| 2021-08-25 15:59:18 | PARTIAL BUILDING DEMO ADD ROOF PORCH |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | 1) PLEASE PROVIDE COMPLETE PRODUCT APPROVALS FOR THE |
| | ROOFING TILE - PLEASE CIRCLE THE ROOFING TILE |
| | ATTACHMENT TO BE USED IN THE PRODUCT APPROVAL. FBC |
| | 1609.5.2 |
| | 2) PLEASE SHOW THE STAIR HANDRAIL EXTENSIONS ON THE |
| | WALL SIDE OF THE STAIR TO COMPLY WITH FBC 1014.6 |
| | |
| | THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A |
| | DEMO PERMIT PER FLORIDA BUILDING CODE, BUILDING 3303: |
| | |
| | 1. UTILITY RELEASE - FLORIDA POWER & LIGHT (ELECTRIC) |
| | RELEASE OF SERVICE CONFIRMATION |
| | |
| | 2. UTILITY RELEASE - FLORIDA PUBLIC UTILITIES (GAS) |
| | RELEASE OF SERVICE CONFIRMATION |
| | |
| | 3. UTILITY RELEASE - CITY OF WEST PALM BEACH WATER |
| | DEPARTMENT, REQUEST FOR METER PULL, ON THEIR FORM |
| | "DEMOLITION APPLICATION" |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED, |
| | THEN A PARTIAL RELEASE WILL BE NOTED ON THEIR FORM. |
| | |
| | FAX THE COMPLETED "DEMOLITION APPLICATION" FORM TO |
| | 561-822-2183. |
| | |
| | IF A BACKFLOW IS UTILIZED, AND THE BACKFLOW PERMIT IS |
| | NOT ALREADY FINALED, BEFORE SCHEDULING THE 703 FINAL |
| | INSPECTION, THE BACKFLOW DEVICE NEEDS TO BE TESTED AND |
| | CERTIFIED BY THE CITY'S UTILITIES DEPT, 561-822-2244. |
| | |
| | 4. SEWER LATERAL CAPPING PERMIT IS REQUIRED (SUBMIT |
| | APPLICATION TO BUILDING DIVISION); SCHEDULE A FINAL |
| | PLUMBING #703. |
| | |
| | 5. EXTERMINATION LETTER - LETTER FROM A LICENSED PEST |
| | CONTROL COMPANY STATING THAT DEMOLITION ADDRESS HAS |
| | BEEN INSPECTED AND/OR TREATED FOR RODENTS. |
| | |
| | 6. COMPLETE THE DEMO DEBRIS FORM: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | IF THE FORM IS NOT AVAILABLE ONLINE, SEND A REQUEST FOR |
| | THE FORM TO [email protected]. |
| | |
| | 7. PROVIDE A SITE PLAN OR SURVEY SHOWING LOCATION OF |
| | THE STRUCTURE(S) TO BE DEMOLISHED, FBC 107. |
| | |
| | 8. PROVIDE A STORMWATER POLLUTION PREVENTION PLAN. |
| | |
| | |