| 2021-07-01 09:50:15 | 07/01/21 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | |
| | 1. NOTE: THE CITY OF WEST PALM BEACH HAS NO RECORD OF |
| | EXISTING GAS. A FULL EVALUATION OF ALL GAS EQUIPMENT |
| | WILL BE DONE AT THE FIELD, AND IF NOT TO CODE, IT MAY |
| | NEED TO BE BOUT UP TO CODE COMPLIANCE AT THE OWNER'S |
| | EXPENSE. |
| | |
| | 2. PLEASE PROVIDE THE SIGNATURE OF ALL INFORMATION, |
| | DRAWINGS, SPECIFICATIONS, AND ACCOMPANYING DATA THAT |
| | SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN PER THE WPB AMENDMENTS TO |
| | THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 3. PLEASE CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS |
| | OF PIPE PER 2020 FBC RES. SECS. G2413.4.1, G2413.4.2. |
| | |
| | 4. SHOW THE DISTANCE FROM THE POINT OF DELIVERY (GAS |
| | METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2020 FBC |
| | RES. SEC. G2413.4.1. THE 14 FT PROVIDED IS NOT CORRECT. |
| | SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE |
| | APPLIANCE. COMPLY WITH 2020 FBC FG RES. TABLE G2413.4 |
| | (12) FOR THE PROPER PIPE SIZE AND BTU LOAD. |
| | |
| | 5. PLEASE PROVIDE SIZE OF PIPE FROM METER TO DRYER AREA |
| | PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1. |
| | |
| | 6. SUBMIT MANUFACTURER?S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH 2020 FBC RES. SEC. G2408.1. |
| | |
| | 7. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| | BTU LOAD ON THE SYSTEM. REFER TO THE 2020 FBC RES. SEC. |
| | G2413. ( THE GAS DRYER HAS NO BTU?S AND THE TOTAL IS |
| | NOT CLEAR) |
| | |
| | 8. THIS HOME HAS AN EXISTING GAS METER AND EQUIPMENT. |
| | THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED |
| | TO THE SYSTEM'S TOTAL BTU LOAD TO ENSURE THE EXISTING |
| | SYSTEM IS SIZED CORRECTLY. IF UNDERSIZED, THE EXISTING |
| | SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING |
| | SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS |
| | THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH |
| | APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH |
| | APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF |
| | PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| | OUTLET AND THE LOAD OF THE SECTION PER THE 2020 FBC |
| | RES. SECS. G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. |
| | |
| | |
| | 9. PLEASE LABEL REGULATOR PER THE 2020 FBC RES. SEC |
| | G2421.2. |
| | |
| | 10. PLEASE SHOW AND LABEL DRIP LEG AND SHUTOFF VALVES |
| | ON GAS ISOMETRIC PER THE 2020 FBC RES. SEC. G2419.2. |
| | |
| | 11. THE SHUT OFF INSIDE SHALL BE ACCESSIBLE WITHOUT |
| | MOVING THE EQUIPMENT PER THE 2020 FBC SEC. G2403 (202) |
| | GD, ACCESS. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |