIPTION
 TO THE SHOPS AT THE PRESS PROJECT WITH PERMIT NUMBERS
 19051045 (DEMO SCOPE) & 20030124 (PHASE 2, LANDLORD
 IMPROVEMENT SCOPE) THAT ARE DOCUMENTED IN REVISON 06.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2021-09-24 Cont ID  
Sent By pvalenti Date 2021-09-24 Time 08:23 Rev Time 0.00
Received By pvalenti Date 2021-09-23 Time 09:13 Sent To  
Notes
2021-09-24 08:25:59PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 ROOFING REVIEW:
  
 ROOFING SUB-PERMIT WILL BE REQUIRED PRIOR TO ANY
 ROOFING WORK.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2021-08-17 Cont ID  
Sent By pvalenti Date 2021-08-17 Time 16:27 Rev Time 0.00
Received By pvalenti Date 2021-08-17 Time 16:27 Sent To  
Notes
2021-08-17 16:29:43****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 ROOFING REVIEW DENIED:
  
 PROVIDE ALL PRODUCT APPROVALS FOR ROOFING MATERIALS TO
 BE USED AND A SUB-PERMIT FOR ROOF WORK.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-10-01 Cont ID  
Sent By medwards Date 2021-10-01 Time 09:20 Rev Time 0.00
Received By medwards Date 2021-10-01 Time 09:20 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-08-12 Cont ID  
Sent By medwards Date 2021-08-12 Time 17:03 Rev Time 0.00
Received By medwards Date 2021-08-12 Time 16:52 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2021-11-19 Cont ID  
Sent By jroach Date 2021-11-19 Time 13:17 Rev Time 0.00
Received By jroach Date 2021-11-19 Time 13:17 Sent To  
Notes
2021-11-19 13:17:531. SEPARATE PERMITS REQUIRED FOR SITE WORK (PARKING
 LOT), STRIPING, HARDSCAPE, LIGHTING, LANDSCAPING,
 IRRIGATION, ETC.
  
 2. THE PERMIT PLANS SHALL BE REVISED (AS NEEDED) TO
 REFLECT THE APPROVED PLANS ASSOCIATED WITH PB CASE NO.
 1086E & G.
  
 3. THE PROJECT IS SUBJECT TO ALL DEVELOPMENT ORDER
 CONDITIONS, AS OUTLINED IN RESOLUTION NO. 81-20, AS
 APPROVED BY THE CITY COMMISSION, AS MAY BE AMENDED, AS
 WELL AS THOSE CONDITIONS ASSOCIATED WITH PB CASE NOS.
 1086E & G, AS OUTLINED IN AN APPROVAL LETTER DATED
 NOVEMBER 2, 2021.
 _______________________________________________________
 _____________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 P: 561.822.1448 | E: [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2021-09-20 Cont ID  
Sent By jroach Date 2021-09-20 Time 10:08 Rev Time 0.00
Received By jroach Date 2021-09-20 Time 10:08 Sent To  
Notes
2021-09-20 10:08:27ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 09.20.2021
 PERMIT NO.: 21061741
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. THE REVISED SITE PLANS, ETC. ARE CURRENTLY BEING
 REVIEWED THROUGH THE MINOR DSI AMENDMENT PROCESS, AND
 NEARING COMPLETION. ONCE THE MINOR AMENDMENT HAS BEEN
 FINALIZED, ALL BUILDING PERMIT PLANS WILL NEED TO MATCH
 THE APPROVED PLANS. PLEASE ENSURE THAT ALL PLANS
 SUBMITTED ARE THE LATEST REVISIONS.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved