| Plan Review Stops For Permit 21061700 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2021-08-12 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2021-08-12 |
Time |
11:12 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2021-08-12 |
Time |
11:03 |
Sent To |
|
|
| Notes |
| 2021-08-12 11:20:12 | DISCUSSED WITH SAMANTHA HILL AND LUIS CRESPO. NO | | | SEPARATE BUILDING PERMIT REQUIRED IF WORK IS ONLY FOR | | | THE DRYWALL REPAIR AT THE SHOWER AREA. JG. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-07-26 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-07-26 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-07-26 |
Time |
11:04 |
Sent To |
|
|
| Notes |
| 2021-07-26 11:13:01 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) PROVIDE A DRAWING TO SHOW THE SHOWER PAN AND SHOWER | | | WALLS. SPECIFY THE DIMENSIONS OF THE BATHROOM AND | | | PROPOSED SHOWER. THE ADDRESS OF THE PROJECT IS REQUIRED | | | ON THE DRAWINGS. FBC AMEND. 107.2 | | | | | | 2) A BUILDING PERMIT IS REQUIRED. FBC AMEND. 105.1 | | | | | | 3) NOTE: THE RELOCATION OF THE KITCHEN SINK MAY AFFECT | | | THE LOCATIONS OF THE COUNTERTOP ELECTRICAL RECEPTICLES. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
N |
Date |
2021-08-12 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-08-12 |
Time |
11:25 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-08-12 |
Time |
11:25 |
Sent To |
|
|
| Notes |
| 2021-08-12 11:26:37 | SEE PERMIT 21071522 FOR ELECTRICAL WORK JLEAHY |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2021-08-09 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-08-09 |
Time |
11:28 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-08-09 |
Time |
11:26 |
Sent To |
|
|
| Notes |
| 2021-08-09 11:30:17 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | MOVING THE SINK IN THE KITCHEN MUST HAVE EQUIPMENT | | | MOVING WITH IT DISPOSAL, DISHWASHER, ECT. ECT. | | | | | | NEED TO SHOW LAYOUT OF OUTLETS ON KITCHEN COUNTER. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2021-07-27 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-07-27 |
Time |
07:56 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-07-27 |
Time |
07:56 |
Sent To |
|
|
| Notes |
| 2021-07-27 07:58:00 | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | NEED TO SUBMIT A PLAN SHOWING THE ELECTRIC THAT IS | | | AFFECTED BY THIS REMODEL. JLEAHY |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-08-12 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2021-08-12 |
Time |
11:12 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2021-08-03 |
Time |
07:57 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-07-27 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-07-27 |
Time |
07:58 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-07-06 |
Time |
10:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2021-08-04 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-08-04 |
Time |
08:14 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-08-04 |
Time |
08:14 |
Sent To |
|
|
| Notes |
| 2021-08-04 08:58:29 | 08/04/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2021-07-08 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-07-08 |
Time |
11:16 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-07-08 |
Time |
11:03 |
Sent To |
|
|
| Notes |
| 2021-07-08 11:17:12 | 07/08/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. THE SCOPE OF WORK FOR REPLACING THE TUB WALLS WILL | | | REQUIRE A BUILDING PERMIT AND INSPECTION BY A LICENSED | | | CONTRACTOR PER THE WPB AMENDMENTS TO THE FBC SEC. | | | 105.1. | | | | | | 2. THE KITCHEN IS MOVING, SO PLEASE PROVIDE A PLUMBING | | | ISOMETRIC RISER DIAGRAM FOR SANITARY PER THE WPB | | | AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL | | | PLUMBING. | | | | | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. | | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|