| 2021-07-08 10:23:04 | PLAN REVIEW / NFIP |
| | |
| | CHRISTOPHER S. THROOP, C.B.O., CFM |
| | PLANS EXAMINER II PX3169/SFP306 |
| | INSPECTOR BN4338 |
| | BUILDING OFFICIAL BU1635 |
| | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | (561) 805-6726 |
| | [email protected] |
| | |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | CITY ORDINANCE NO. 4658-16 |
| | |
| | 2ND REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | NOTICE: PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. |
| | PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED |
| | SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN |
| | PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER |
| | PREVIOUS COMMENTS. |
| | |
| | PROPERTY IS LOCATED IN A SPECIAL FLOOD HAZARD AREA |
| | (SFHA). IT IS LOCATED IN ZONE AE WITH BASE FLOOD |
| | ELEVATIONS OF 6.0 FEET AND 7.0 FEET NAVD. DESIGN FLOOD |
| | ELEVATION SHALL BE NOT LESS THAN 9.0 FEET NAVD. |
| | |
| | 1. SECTION A6 CORRECTED |
| | |
| | 2. SECTION A9A) |
| | GARAGE SF IS INDICATED AS 572 SF. PLAN PAGE SP-1.01 |
| | STATES GARAGE SF IS 597 SF. PLEASE CORRECT. |
| | |
| | NEW COMMENT: |
| | REVISED PLAN PAGE SP-1.01 SUBMITTED FOR REVIEW. SUBMIT |
| | CHANGES TO APPROVED PLANS AS A REVISION TO MASTER |
| | PERMIT 19050988. |
| | NOTICE: FEMA REQUIRES THE SQUARE FOOTAGE OF THE GARAGE |
| | TO BE MEASURED ON THE OUTSIDE OF THE GARAGE. PLEASE |
| | RE-EVALUATE THE SQUARE FOOTAGE. SEE COMMENTS UNDER |
| | BLDG. REVIEW. |
| | |
| | 3. SECTION A9B) CORRECTED |
| | |
| | 4. SECTION B8 |
| | FLOOD ZONE SHOULD ONLY BE AE. (REMOVE THE REFERENCE TO |
| | ZONE X. ZONE X IS NOT A SPECIAL FLOOD HAZARD AREA) |
| | |
| | 5. SECTION B9 |
| | BASE FLOOD ELEVATIONS SHOULD BE 6.0 FEET AND 7.0 FEET |
| | NAVD. (REMOVE THE REFERENCE TO 0.2% ANNUAL CHANCE OF |
| | FLOOD. THIS PERTAINS TO ZONE X-500 WHICH IS NOT A |
| | SPECIAL FLOOD HAZARD AREA) |
| | |
| | 6. SECTION D |
| | INCLUDE THE FUTURE GENERATOR SHOWN ON PLAN PAGE SP-1.01 |
| | IN THE COMMENTS SECTION UNDER EQUIPMENT SERVICING THE |
| | BUILDING. |
| | (COMMENT FOR THE GENERATOR STATES "GENERATOR SLAB IS AT |
| | ELEVATION 9.6 NAVD AND BOTTOM OF THE GENERATOR IS AT |
| | ELEVATION 10.3 NAVD". PLEASE CLARIFY. |
| | |
| | NEW COMMENT: |
| | |
| | 7. PROVIDE A FINAL BOUNDRY LINE SURVEY PER FEMA EC |
| | INSTRUCTIONS ITEM C2. |
| | |
| | NOTICE: SUBMITTAL FOR FINISHED CONSTRUCTION EC SHOULD |
| | INCLUDE ONLY THE EC AND A FINAL BOUNDRY LINE SURVEY. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |