Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2021-06-23 Time   Rev Time 0.00
Received By bdolan Date 2021-06-23 Time 11:58 Sent To  
Notes
2021-06-23 12:00:44THE FOLLOWING COMMENTS WERE SUBMITTED BY LIEUTENANT
 BRIAN DOLAN, BUREAU OF FIRE PREVENTION, WEST PALM BEACH
 FIRE RESCUE:
  
 25.2.1.5 WHERE ADDITION OR MODIFICATION IS MADE TO AN
 EXISTING SYSTEM AFFECTING MORE THAN 20 SPRINKLERS, THE
 NEW PORTION SHALL BE ISOLATED AND TESTED AT NOT LESS
 THAN 200 PSI (13.8 BAR) FOR 2 HOURS.
  
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]