Plan Review Details - Permit 21061686
Plan Review Stops For Permit 21061686
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-02-16 Cont ID  
Sent By rmcdouga Date 2022-02-16 Time 08:57 Rev Time 0.00
Received By rmcdouga Date 2022-02-16 Time 08:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-02-11 Cont ID  
Sent By rmcdouga Date 2022-02-11 Time 15:03 Rev Time 0.00
Received By rmcdouga Date 2022-02-11 Time 15:03 Sent To  
Notes
2022-02-11 15:53:46PLAN
 REVIEW COMMENTS
  
 3RD EVIEW: FBC SEVENTH EDITION (2020) ( APPLICATION
 DATE 6/28/2021)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 THERE ARE NO RECORDS OF PERMITS OR INSPECTIONS FOR THE
 SCOPE OF WORK CITED IN THE WEST PALM BEACH CODE
 ENFORCEMENT VIOLATION (CE 21060048).
  
 GENERAL AFTER THE FACT PERMITS:
 PLEASE BE ADVISED THE INSPECTOR MAY REQUIRE PREVIOUSLY
 COMPLETED WORK TO BE MADE ACCESSIBLE AND OPEN FOR
 INSPECTION OR REQUIRE ADDITIONAL DOCUMENTATION FOR ALL
 CONCEALED WORK PREVIOUSLY COMPLETED PURSUANT TO FBC 110
 & FBC 117.
 FBC 110.1 GENERAL - CONSTRUCTION OR WORK FOR WHICH A
 PERMIT IS REQUIRED SHALL BE SUBJECT TO INSPECTION BY
 THE BUILDING OFFICIAL AND SUCH CONSTRUCTION OR WORK
 SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION
 PURPOSES UNTIL APPROVED.
 FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR
 TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE
 TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN
 APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY.
  
 1) [ I COULD NOT LOCATE THE PROBABLE COST WORKSHEET
 THAT IS REFERENCED IN THE ARCHITECT'S RESPONSE LETTER.]
 [ NOT ADD ADDRESSED. SUBMIT A COST BREAK DOWN FOR ALL
 OF THE WORK THAT IS PROPOSED AND THAT WAS DONE WITHOUT
 PERMITS.] THE VALUATION FOR THE WORK IS SPECIFIED AS
 $2300.00 ON THE APPLICATION. THE VALUATION FOR THIS
 PROJECT IS THE VALUE OF ALL THE MATERIALS AND LABOR
 COST FOR ALL OF THE WORK THAT WAS DONE PLUS OVERHEAD
 AND PROFIT AS WOULD BE CHARGED BY A CONTRACTOR. THIS IS
 WHAT THE REPLACEMENT COST WOULD BE. BUILDING PERMIT
 VALUATION. FOR PERMITTING PURPOSES, VALUATION OF FBC
 109.3 BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2) [RESOLVED.]
  
 3) [ SUBMIT A COMPLETE MIAMI-DADE OR FLORIDA PRODUCT
 APPROVAL FOR THE WOOD EXTERIOR DOOR THAT IS SPECIFIED
 ON THE PLANS.] [PARTIALLY ADDRESSED. SUBMIT THE
 COMPLETE PRODUCT APPROVAL FOR THE EXTERIOR DOORS TO
 INCLUDE THE FL COVERSHEET, THE EVALUATION REPORT AND
 THE INSTALLATION INSTRUCTIONS.] FBC 107.3.4 - PROVIDE
 TWO SETS OF PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH
 ARE REGULATED BY FAC 61G20-3.001 PER FLORIDA STATUTE
 553.842 (5) THAT HAVE BEEN REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. PROVIDE TWO COMPLETE
 PRODUCT APPROVALS WITH FL OR NOA NUMBERS INCLUDING
 INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES
 FOR EACH OF THE DIFFERENT WINDOW TYPES (GLASS TYPES),
 STRUCTURAL MULLIONS AND EXTERIOR DOOR TYPES. ONLY ONE
 SET IS REQUIRED TO BE UPLOADED FOR ELECTRONICALLY
 SUBMITTED DOCUMENTS.
  
 4) [RESOLVED.]
  
 5) [ RESOLVED.]
  
 6) [RESOLVED.]
  
 7) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-11-16 Cont ID  
Sent By rmcdouga Date 2021-11-16 Time 15:42 Rev Time 0.00
Received By rmcdouga Date 2021-11-09 Time 09:02 Sent To  
Notes
2021-11-16 13:59:18PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020) ( APPLICATION
 DATE 6/28/2021)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 THERE ARE NO RECORDS OF PERMITS OR INSPECTIONS FOR THE
 SCOPE OF WORK CITED IN THE WEST PALM BEACH CODE
 ENFORCEMENT VIOLATION (CE 21060048).
  
 GENERAL AFTER THE FACT PERMITS:
 PLEASE BE ADVISED THE INSPECTOR MAY REQUIRE PREVIOUSLY
 COMPLETED WORK TO BE MADE ACCESSIBLE AND OPEN FOR
 INSPECTION OR REQUIRE ADDITIONAL DOCUMENTATION FOR ALL
 CONCEALED WORK PREVIOUSLY COMPLETED PURSUANT TO FBC 110
 & FBC 117.
 FBC 110.1 GENERAL - CONSTRUCTION OR WORK FOR WHICH A
 PERMIT IS REQUIRED SHALL BE SUBJECT TO INSPECTION BY
 THE BUILDING OFFICIAL AND SUCH CONSTRUCTION OR WORK
 SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION
 PURPOSES UNTIL APPROVED.
 FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR
 TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE
 TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN
 APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY.
  
 1) [NOT ADDRESSED. SUBMIT A COST BREAK DOWN FOR ALL OF
 THE WORK THAT IS PROPOSED AND THAT WAS DONE WITHOUT
 PERMITS.] THE VALUATION FOR THE WORK IS SPECIFIED AS
 $2300.00 ON THE APPLICATION. THE VALUATION FOR THIS
 PROJECT IS THE VALUE OF ALL THE MATERIALS AND LABOR
 COST FOR ALL OF THE WORK THAT WAS DONE PLUS OVERHEAD
 AND PROFIT AS WOULD BE CHARGED BY A CONTRACTOR. THIS IS
 WHAT THE REPLACEMENT COST WOULD BE. BUILDING PERMIT
 VALUATION. FOR PERMITTING PURPOSES, VALUATION OF FBC
 109.3 BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2) [NOT ADDRESSED.] FBC 107.3.5.3 - PROVIDE WIND DESIGN
 LOADS AND COMPONENT AND CLADDING DESIGN PRESSURES
 PURSUANT TO FBC-R301.2.
  
 3) [PARTIALLY ADDRESSED. SUBMIT THE COMPLETE PRODUCT
 APPROVAL FOR THE EXTERIOR DOORS TO INCLUDE THE FL
 COVERSHEET, THE EVALUATION REPORT AND THE INSTALLATION
 INSTRUCTIONS.] FBC 107.3.4 - PROVIDE TWO SETS OF
 PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE
 REGULATED BY FAC 61G20-3.001 PER FLORIDA STATUTE
 553.842 (5) THAT HAVE BEEN REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. PROVIDE TWO COMPLETE
 PRODUCT APPROVALS WITH FL OR NOA NUMBERS INCLUDING
 INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES
 FOR EACH OF THE DIFFERENT WINDOW TYPES (GLASS TYPES),
 STRUCTURAL MULLIONS AND EXTERIOR DOOR TYPES. ONLY ONE
 SET IS REQUIRED TO BE UPLOADED FOR ELECTRONICALLY
 SUBMITTED DOCUMENTS.
  
 4) [NOT ADDRESSED. SUBMIT PRODUCT APPROVALS OR SITE
 SPECIFIC ENGINEERING FOR THE AWNINGS OR SUBMIT UNDER A
 SEPARATE PERMIT.] FBC 107.34 - SUBMIT STRUCTURAL
 DETAILED DRAWINGS OR PRODUCT APPROVALS FOR THE PROPOSED
 WOOD CANOPIES AND AWNING SHOWN ON SHEET A-2.1.
  
 5) SPECIFY THE DIMENSIONS OF THE NEW CONCRETE PATIO ON
 THE PLANS. FBC 107.2.1
  
 6) SUBMIT A SURVEY THAT SHOWS THE LOCATION OF THE
 PROPOSED CONCRETE PATIO. FBC 107.2.1
  
 7) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-09-20 Cont ID  
Sent By rmcdouga Date 2021-09-20 Time 16:46 Rev Time 0.00
Received By rmcdouga Date 2021-09-20 Time 15:02 Sent To  
Notes
2021-09-20 15:07:08PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020) ( APPLICATION
 DATE 6/28/2021)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 THERE ARE NO RECORDS OF PERMITS OR INSPECTIONS FOR THE
 SCOPE OF WORK CITED IN THE WEST PALM BEACH CODE
 ENFORCEMENT VIOLATION (CE 21060048).
  
 GENERAL AFTER THE FACT PERMITS:
 PLEASE BE ADVISED THE INSPECTOR MAY REQUIRE PREVIOUSLY
 COMPLETED WORK TO BE MADE ACCESSIBLE AND OPEN FOR
 INSPECTION OR REQUIRE ADDITIONAL DOCUMENTATION FOR ALL
 CONCEALED WORK PREVIOUSLY COMPLETED PURSUANT TO FBC 110
 & FBC 117.
 FBC 110.1 GENERAL - CONSTRUCTION OR WORK FOR WHICH A
 PERMIT IS REQUIRED SHALL BE SUBJECT TO INSPECTION BY
 THE BUILDING OFFICIAL AND SUCH CONSTRUCTION OR WORK
 SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION
 PURPOSES UNTIL APPROVED.
 FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR
 TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE
 TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN
 APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY.
  
 1) THE VALUATION FOR THE WORK IS SPECIFIED AS $2300.00
 ON THE APPLICATION. THE VALUATION FOR THIS PROJECT IS
 THE VALUE OF ALL THE MATERIALS AND LABOR COST FOR ALL
 OF THE WORK THAT WAS DONE PLUS OVERHEAD AND PROFIT AS
 WOULD BE CHARGED BY A CONTRACTOR. THIS IS WHAT THE
 REPLACEMENT COST WOULD BE. BUILDING PERMIT VALUATION.
 FOR PERMITTING PURPOSES, VALUATION OF FBC 109.3
 BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE
 TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL,
 INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND
 DESIGN FEES, MARKETING COSTS, OVERHEAD AND PROFIT;
 EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS, ETC.), AS PUBLISHED BY INTERNATIONAL CODE
 CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE SET
 BY THE BUILDING OFFICIAL.
  
 2) FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS AND
 COMPONENT AND CLADDING DESIGN PRESSURES PURSUANT TO
 FBC-R301.2.
  
 3) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 WINDOW TYPES (GLASS TYPES), STRUCTURAL MULLIONS AND
 EXTERIOR DOOR TYPES. ONLY ONE SET IS REQUIRED TO BE
 UPLOADED FOR ELECTRONICALLY SUBMITTED DOCUMENTS.
  
 4) FBC 107.34 - SUBMIT STRUCTURAL DETAILED DRAWINGS OR
 PRODUCT APPROVALS FOR THE PROPOSED WOOD CANOPIES AND
 AWNING SHOWN ON SHEET A-2.1.
  
 5) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE
 COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION ON
 THE SUBMITTED PLANS. ADDITIONAL PLAN REVIEW COMMENTS
 MAY BE GENERATED WHEN MORE INFORMATION IS PROVIDED.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-11-15 Cont ID  
Sent By jleahy Date 2021-11-15 Time 07:54 Rev Time 0.00
Received By jleahy Date 2021-11-15 Time 07:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-09-07 Cont ID  
Sent By jleahy Date 2021-09-07 Time 16:02 Rev Time 0.00
Received By jleahy Date 2021-09-07 Time 16:02 Sent To  
Notes
2021-09-07 16:03:09ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED TO SUBMIT A RISER DIAGRAM, LOAD CALCULATION, AND
 PANEL SCHEDULE. 215.5

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2021-10-25 Cont ID  
Sent By lcrespo Date 2021-10-25 Time 07:35 Rev Time 0.00
Received By lcrespo Date 2021-10-25 Time 07:19 Sent To  
Notes
2021-10-25 07:35:24GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN
 THIS SUBMITTAL PACKAGE, AND A GAS PLAN REVIEW HAS NOT
 BEEN PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND
 PLANS WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE
 RELATED WORK. PROVIDE COMPLETE PLANS AND GAS RISER THAT
 REFLECTS THE ENTIRE SCOPE OF GAS WORK TO BE DONE PER
 THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 A SUB GAS PERMIT IS REQUIRED BY A LICENSED CONTRACTOR
 FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS TO THE FBC
 SEC. 105.1.
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-09-08 Cont ID  
Sent By lcrespo Date 2021-09-08 Time 15:56 Rev Time 0.00
Received By lcrespo Date 2021-09-08 Time 15:56 Sent To  
Notes
2021-09-08 18:22:1209/08/21 1 ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. GAS RISER DIAGRAM REQUIRED PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL GAS.
  
 2. WOULD YOU PLEASE SHOW THE CORRESPONDING EHD NUMBER
 OF THE CORRUGATED STAINLESS STEEL TUBING FOR EACH PIPE
 SIZE PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2020 FBC RES.
 SECS. G2413.4.1, G2413.4.2.
  
 4. WOULD YOU PLEASE PROVIDE WHAT TYPE OF GAS (LP OR
 NATURAL) IS BEING USED PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 5. INDICATE THE SYSTEM'S DELIVERY PRESSURE (PSI) ON THE
 PLAN PER THE 2020 FBC RES. SEC. G2413.2.
  
 6. THIS TANKLESS UNIT CALL FOR A 10.5? WATER COLUMN,
 AND THE SERVICE METER DISCHARGES IS A 12? WATER COLUMN
 REQUIRING A REGULATOR FOR THIS UNIT AS PER THE
 MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER?S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES.
 SEC. G2421.1.
  
 7. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM; ADD THE FUTURE, PLEASE. REFER
 TO THE 2020 FBC RES. SEC. G2413.
  
 8. SHOW THE DISTANCE FROM THE POINT OF DELIVERY (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2020 FBC
 RES. SEC. G2413.4.1.
  
 9. SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2020 FBC RES. SEC. G2408.1.
  
 10. WOULD YOU PLEASE SUBMIT A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANK-LESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER? THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE
 HAND-DRAWN PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 11. GAS UNITS MAY REQUIRE CONDENSATE, AND THEY NEED TO
 BE 1' AWAY FROM THE STRUCTURE PER THE 2020 FBC SEC
 R318.5. A NOTE ON ISO WILL BE OK.
  
 12. HOT WATER LINES NOT IN CONDITION SPACE NEED TO BE
 INSULATED WITH A MINIMUM R-3 PER THE 2020 FBC SEC. RE
 403.5.3. A NOTE ON ISO WILL BE OK.
  
 13. WOULD YOU PLEASE SHOW AND LABEL UNIONS IN FRONT OF
 REGULATOR 1? OF EITHER SIDE PER THE 2020 FBC RES. SEC
 G2421.2.
  
 14. WOULD YOU PLEASE SHOW AND LABEL THE SHUTOFF VALVE
 ON GAS ISOMERIC PER THE 2020 FBC FG SEC. 409.5 OR 2020
 FBC RES. SEC. G2420.5.
  
 15. THE SHUT-OFF INSIDE SHALL BE ACCESSIBLE WITHOUT
 MOVING THE EQUIPMENT PER THE 2020 FBC SEC. G2403 (202)
 GD, ACCESS. A NOTE ON ISO WILL BE OK.
  
 16. SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE
 DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR
 ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS
 SYSTEM PER THE 2020 FBC FG SEC. 402.3 OR 2020 FBC RES.
 SEC. G2413.3.
  
 17. SHOW AND LABEL DRIP LEG ON EQUIPMENT INSTALLED,
 EXCEPT FOR APPLIANCES, RANGE, DRYERS & OD GRILLS PER
 THE 2020 FBC FG 408.2 OR 2020 FBC RES. SEC. G2419.2.
  
 NOTE: YOU MAY CHOOSE TO HAVE A GAS REVIEW DONE THIS
 TIME AND ADDRESS THE COMMENTS ABOVE. THIS WILL HAVE THE
 GAS APPROVE FOR A SUB PERMIT, OR IF YOU DECIDED NOT TO
 ADDRESS THESE COMMENTS, PLEASE PUT A NOTE ON THE GAS
 HEATER (A SEPARATE PERMIT BY A LICENSED CONTRACTOR FOR
 THE GAS SYSTEM). THEN PLEASE TAKE OFF ANY GAS SHOWN ON
 PLANS; THESE COMMENTS CAN BE FORWARD TO THE GAS
 CONTRACTOR FOR REFERENCE. AN N WILL BE PUT ON THIS
 REVIEW, WHICH STANDS FOR NOT REQUIRED, BUT A SUB PERMIT
 WON'T BE ISSUED ONCE A REVIEW IS DONE FOR THAT SUB
 PERMIT, SO PLEASE BE ADVISED ON THIS PROCEDURE.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2022-02-02 Cont ID  
Sent By amhamilt Date 2022-02-02 Time 14:21 Rev Time 0.00
Received By amhamilt Date 2022-02-02 Time 14:21 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2021-10-28 Cont ID  
Sent By amhamilt Date 2021-10-28 Time 10:41 Rev Time 0.00
Received By amhamilt Date 2021-10-28 Time 10:41 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2021-09-15 Cont ID  
Sent By fmittner Date 2021-09-15 Time 10:48 Rev Time 0.00
Received By fmittner Date 2021-09-15 Time 10:48 Sent To  
Notes
2021-09-15 10:48:49WAITING ON HPB APPROVAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-02-16 Cont ID  
Sent By rmcdouga Date 2022-02-16 Time 09:07 Rev Time 0.00
Received By rmcdouga Date 2022-02-15 Time 07:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-02-11 Cont ID  
Sent By rmcdouga Date 2022-02-11 Time 15:27 Rev Time 0.00
Received By rmcdouga Date 2022-01-20 Time 09:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-12-01 Cont ID  
Sent By ajones Date 2021-12-01 Time 11:26 Rev Time 0.00
Received By ajones Date 2021-10-22 Time 10:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-09-20 Cont ID  
Sent By rmcdouga Date 2021-09-20 Time 16:46 Rev Time  
Received By rmcdouga Date 2021-08-17 Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-10-25 Cont ID  
Sent By medwards Date 2021-10-25 Time 09:32 Rev Time 0.00
Received By medwards Date 2021-10-25 Time 09:32 Sent To  
Notes
2021-10-25 09:34:54APPROVED WITH PRIVISO:
 MECHANICAL INSPECTOR TO VERIFY CONDENSATE DRAIN PIPE
 AND TERMINATION LOCATION MEETS FBC RES M1411.3
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-09-07 Cont ID  
Sent By medwards Date 2021-09-07 Time 06:45 Rev Time 0.00
Received By medwards Date 2021-09-07 Time 06:45 Sent To  
Notes
2021-09-07 06:49:28WE DO NOT HAVE A RECORD OF AN EXISTING PERMITTED
 MECHANICAL SYSTEM. WE WILL HAVE TO REVIEW THIS AS A NEW
 SYSTEM. PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS AND PROVIDE A MECHANICAL DRAWING SHOWING
 THE DUCT WORK. PLEASE ALSO SHOW THE APPLIANCE ANCHORING
 DETAIL FOR THE CONDENSING UNIT. SHOW ON THE MECHANICAL
 DRAWING THE CONDENSATE PIPING AND THE TERMINATION
 LOCATION. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-10-25 Cont ID  
Sent By lcrespo Date 2021-10-25 Time 07:34 Rev Time 0.00
Received By lcrespo Date 2021-10-25 Time 07:19 Sent To  
Notes
2021-10-25 07:34:5910/25/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-09-08 Cont ID  
Sent By lcrespo Date 2021-09-08 Time 17:13 Rev Time 0.00
Received By lcrespo Date 2021-09-08 Time 08:59 Sent To  
Notes
2021-09-08 17:59:5909/08/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET A1.2, IT IS A 40-GALLON ELECTRIC HEATER,
 BUT IT SHOWS A GAS HEATER ON THE HOUSE PLANS. WOULD YOU
 PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. HOT WATER LINES NOT IN CONDITION SPACE NEED TO BE
 INSULATED WITH A MINIMUM R-3 PER THE 2020 FBC SEC. RE
 403.5.3.
  
 3. CONDENSATE NEEDS TO BE 1' AWAY FROM THE STRUCTURE
 PER THE 2020 FBC SEC. R318.5.
  
 4. WASHING MACHINE VALVES MUST BE ACCESSIBLE FOR
 SHUTTING OFF WITHOUT MOVING UNITS, 2017 FBC SEC. R
 2903.9.3 FIXTURE VALVES AND ACCESS.
  
 5. WOULD YOU PLEASE PROVIDE A PLUMBING ISOMETRIC RISER
 DIAGRAM FOR SANITARY AND WATER PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL PLUMBING?
  
 6. A SUB GAS PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-02-16 Cont ID  
Sent By rmcdouga Date 2022-02-16 Time 08:57 Rev Time 0.00
Received By rmcdouga Date 2022-02-16 Time 08:57 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-02-11 Cont ID  
Sent By rmcdouga Date 2022-02-11 Time 15:26 Rev Time 0.00
Received By rmcdouga Date 2022-02-11 Time 15:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-11-09 Cont ID  
Sent By rmcdouga Date 2021-11-09 Time 08:02 Rev Time 0.00
Received By rmcdouga Date 2021-11-09 Time 08:02 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-08-18 Cont ID  
Sent By jleahy Date 2021-08-18 Time 08:25 Rev Time 0.00
Received By jleahy Date 2021-08-18 Time 08:25 Sent To  
Notes
2021-08-18 08:25:45SIGNATURE PLANS SENT TO STORAGE JLEAHY

Review Stop Z ZONING
Rev No 2 Status P Date 2022-02-02 Cont ID  
Sent By amhamilt Date 2022-02-02 Time 14:21 Rev Time 0.00
Received By amhamilt Date 2022-02-02 Time 14:21 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-12-01 Cont ID  
Sent By ajones Date 2021-12-01 Time 11:23 Rev Time 0.00
Received By ajones Date 2021-12-01 Time 11:23 Sent To  
Notes
***NONE***