| 2021-07-21 11:54:57 | 07/21/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE |
| | MAXIMUM SYSTEM FLOW. THE MAXIMUM FLOW OF THE PUMP FROM |
| | ITS PUMP CURVE IS NO LONGER ALLOWED TO BE USED IN |
| | DETERMINING THE MAXIMUM SYSTEM FLOW RATE PER |
| | ANSI/APSP/ICC 7 - 2015 SECS. 4.4.9, 4.4.9.1. THE 2015 |
| | EDITION ADDRESSES THE FLOW RATE IN GALLONS PER MINUTE |
| | (GPM). IT REQUIRES THAT THE MAXIMUM SYSTEM FLOW RATE |
| | DOES NOT EXCEED THE LISTED MAXIMUM FLOW RATE OF THE |
| | SUCTION OUTLET FITTING ASSEMBLY (DRAIN COVER). THE TDH |
| | CALCULATIONS MUST INCLUDE ALL THE SYSTEM COMPONENTS |
| | INCLUDING SUCTION AND RETURN PIPING, FITTINGS, VALVES, |
| | HEATER, FILTER, AND CHLORINATOR. ALL SYSTEM COMPONENTS |
| | EXCEPT THE PUMP. |
| | |
| | 2. SUBMIT THE POOL PUMP CURVE. IDENTIFY ON THE PUMP |
| | CURVE WHICH CURVE KEY IS SPECIFIC TO THE PUMP BEING |
| | INSTALLED ON THIS POOL. THIS IS NEEDED TO CONFIRM THE |
| | MAXIMUM SYSTEM FLOW FROM THE TDH CALCULATIONS PER THE |
| | ANSI/APSP/ICC 7 - 2015 SECS. 4.4.9, 4.4.9.1 |
| | |
| | 3. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MAIN |
| | DRAIN, THE PUMP, FILTER AND CHLORINATOR PER THE WPB |
| | AMENDMENTS TO FBC SEC. 107.2.1. |
| | |
| | 4. A CONTAINMENT REDUCED PRINCIPAL ZONE BACKFLOW DEVICE |
| | WILL BE REQUIRED AT THE WATER METER BY A LICENSED |
| | CONTRACTOR WITH A SEPARATE PERMIT AND CERTIFIED BY THE |
| | CITY OF WEST PALM BEACH UTILITY DEPARTMENT PER THE |
| | CROSS CONNECTION CONTROL MANUAL PAGE. THE STRUCTURES |
| | ARE MULTI-FAMILY DWELLINGS, AND WATER USERS WILL BE |
| | REQUIRED TO INSTALL A BACKFLOW PREVENTION ASSEMBLY AT |
| | THE POINT OF DELIVERY. THE TYPE OF BACKFLOW ASSEMBLY |
| | REQUIRED WILL BE DEPENDENT UPON THE DEGREE OF HAZARD |
| | POSED BY THE WATER USER. THE HOME OWNER IS RESPONSIBLE |
| | FOR THIS, SO PLEASE GET IN TOUCH WITH THEM AT |
| | 561-822-2240. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |