Plan Review Details - Permit 21061258
Plan Review Stops For Permit 21061258
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2021-07-29 Cont ID  
Sent By rmcdouga Date 2021-07-29 Time 07:49 Rev Time 0.00
Received By rmcdouga Date 2021-07-29 Time 07:44 Sent To  
Notes
2021-07-29 07:54:40THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10
 FEET FROM ANY OPENINGS INTO A BUILDING.
 R303.5.1 INTAKE OPENINGS
 MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS
 SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM
 ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS,
 CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS
 AND LOADING DOCKS.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-07-21 Cont ID  
Sent By jleahy Date 2021-07-21 Time 20:34 Rev Time 0.00
Received By jleahy Date 2021-07-21 Time 20:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-08-24 Cont ID  
Sent By lmarchan Date 2021-08-24 Time 15:17 Rev Time 0.00
Received By lmarchan Date 2021-07-16 Time 11:36 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-07-29 Cont ID  
Sent By rmcdouga Date 2021-07-29 Time 07:49 Rev Time 0.00
Received By rmcdouga Date 2021-07-29 Time 07:44 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-08-23 Cont ID  
Sent By rthermid Date 2021-08-23 Time   Rev Time  
Received By rthermid Date 2021-08-23 Time   Sent To I
Notes
2021-08-23 09:40:36GENERATOR MUST BE A MINIMUM OF 4 FEET FROM THE SIDE
 PROPERTY LINE.