Plan Review Details - Permit 21061480
Plan Review Stops For Permit 21061480
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-08-23 Cont ID  
Sent By jwitmer Date 2021-08-23 Time 15:35 Rev Time 0.00
Received By jwitmer Date 2021-08-23 Time 15:35 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-07-25 Cont ID  
Sent By jwitmer Date 2021-07-25 Time 16:14 Rev Time 0.00
Received By jwitmer Date 2021-07-25 Time 16:00 Sent To  
Notes
2021-07-25 16:14:05TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected] THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-09-21 Cont ID  
Sent By jwitmer Date 2021-09-21 Time 07:51 Rev Time 0.00
Received By jwitmer Date 2021-09-15 Time 09:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-08-23 Cont ID  
Sent By jwitmer Date 2021-08-23 Time 15:42 Rev Time 0.00
Received By jwitmer Date 2021-08-23 Time 15:36 Sent To  
Notes
2021-08-23 15:42:08WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21061480
 ADD: 651 OKEECHOBEE BLVD. # 1203
 CONT: BOYNTON BCH. MARBLE & GRANITE/ TBD/ TO BE
 DETERMINED
 TEL: 561-
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. AUGUST 23RD/ 2021
 ACTION: DENIED
  
 4X FEE / NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B) .WITH
 RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
 1) 2ND REQUEST. NO CHANGE IN PLANS. THE MASTER BATH
 FLOOR PLAN BOTH THE GENERAL CONTRACTOR AND PLUMBING
 CONTRACTOR CAN NOT TAKE OWNERSHIP OF THE SAME PLAN.
 ONLY ONE CONTRACTOR CAN TAKE OWNERSHIP OF A PLAN.
 CERTIFICATION BY CONTRACTOR. 107.3.4.3. THE CONTRACTOR
 (QUALIFIER) THAT CREATED / DREW THE SET OF PLANS WILL
 NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS.
 PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE
 NUMBER FOR THE TRADE YOU ARE LICENSED IN AND PLANS
 DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
  
 2) 2ND REQUEST, NO CHANGE IN PLANS. THE SUBMITTED PLANS
 INDICATE WITH NOTE 1 THEY MEET OR EXCEED THE 2017 FBCB
 6TH EDITION PLEASE NOTE THE 2020 FBC-BUILDING CODE 7TH
 EDITION WAS ADOPTED DEC. 31/ 2020CODE REQUIREMENTS,
 PLEASE UPDATE YOUR PLANS. PLANS. THE 2020 FBC-BUILDING
 CODE
  
 3) 2ND REQUEST, NO CHANGE IN PLANS. PLEASE UPDATE THE
 NOTE 2 FOR THE CLASSIFICATION OF WORK LEVEL 1
 ALTERATIONS. LEVEL 1 ALTERATIONS IS EXCHANGING SURFACES
 LIKE FOR LIKE. THE FLOOR PLAN STATES ELIMINATING TUB
 AND CONVERTING TO A SHOWER. THIS BECOMES A LEVEL 2
 ALTERATION WITH THE CONVERSION FROM TUB TO SHOWER. 2020
 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 4) 2ND REQUEST, NO CHANGE IN PLANS. BOTH FLOOR PLANS
 FOR THE MASTER BATH AND KITCHEN STATE THE REPLACEMENT
 OF FLOOR TILE, NOTHING HAS BEEN SAID ABOUT THE FLOOR
 UNDERLAYMENT REQUIREMENTS. FLOOR INSULATION/
 UNDERLAYMENT (FBC-B 2020) FOR TILE, STONE, MARBLE,
 VINYL AND WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/
 NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 4A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 4B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 4C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE
 WORKING FROM CITY HALL
 MY WORK HOURS ARE MON. & TUES. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2021-07-25 Time 16:44 Rev Time 0.00
Received By jwitmer Date 2021-07-25 Time 16:00 Sent To  
Notes
2021-07-25 16:36:14WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21061480
 ADD: 651 OKEECHOBEE BLVD. # 1203
 CONT: BOYNTON BCH. MARBLE & GRANITE/ TBD/ TO BE
 DETERMINED
 TEL: 561-
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SUN. JULY 25TH/ 2021
 ACTION: DENIED
  
 1) THE MASTER BATH FLOOR PLAN BOTH THE GENERAL
 CONTRACTOR AND PLUMBING CONTRACTOR CAN NOT TAKE
 OWNERSHIP OF THE SAME PLAN. ONLY ONE CONTRACTOR CAN
 TAKE OWNERSHIP OF A PLAN. CERTIFICATION BY CONTRACTOR.
 107.3.4.3. THE CONTRACTOR (QUALIFIER) THAT CREATED /
 DREW THE SET OF PLANS WILL NEED TO IDENTIFY THEMSELVES
 AS THE AUTHOR OF THE PLANS. PLEASE PRINT YOUR NAME,
 SIGN YOUR NAME AND LICENSE NUMBER FOR THE TRADE YOU ARE
 LICENSED IN AND PLANS DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
  
 2) THE SUBMITTED PLANS INDICATE WITH NOTE 1 THEY MEET
 OR EXCEED THE 2017 FBCB 6TH EDITION PLEASE NOTE THE
 2020 FBC-BUILDING CODE 7TH EDITION WAS ADOPTED DEC. 31/
 2020CODE REQUIREMENTS, PLEASE UPDATE YOUR PLANS. PLANS.
 THE 2020 FBC-BUILDING CODE
  
 3) PLEASE UPDATE THE NOTE 2 FOR THE CLASSIFICATION OF
 WORK LEVEL 1 ALTERATIONS. LEVEL 1 ALTERATIONS IS
 EXCHANGING SURFACES LIKE FOR LIKE. THE FLOOR PLAN
 STATES ELIMINATING TUB AND CONVERTING TO A SHOWER. THIS
 BECOMES A LEVEL 2 ALTERATION WITH THE CONVERSION FROM
 TUB TO SHOWER. 2020 EXISTING BUILDING CODE. 801.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 4) BOTH FLOOR PLANS FOR THE MASTER BATH AND KITCHEN
 STATE THE REPLACEMENT OF FLOOR TILE, NOTHING HAS BEEN
 SAID ABOUT THE FLOOR UNDERLAYMENT REQUIREMENTS. FLOOR
 INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE, STONE,
 MARBLE, VINYL AND WOOD FLOORING ALL NEED TO HAVE HAD
 THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE
 FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS LISTED
 UNDER EACH OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR
 ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 4A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 4B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 4C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE
 WORKING FROM CITY HALL
 MY WORK HOURS ARE MON. & TUES. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2021-07-22 Cont ID  
Sent By jleahy Date 2021-07-22 Time 13:30 Rev Time 0.00
Received By jleahy Date 2021-07-22 Time 13:27 Sent To  
Notes
2021-07-22 13:30:42NOTES ON PLANS SHOW NO ELECTRICAL WORK JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-07-08 Cont ID  
Sent By pleduc Date 2021-07-08 Time   Rev Time 0.00
Received By pleduc Date 2021-07-08 Time 16:17 Sent To  
Notes
2021-07-08 16:18:09FIRE PROVISO:
  
 PROTECT FIRE SPRINKLERS AND FIRE ALARM DEVICES AND
 EQUIPMENT.
  
  
 DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM
 DEVICES/EQUIPMENT.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-10-12 Cont ID  
Sent By lcrespo Date 2021-10-12 Time 08:23 Rev Time 0.00
Received By lcrespo Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-09-28 Cont ID  
Sent By shill Date 2021-09-28 Time 14:59 Rev Time 0.00
Received By shill Date 2021-09-01 Time 07:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-08-23 Cont ID  
Sent By jwitmer Date 2021-08-23 Time 15:43 Rev Time 0.00
Received By jwitmer Date 2021-08-06 Time 10:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-07-25 Time 16:44 Rev Time 0.00
Received By cdecoeur Date 2021-07-07 Time 11:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2021-10-12 Cont ID  
Sent By lcrespo Date 2021-10-12 Time 08:23 Rev Time 0.00
Received By lcrespo Date 2021-10-12 Time 08:23 Sent To  
Notes
2021-10-12 08:27:3110/12/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2021-09-28 Cont ID  
Sent By lcrespo Date 2021-09-28 Time 13:17 Rev Time 0.00
Received By lcrespo Date 2021-09-24 Time 09:00 Sent To  
Notes
2021-09-28 13:17:5109/28/21 3RD PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 1. 3RD REQUEST- THIS BUILDING WAS CONSTRUCTED UNDER THE
 REQUIREMENTS OF THE FAIR HOUSING ACT. THE INDICATION ON
 THE PLANS IS NOT PROVIDED AS TO WHICH DESIGN
 SPECIFICATION ( "A" OR 'B" OF THE ACT) WAS USED IN THE
 ORIGINAL DESIGN OF THIS UNIT. THE UNITS THAT ARE BEING
 CONVERTED SEEM TO BE TYPE A, AND THE FAIR HOUSING ACT
 WILL NOT ALLOW THE CHAINING OF A TUB TO A SHOWER SINCE
 THEY ARE A FOWARD APPROACH. SPECIFICATION B BATHROOMS
 OFFER GREATER ACCESS TO THE TUB THAN SPECIFICATION A
 BATHROOMS. THE CASE HERE IS THAT THE TYPE OF UNIT CAN
 BE CHANGED WITH AN AFFIDAVIT THAT PROVIDES AN OPTION
 FOR CHANGING AN FHA COMPLIANCE STRUCTURE. THE OWNER AND
 DESIGNER OF RECORD ACKNOWLEDGE THAT THE PROPOSED
 BATHROOM DESIGN DOES NOT MEET THE FAIR HOUSING
 ACCESSIBILITY GUIDELINES REQUIREMENTS. THE OWNER AGREES
 TO REVERT THE UNIT BACK TO COMPLIANCE AT THE TIME OF
 SALE IF SO, REQUESTED BY THE BUYER. THIS WILL BE IN A
 LETTER-TYPE FORMAT SIGNED AND NOTARIZED BY THE OWNER.
 WE PROVIDE A SAMPLE LETTER, AND IT MUST BE SUBMITTED TO
 THE BUILDING DEPARTMENT OF THE CITY OF WPB. IF THIS
 OPTION IS CHOSEN, PLEASE SEND AN EMAIL TO
 [email protected], AND I WILL SEND A COPY OF THE FAIR
 HOUSING AFFIDAVIT.
  
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-08-23 Cont ID  
Sent By abelisle Date 2021-08-23 Time 07:33 Rev Time 0.00
Received By abelisle Date 2021-08-23 Time 06:55 Sent To  
Notes
2021-08-23 07:33:122ND REVIEW FBC-2020 PLUMBING
 PERMIT-21061480
 8/23/2021
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020
 FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH
 EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1- 2ND REQUEST- THIS BUILDING WAS CONSTRUCTED UNDER THE
 REQUIREMENTS OF THE FAIR HOUSING ACT. INDICATE ON THE
 PLANS WHICH DESIGN SPECIFICATION ( "A" OR 'B" OF THE
 ACT) WAS USED IN THE ORIGINAL DESIGN OF THIS UNIT.
 2- THE FAIR HOUSING GUIDLINES ALLOW A COUNTERTOP
 LAVATORY, WITH EITHER A REMOVABLE OR FIXED BASE
 CABINET, TO BE A MAXIMUM DEPTH OF 24". A WING OR
 PRIVACY WALL ALSO MAY OIVERLAP THE CLEAR FLOOR SPACE;
 HOWEVER, IT, TOO, IS RESTRICTED TO A LENGTH OF 24" AND
 MUST BE AT LEAST 33" FROM THE OPPOSITE WALL. FAIR
 HOUSING ACT DESIGN MANUAL 7.43
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-07-17 Cont ID  
Sent By abelisle Date 2021-07-17 Time 12:57 Rev Time 0.00
Received By abelisle Date 2021-07-17 Time 11:51 Sent To  
Notes
2021-07-17 12:26:181ST REVIEW FBC-2020 PLUMBING
 PERMIT-21061480
 7/17/2021
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020
 FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH
 EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1- THIS BUILDING WAS CONSTRUCTED UNDER THE REQUIREMENTS
 OF THE FAIR HOUSING ACT. INDICATE ON THE PLANS WHICH
 DESIGN SPECIFICATION ( "A" OR 'B" OF THE ACT) WAS USED
 IN THE ORIGINAL DESIGN OF THIS UNIT.
 2- 421.5.2SHOWER LINING.FLOORS UNDER SHOWER
 COMPARTMENTS, EXCEPT WHERE PREFABRICATED RECEPTORS HAVE
 BEEN PROVIDED, SHALL BE LINED AND MADE WATER TIGHT
 UTILIZING MATERIAL COMPLYING WITH SECTIONS 421.5.2.1
 THROUGH 421.5.2.6. SUCH LINERS SHALL TURN UP ON ALL
 SIDES NOT LESS THAN 2 INCHES (51 MM) ABOVE THE FINISHED
 THRESHOLD LEVEL. LINERS SHALL BE RECESSED AND FASTENED
 TO AN APPROVED BACKING SO AS NOT TO OCCUPY THE SPACE
 REQUIRED FOR WALL COVERING, AND SHALL NOT BE NAILED OR
 PERFORATED AT ANY POINT LESS THAN 1 INCH (25 MM) ABOVE
 THE FINISHED THRESHOLD. LINERS SHALL BE PITCHED
 ONE-FOURTH UNIT VERTICAL IN 12 UNITS HORIZONTAL
 (2-PERCENT SLOPE) AND SHALL BE SLOPED TOWARD THE
 FIXTURE DRAINS AND BE SECURELY FASTENED TO THE WASTE
 OUTLET AT THE SEEPAGE ENTRANCE, MAKING A WATER-TIGHT
 JOINT BETWEEN THE LINER AND THE OUTLET. THE COMPLETED
 LINER SHALL BE TESTED IN ACCORDANCE WITH SECTION 312.9.
 3- THE CURRENT CODE CYCLE IS THE FLORIDA BUILDING CODE
 SEVENTH EDITION 2020, WPB AMENDMENTS TO THE FBC SEC.
 107.2.1.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-09-28 Cont ID  
Sent By lcrespo Date 2021-09-28 Time 13:39 Rev Time 0.00
Received By lcrespo Date 2021-09-28 Time 13:39 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-08-23 Cont ID  
Sent By jwitmer Date 2021-08-23 Time 15:43 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2021-08-23 15:43:26NO CHANGE IN PLANS, SEE 2ND BUILDING REVIEW. J. WITMER

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-07-25 Cont ID  
Sent By jwitmer Date 2021-07-25 Time 16:44 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2021-07-25 16:38:19SEE BUILDING REVIEW ABOUT SIGNATURES.