Plan Review Details - Permit 21061171
Plan Review Stops For Permit 21061171
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-06-18 Cont ID  
Sent By cpuell Date 2021-06-18 Time 16:03 Rev Time 0.00
Received By cpuell Date 2021-06-18 Time 16:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-06-14 Cont ID  
Sent By cthroop Date 2022-06-14 Time 14:27 Rev Time 0.00
Received By cthroop Date 2022-06-14 Time 13:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-01-18 Cont ID  
Sent By cthroop Date 2022-01-18 Time 16:22 Rev Time 0.00
Received By cthroop Date 2022-01-18 Time 16:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-12-14 Cont ID  
Sent By cthroop Date 2021-12-14 Time 10:51 Rev Time 0.00
Received By cthroop Date 2021-12-09 Time 11:30 Sent To  
Notes
2021-12-14 10:56:43PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: THE LEGAL ADDRESS FOR THIS PROPERTY IS 200
 ARKONA CT. ADDRESS WAS CORRECTED ON COVER PAGE AND SP
 PAGES.
  
  
 1. MAIN DRAIN GRATE AND FRAME SHALL COMPLY WITH FBC
 454.1.5.5.10.2 AND ANSI/APSP 16.
 SUBMIT NEW MAIN GRATE SPECS.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-07-23 Cont ID  
Sent By cthroop Date 2021-07-23 Time 11:19 Rev Time 0.00
Received By cthroop Date 2021-07-23 Time 09:57 Sent To  
Notes
2021-07-23 11:19:20PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 INSUFFICIENT INFORMATION. CLARIFY ADDRESS AND SCOPE OF
 WORK (SOW)
  
 1. PROJECT ADDRESS ON PERMIT APP. IS 200 ARKONA CT.
 ADDRESS ON PLANS IS 1515 S FLAGLER DR.
 PCN 7443432783001000 IS FOR 1515 S FLAGLER DR.
 PLEASE CLARIFY?
  
 2. SOW ON APP. STATES FOUNTAIN INTERIOR FINISH AND
 TILE.
 PLANS INDICATE NEW CONSTRUCTION.
 PLEASE CLARIFY?
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-04-22 Cont ID  
Sent By fgiaquin Date 2022-04-22 Time 23:00 Rev Time 0.00
Received By fgiaquin Date 2022-04-22 Time 22:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-11-18 Cont ID  
Sent By jleahy Date 2021-11-18 Time 13:56 Rev Time 0.00
Received By jleahy Date 2021-11-18 Time 13:53 Sent To  
Notes
2021-11-18 13:57:51ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 COULD NOT FIND THE EQUIPMENT WITH WIRE SIZES AND
 BREAKER SIZES.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-06-28 Cont ID  
Sent By fgiaquin Date 2021-06-28 Time 23:20 Rev Time 0.00
Received By fgiaquin Date 2021-06-28 Time 22:23 Sent To  
Notes
2021-06-28 23:20:34ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NOT ENOUGH INFORMATION SUBMITTED. WHERE ARE WIRE
 SIZES, OCP, CONDUIT SIZES FOR POOL EQUIPMENT? FBC
 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2022-07-14 Cont ID  
Sent By ccole Date 2022-07-14 Time 15:57 Rev Time 0.00
Received By ccole Date 2022-07-14 Time 15:57 Sent To  
Notes
2022-07-14 15:58:16A SEPARATE PERMIT IS REQUIRED FOR INSTALLATION OF THE
 GAS POOL HEATER AND GAS PIPING.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date   Cont ID  
Sent By   Date 2022-07-14 Time   Rev Time 0.00
Received By aoliver Date 2022-07-13 Time 08:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-06-27 Cont ID  
Sent By medwards Date 2022-06-27 Time 10:06 Rev Time 0.00
Received By medwards Date 2022-06-21 Time 08:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-06-14 Cont ID  
Sent By cthroop Date 2022-06-14 Time 14:27 Rev Time 0.00
Received By cthroop Date 2022-04-06 Time 08:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-12-14 Cont ID  
Sent By cthroop Date 2021-12-14 Time 10:56 Rev Time 0.00
Received By cthroop Date 2021-10-26 Time 10:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-07-23 Cont ID  
Sent By cthroop Date 2021-07-23 Time 11:26 Rev Time 0.00
Received By cthroop Date 2021-06-21 Time 11:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-06-27 Cont ID  
Sent By medwards Date 2022-06-27 Time 10:06 Rev Time 0.00
Received By medwards Date 2022-06-27 Time 10:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-04-25 Cont ID  
Sent By medwards Date 2022-04-25 Time 11:39 Rev Time 0.00
Received By medwards Date 2022-04-25 Time 11:39 Sent To  
Notes
2022-04-25 11:40:50PLEASE ADDRESS COMMENTS 2 AND 3 FROM PREVIOUS REVIEW
 CYCLE.
  
  
  
 2) SHEET M-101A: PLEASE PROVIDE THE INFORMATION FOR THE
 INTAKE AND EXHAUST FOR THE POOL EQUIPMENT ROOM.
 PESF-1,PESF-1A, PEEF-1,PEEF-1A,PEEF-2 AND THE CFM?S
 BROUGHT IN THROUGH THE 24 INCH X 10 INCH INTAKE DUCT.
 FBC 107.2.1
  
 3) SHEET M-101A: PLEASE PROVIDE THE SPECIFICATIONS FOR
 THE CHLORINE SENSOR. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-11-17 Cont ID  
Sent By medwards Date 2021-11-17 Time 09:11 Rev Time 0.00
Received By medwards Date 2021-11-17 Time 09:10 Sent To  
Notes
2021-11-17 09:11:221ST REVIEW FBC-2020 MECHANICAL
 PERMIT- 21061171
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A-253: PLEASE PROVIDE THE POOL STORAGE EXHAUST
 DRAWING FOR THE LEVEL 02 POOL STORAGE ROOM. FBC 107.2.1
  
 2) SHEET M-101A: PLEASE PROVIDE THE INFORMATION FOR THE
 INTAKE AND EXHAUST FOR THE POOL EQUIPMENT ROOM.
 PESF-1,PESF-1A, PEEF-1,PEEF-1A,PEEF-2 AND THE CFM?S
 BROUGHT IN THROUGH THE 24 INCH X 10 INCH INTAKE DUCT.
 FBC 107.2.1
  
 3) SHEET M-101A: PLEASE PROVIDE THE SPECIFICATIONS FOR
 THE CHLORINE SENSOR. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2022-07-14 Cont ID  
Sent By ccole Date 2022-07-14 Time 15:57 Rev Time 0.00
Received By ccole Date 2022-07-14 Time 15:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2022-06-24 Cont ID  
Sent By ccole Date 2022-06-24 Time 15:52 Rev Time 0.00
Received By ccole Date 2022-06-24 Time 15:39 Sent To  
Notes
2022-06-24 16:02:124TH REVIEW FBC-2020 PLUMBING
 PERMIT- 21061171
 6/24/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SUBMITTED MANUFACTURER'S SPECIFICRTIONS FOR THE
 ARCHIE AR031 SHOWER VALVE DO NOT INDICATE COMPLIANCE
 WITH SEC. 412.3 FBC P- INDIVIDUAL SHOWER AND TUB-SHOWER
 COMBINATION VALVES SHALL BE BALANCED-PRESSURE,
 THERMOSTATIC OR COMBINATION
 BALANCED-PRESSURE/THERMOSTATIC VALVES THAT CONFORM TO
 THE REQUIREMENTS OF ASSE 1016/ASME A112.1016/CSA
 B125.16 OR ASME A112.18.1/CSA B125.1.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2022-04-19 Cont ID  
Sent By ccole Date 2022-04-19 Time 10:26 Rev Time 0.00
Received By ccole Date 2022-04-07 Time 11:43 Sent To  
Notes
2022-04-12 13:49:193RD REVIEW FBC-2020 PLUMBING
 PERMIT- 21061171
 4/19/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS SP-1.08 & SP-3.01: PLEASE SUBMIT THE
 MANUFACTURER?S SPECIFICATIONS FOR THE CARTRIDGE FILTER
 TO VERIFY NO BACKWASHING IS REQUIRED AND NO CHLORINATED
 WASTEWATER WILL BE DISCHARGED TO THE STORM DRAINAGE
 SYSTEM- SECS. 454.1.6.5.5.1 & 454.1.6.5.5.2 FBC B &
 SEC. 90-205 (1) WPB CODE OR ORDINANCES.
  
 2) A-253: THE OUTDOOR SHOWER DETAIL DOES NOT APPEAR TO
 MATCH THE DRAWING SHOWN ON THE RINSE SHOWER SUBMITTAL.
 THE SUBMITTAL IS FOR AN INDEPENDENT FOOT TOWER SHOWER
 STATION HOWEVER THE DRAWING SHOWS THE SHOWER CONTROL,
 HEAD AND SPRAYER ATTACHED TO THE EXTERIOR SIDE OF THE
 RESTROOM WALL- PLEASE CLARIFY. PLEASE PROVIDE AN
 EQUIPMENT SCHEDULE SHOWER VALVE, HEAD AND SPRAYER
 INDICATING THE MAKES AND MODELS- SEC. 107.2.1 WPB. IF
 THE RINSE SHOWER IS TO BE INSTALLED PLEASE INDICATE THE
 MODEL NUMBER ON THE PLAN. PLEASE NOTE THAT MODEL NOS
 564 & 565 ARE DESIGNATED AS ACCESSIBLE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-11-09 Cont ID  
Sent By lcrespo Date 2021-11-09 Time 17:09 Rev Time 0.00
Received By lcrespo Date 2021-11-09 Time 08:33 Sent To  
Notes
2021-11-09 17:09:3211/09/21 2ND COMMERCIAL POOL REVIEW**DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  
 1. DONE AND CLEAR
  
 2. UNDER LS-03, WOULD YOU PLEASE PROVIDE THE DISTANCE
 FOR THE ENTRY DOORS OF THE RESTROOMS THAT SHALL BE
 LOCATED WITHIN A 200-FOOT HORIZONTAL RADIUS OF THE
 NEAREST WATER'S EDGE PER THE 2020 FBC SEC. B
 454.1.6.1SANITARY FACILITIES (EXCEPTION).
  
 3. DONE AND CLEAR
  
 4. DONE AND CLEAR
  
 5. DONE AND CLEAR
  
 6.SECOND REQUEST; SP-102: PROVIDE COMPLETE PLANS AND
 SPECIFICATIONS FOR INSTALLATION OF THE RINSE SHOWER
 (MDF MODEL 500)- SECTION 107.2.1 WPB & 606.2 FBC P.
  
 NEW COMMENTS;
 A. ON SHEET P-102A SHOWS A DIFFERENT LAYOUT FOR THE
 SHOWER IN S DIFFERENT LOCATION THAN A-102A. WOULD YOU
 PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. COULD NOT FIND THE SPECIFICATIONS FOR MDF MODEL 500.
 WOULD YOU PLEASE RESUBMIT PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. ON SHEET P-102A, A FLOOR DRAIN IS SHOWN, BUT IF IT
 IS EXPOSED TO THE OUTSIDE, IT CANNOT GO INTO THE
 SANITARY SYSTEM PER CITY ORDNANCE SEC. 90-126(5). -
 PROHIBITIONS AND LIMITATIONS OF DISCHARGE.
  
 D. THE RUNOFF OF THE SHOWER NEEDS TO GO INTO A LOCATION
 THAT CAN BE COLLECTED AND DISPOSED OF. WOULD YOU PLEASE
 PROVIDE A DRAIN TO THE STORM DRAIN OR A SAFE DRAINING
 PLACE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. FAIR HOUSING ACT MANUAL COMPLIANCE: SHOW THE
 ACCESSIBLE ROUTE TO THE RINSE SHOWER AND PROVIDE
 ENLARGED DRAWINGS AND CUTS SHOWING THE LOCATIONS AND
 HEIGHTS OF SHOWERHEADS AND CONTROLS, AND COMPLIANCE
 DETAILS FOR SPACE ALLOWANCE, REACH RANGES, AND CONTROLS
 AND OPERATING MECHANISMS- REFER TO PAGES 2.10- 2.12 OF
 THE MANUAL.
  
 THE MDF MODEL 500 IS NOT THE ONE SHOWN IN DETAIL # 2 ON
 SHEET A-253. WOULD YOU PLEASE PROVIDE A DETAIL THAT HAS
 THE INFORMATION REQUESTED PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 7. ON THE DETAIL, SP-108 SHOWS WHAT APPEARS TO BE THE
 REQUIRED MAKEUP WATER CONTROLLER (AUTO-FILL) AT THE
 COLLECTOR TANK. WOULD YOU PLEASE NOTE THAT SEPARATE
 PERMITS ARE NEEDED TO INSTALL THE DEVICES- SECTION
 105.1 WPB?
  
 8. ON SHEET SP-105, IT SHOWS NO LOCATIONS OF ALL ITEMS
 IN THE PIPING LEGEND- E, F, G, H, I, J, K, & L. WOULD
 YOU PLEASE REMOVE PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 9. DONE AND CLEAR
  
 10. DONE AND CLEAR
  
 11. DONE AND CLEAR
  
 12. DONE AND CLEAR
  
 13. DINE AND CLEAR
  
 14. DONE AND CLEAR
  
 15. SP-108 & 301: ON THE PUMP CURVE FOR THE SELECTED
 PUMP AND SUBMIT MANUFACTURER'S SPECIFICATIONS- SECTION
 454.1.6.5.4 FBC B.
  
 NEW COMMENT; WOULD YOU PLEASE IDENTIFY ON THE PUMP
 CURVE WHICH CURVE KEY IS SPECIFIC TO THE PUMP BEING
 INSTALLED ON THIS POOL, THIS IS NEEDED TO CONFIRM THE
 MAXIMUM SYSTEM FLOW FROM THE TDH CALCULATIONS PER THE
 ANSI/APSP/ICC 7 - 2015 SECS. 4.4.9, 4.4.9.1.
  
 16. SECOND REQUEST; WOULD YOU PLEASE SUBMIT THE
 MANUFACTURER'S SPECIFICATIONS FOR RECIRCULATION AND
 TREATMENT EQUIPMENT, INCLUDING THE SAND FILTER,
 CHEMICAL STORAGE TANKS, CHEMICAL CONTROLLER, AND
 FEEDERS SHOWING THE EQUIPMENT CONFORMS WITH REQUIRED
 STANDARDS NSF/ANSI STANDARD 50, CIRCULATION SYSTEM
 COMPONENTS, AND RELATED MATERIALS FOR SWIMMING POOL,
 SPAS/HOT TUBS, DATED APRIL 2007- SECTION 454.1.6.5.1
 FBC B.
  
 17. THE GRATE SUBMITTAL SUPPLIED DOES NOT COMPLY WITH
 THE 2017 FBC SEC 454.1.6.5.10.2. MAIN DRAIN
 COVERS/GRATES SHALL COMPLY WITH THE REQUIREMENTS OF
 ANSI/APSP 16 AND THE WATER VELOCITY OF THIS SECTION.
 18. SP-301: INCLUDE THE HOSE BIB IN THE EQUIPMENT
 SCHEDULE- SECTION 608.15.4.2 FBC P.
  
 IT SAYS TO REFER TO P-601 ON RESPONSE, AND THIS SHEET
 IS NOT PROVIDED. WOULD YOU PLEASE PROVIDE PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 19) SP-108, 301: THE GAS WATER HEATER INSTALLATIONS,
 INCLUDING THE GAS PIPING, COMBUSTION AND VENTING PLANS,
 AND EQUIPMENT ROOM VENTILATION SYSTEM, SHALL BE
 REVIEWED UNDER SEPARATE PERMITS AND PLAN SUBMITTALS-
 SECTION 105.1, 107.2.1, AND 107.3.5.3.1 WPB. PLEASE
 NOTE THAT THE EQUIPMENT ROOM VENTILATION SHALL COMPLY
 WITH THE FBC BUILDING AND MECHANICAL CODES.
  
 PER THE RESPONSE, P-101A HAS NO VERBIAGE OF A SEPARATE
 PERMIT REQUIRED FOR GAS AND SHEET M-101A, NOT SUPPLIES.
 WOULD YOU PLEASE PROVIDE PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 20. DONE AND CLEAR
  
 21. DONE AND CLEAR
  
 22. NEW COMMENT: ON SHEET SP-103 THE ACCESSIBLE REST
 ROOM SHOWS NO ELEVATION TO ENTER THE RESTROOM BUT ON
 SP-1.01. SP-1.02, A-1.02A, A-1.02B IT SHOWS TWO STEPS.
 WOULD YOU PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-07-13 Cont ID  
Sent By ccole Date 2021-07-13 Time 16:36 Rev Time 0.00
Received By ccole Date 2021-07-12 Time 13:25 Sent To  
Notes
2021-07-13 16:36:171ST REVIEW FBC-2017 PLUMBING
 PERMIT- 21061171
 7/12/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 6TH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE 6TH EDITION 2017
 FBC B- FLORIDA BUILDING CODE 6TH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 6TH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS FOR THE MAIN POOL- DENIED.
  
 1) THE DOH RECEIPT OF APPLICATION AND THE PLANS DO NOT
 BEAR THE 200 ARKONA COURT ADDRESS- SECTION 107.2.1 WPB.
  
 2) DESIGN CRITERIA: PROVIDE A LIST OF CODES AND
 STANDARDS USED IN THE DESIGN OF THE POOLS- SECTION
 107.2.1 WPB. PLEASE INCLUDE THE EDITION DATES OF EACH
 CODE OR STANDARD. THE LA CLARA CONDOMINIUM PROJECT WAS
 DESIGNED IN ACCORDANCE WITH THE FBC- 2017 CODES, SO FOR
 PURPOSE OF THIS REVIEW, IT IS ASSUMED THE POOL WAS ALSO
 DESIGNED UNDER THE 2017 CODE. BECAUSE THE POOL IS BEING
 LOCATED IN A MULTI-FAMILY BUILDING, COMPLIANCE WITH THE
 FAIR HOUSING ACT DESIGN MANUAL IS REQUIRED AND SHALL BE
 NOTED IN THE DESIGN CRITERIA. THE PLANS SHALL ALSO
 REFLECT COMPLIANCE WITH THE SPECIFICATIONS IN THE
 MANUAL INCLUDING ACCESSIBLE ROUTES.
  
 3) REFER TO SECTION 454.1 FBC B AND SECTION 106.5 FBC
 ACC- PLEASE PROVIDE NOTES INDICATING WHICH GROUP OF
 PEOPLE WILL HAVE ACCESS TO THE POOL- THE GENERAL PUBLIC
 OR EXCLUSIVELY BY THE RESIDENTS OF LA CLARA. PLEASE
 NOTE THAT THE DOH RECEIPT INDICATES A PUBLIC POOL WHICH
 WOULD IMPLY COMPLIANCE WITH THE FBC ACC IS REQUIRED-
 SECTION 101.1.2. PLEASE REFER TO SECTION 242.2 FBC ACC-
 A MINIMUM OF TWO ACCESSIBLE ENTRIES INTO THE POOL
 INCLUDING A LIFT ARE REQUIRED FOR PUBLIC POOLS. FURTHER
 REVIEW OF ACCESSIBILITY COMPLIANCES FOR THE POOL ARE
 STOPPED AT THIS POINT PENDING SUBMITTAL OF MORE
 INFORMATION.
  
 4) SP-102 & SP-108: THE LOCATION OF THE COLLECTOR TANK
 AT THE PLANTER, AND ACCESS TO THE TANK DO NOT APPEAR TO
 BE IN COMPLIANCE WITH SECTION 454.1.5.1 FBC B. PLEASE
 CLARIFY OF THE TANK IS IN AN ENCLOSURE AS REQUIRED AND
 PROVIDE DETAILS TO SHOW COMPLIANCE WITH ITEMS BELOW:
 A) 454.1.5.2: ENCLOSURE DETAILS. B) 451.5.3: ENCLOSURE
 MATERIALS. C) 454.1.5.4: VENTILATION. D) 454.1.5.5:
 ACCESS. E) 454.1.5.6: SIZE. F) 454.1.5.7: LIGHTING. G)
 454.1.5.8: STORAGE. H) 454.1.5.9: HOSE BIBS- PLEASE
 SHOW THE LOCATION AND PROVIDE PLUMBING DETAILS AND
 SPECIFICATIONS. I) PLEASE NOTE THAT THE COLLECTOR TANK
 DETAIL ON SP-108 SHOWS A HINGED LOCKABLE COVER AS
 OPTIONAL.
  
 5) SP-102: DECK DRAINS ARE CALLED OUT BUT NOT SHOWN-
 SECTION 454.1.3.1.2 FBC B.
  
 6) SP-102: PROVIDE COMPLETE PLANS AND SPECIFICATIONS
 FOR INSTALLATION OF THE RINSE SHOWER (MDF MODEL 500)-
 SECTION 107.2.1 WPB & 606.2 FBC P.
  
 A) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION GUIDELINES FOR THE SHOWER UNIT AND SHOWER
 VALVE- SECTIONS 417.1, 424.1, & 424.3 FBC P.
  
 B) SHOW THE MAIN HOT AND COLD WATER LINES TO THE RINSE
 SHOWER TOWER AND INDICATE HOW WATER WILL BE DRAINED
 FROM THE AREA TO AN APPROVED PLACE OF DISPOSAL-
 SECTIONS 454.1.6.2 & 454.1.3.1.2 FBC B. CLARIFY IF THE
 UNIT IS PRE-PIPED AND HOW WATER CONNECTIONS ARE BEING
 MADE, SHUT OFF VALVE AND WATER HAMMER ARRESTOR
 LOCATIONS ETC. A WATER RISER DRAWING MAY BE HELPFUL IN
 EXPEDITING THE REVIEW- SECTION 107.3.5.1.3 WPB.
  
 C) FAIR HOUSING ACT MANUAL COMPLIANCE: SHOW THE
 ACCESSIBLE ROUTE TO THE RINSE SHOWER AND PROVIDE
 ENLARGED DRAWINGS AND CUTS SHOWING THE LOCATIONS AND
 HEIGHTS OF SHOWER HEADS AND CONTROLS, AND COMPLIANCE
 DETAILS FOR SPACE ALLOWANCE, REACH RANGES, AND CONTROLS
 AND OPERATING MECHANISMS- REFER TO PAGES 2.10- 2.12 OF
 THE MANUAL.
  
 7) SP-102, 108: SHOW THE LOCATION OF THE REQUIRED
 POTABLE WATER BACKFLOW PREVENTER FOR THE MAKEUP WATER
 LINE TO THE COLLECTOR TANK- SECTION 454.1.6.3 FBC P &
 SECTION 608.3 FBC P. THE DETAIL ON SP-108 SHOWS WHAT
 APPEARS TO BE THE REQUIRED MAKEUP WATER CONTROLLER
 (AUTO FILL) AT THE COLLECTOR TANK HOWEVER IT IS NOT
 CALLED OUT- SECTION 454.1.6.5.11 FBC B. PLEASE NOTE
 THAT SEPARATE PERMITS ARE REQUIRED FOR INSTALLATION OF
 THE DEVICES- SECTION 105.1 WPB.
  
 8) SP-105: SHOW LOCATIONS OF ALL ITEMS IN THE PIPING
 LEGEND- E, F, G, H, I, J, K, & L- SECTION 107.2.1 WPB.
  
 9) SP-105: IT APPEARS THE LOCATIONS OF THE GUTTER DRAIN
 OUTLETS ARE EXCEEDING THE MAXIMUM 15 FT. SPACING PER
 SECTION 454.1.6.5.3.1 FBC B.
  
 10) SP-105 & 107: PLEASE INDICATE THE SLOPE OF THE
 GUTTERS- SECTION 454.1.6.5.3.1 FBC B.
  
 11) SP-104,105,108, & 301: PLEASE CLARIFY THE ELEVATION
 HEIGHT OF THE COLLECTOR TANK. ALTHOUGH IT IS SHOWN ON
 THE SAME FLOOR LEVEL OF THE POOL, IT APPEARS THAT THE
 DRAIN INLETS OF THE COLLECTOR TANK WOULD HAVE TO BE AT
 A LOWER ELEVATION THAN THE DRAIN PIPING FROM THE
 GUTTER, FLOOR AND WALL DRAINS IN ORDER FOR THE SYSTEM
 TO GRAVITY DRAIN INTO THE TANK. PLEASE INDICATE THE
 SLOPES OF THE GRAVITY DRAIN PIPING SHOWN ON THE PLAN
 USING ELEVATION HEIGHT MEASUREMENTS- SECTION 704.1 FBC
 P. THE COLLECTOR TANK DETAIL ON SP-108 INDICATES THE
 STRUCTURAL DESIGN OF THE TANK SUPPORTING SLAB TO BE
 DESIGNED BY OTHERS. PLEASE PROVIDE MORE INFORMATION
 ABOUT THE STRUCTURAL DESIGN IN ORDER TO CLARIFY THE
 LOCATION OF THE TANK AND HOW IT IS BEING SUPPORTED-
 SECTION 107.2.1 WPB. PLEASE SUBMIT MANUFACTURER'S SPECS
 FOR THE TANK- SECTION 454.1.5.1 FBC B.
  
 12) SP-108: THE BACKWASH LINE SHALL NOT DRAIN INTO THE
 CITY SANITARY SYSTEM- SECTION 454.1.6.5.15 & SEC.
 90-126(5) WPB CODE OF ORDINANCES.
  
 13) SP-105, 108: SHOW THE LOCATION OF THE RAINWATER
 OVERFLOW LINE TO THE STORM DRAIN. CONCERNING F AND J
 (POOL MAINTENANCE LINE DRAIN), PLEASE VERIFY THAT ANY
 WASTE WATER DRAINING FROM THE POOL SYSTEM INTO THE
 STORM DRAINAGE SYSTEM HAS BEEN DECHLORINATED OR IT IS
 PROHIBITED- SEC. 90-203 & 90-205- WPB CODE OF
 ORDINANCES.
  
 14) SP-105 & 107: PROVIDE A WALL INLET DETAIL- SECTION
 454.1.6.5.9 FBC B.
  
 15) SP-108 & 301: PROVIDE THE PUMP CURVE FOR THE
 SELECTED PUMP AND SUBMIT MANUFACTURER'S SPECIFICATIONS-
 SECTION 454.1.6.5.4 FBC B.
  
 16) SP-108, 301: SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR RECIRCULATION AND TREATMENT EQUIPMENT INCLUDING THE
 SAND FILTER, CHEMICAL STORAGE TANKS, CHEMICAL
 CONTROLLER, AND FEEDERS SHOWING THE EQUIPMENT CONFORMS
 WITH REQUIRED STANDARDS NSF/ANSI STANDARD 50,
 CIRCULATION SYSTEM COMPONENTS AND RELATED MATERIALS FOR
 SWIMMING POOL, SPAS/HOT TUBS, DATED APRIL 2007- SECTION
 454.1.6.5.1 FBC B.
  
 17) SP-107 & 301: SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE MAIN DRAINS AND COVERS SHOWING CONFORMANCE WITH
 THE ANSI/APSP 16 STANDARD- 454.1.6.5.10.2 FBC P.
  
 18) SP-301: INCLUDE THE HOSE BIB IN THE EQUIPMENT
 SCHEDULE- SECTION 608.15.4.2 FBC P.
  
 19) SP-108, 301: THE GAS WATER HEATER INSTALLATIONS
 INCLUDING THE GAS PIPING, COMBUSTION AND VENTING PLANS,
 AND EQUIPMENT ROOM VENTILATION SYSTEM SHALL BE REVIEWED
 UNDER SEPARATE PERMITS AND PLAN SUBMITTALS- SECTION
 105.1, 107.2.1 AND 107.3.5.3.1 WPB. PLEASE NOTE THAT
 THE EQUIPMENT ROOM VENTILATION SHALL BE IN COMPLIANCE
 WITH THE FBC BUILDING AND MECHANICAL CODES.
  
 20) PLEASE SHOW COMPLIANCE WITH THE FOLLOWING SECTIONS
 FROM THE FBC EC:
 C404.9.1 HEATERS. THE ELECTRIC POWER TO ALL HEATERS
 SHALL BE CONTROLLED BY A READILY ACCESSIBLE ON-OFF
 SWITCH THAT IS AN INTEGRAL PART OF THE HEATER, MOUNTED
 ON THE EXTERIOR OF THE HEATER, OR EXTERNAL TO AND
 WITHIN 3 FEET (914 MM) OF THE HEATER. OPERATION OF SUCH
 SWITCH SHALL NOT CHANGE THE SETTING OF THE HEATER
 THERMOSTAT. SUCH SWITCHES SHALL BE IN ADDITION TO A
 CIRCUIT BREAKER FOR THE POWER TO THE HEATER. GAS-FIRED
 HEATERS SHALL NOT BE EQUIPPED WITH CONTINUOUSLY BURNING
 IGNITION PILOTS.
 C404.9.2 TIME SWITCHES. TIME SWITCHES OR OTHER CONTROL
 METHODS THAT CAN AUTOMATICALLY TURN OFF AND ON HEATERS
 AND PUMP MOTORS ACCORDING TO A PRESET SCHEDULE SHALL BE
 INSTALLED FOR HEATERS AND PUMP MOTORS. HEATERS AND PUMP
 MOTORS THAT HAVE BUILT-IN TIME SWITCHES SHALL BE IN
 COMPLIANCE WITH THIS SECTION.
 EXCEPTIONS:
 1. WHERE PUBLIC HEALTH STANDARDS REQUIRE 24-HOUR PUMP
 OPERATION.
 2. PUMPS THAT OPERATE SOLAR- AND WASTE-HEAT-RECOVERY
 POOL HEATING SYSTEMS.
 C404.9.3 COVERS. OUTDOOR HEATED SWIMMING POOLS AND
 OUTDOOR PERMANENT SPAS SHALL BE EQUIPPED WITH A
 VAPOR-RETARDANT COVER ON OR AT THE WATER SURFACE OR A
 LIQUID COVER OR OTHER MEANS PROVEN TO REDUCE HEAT LOSS.
  
 21) PLEASE NOTE THAT SEPARATE PERMITS AND PLANS ARE
 REQUIRED FOR INSTALLATION OF THE POOL HEATER AND GAS
 PIPING, THE MAKEUP WATER LINE, AUTOFILL AND BACKFLOW
 PREVENTER, AND THE HOSE BIB AND POOL RINSE SHOWER-
 SECTION 105.1 & 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-04-25 Cont ID  
Sent By medwards Date 2022-04-25 Time 11:41 Rev Time 0.00
Received By medwards Date 2022-04-25 Time 11:41 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-12-14 Cont ID  
Sent By cthroop Date 2021-12-14 Time 10:14 Rev Time 0.00
Received By cthroop Date 2021-12-09 Time 11:30 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-07-23 Cont ID  
Sent By cthroop Date 2021-07-23 Time 11:26 Rev Time 0.00
Received By cthroop Date 2021-07-23 Time 09:57 Sent To  
Notes
2021-07-23 11:26:22PLAN REVIEW SIGNATURES
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC2017
  
 1ST REVIEW
 RESULTS: DENIED
  
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RE: PLAN PAGES A-101, P-101A, P-102B, M-101A, E-101A,
 E-606
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR
 DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL
 SIGNATURE.
  
 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR
 DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL
 WET SEAL AND SIGNATURE TO:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  

Review Stop Z ZONING
Rev No 3 Status P Date 2022-04-19 Cont ID  
Sent By eschneid Date 2022-04-19 Time 17:32 Rev Time 0.25
Received By eschneid Date 2022-04-19 Time 17:32 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2021-11-30 Cont ID  
Sent By eschneid Date 2021-11-30 Time 19:03 Rev Time 0.50
Received By eschneid Date 2021-11-30 Time 18:03 Sent To  
Notes
2021-11-30 19:03:41FAILED
  
 1) REPEAT COMMENT - THANK YOU FOR PROVIDING THE MOST
 RECENT ARCHITECTURAL SITE PLANS FOR LEVEL 2; HOWEVER,
 THE AQUADYNAMICS PLANS (SHEETS SP-1.02 AND SP-1.01)
 WERE NOT UPDATED TO MATCH THESE PLANS. THE AQUADYNAMICS
 PLANS MUST MATCH THE LATEST ARCHITECTURAL PLANS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-06-24 Cont ID  
Sent By eschneid Date 2021-06-24 Time 13:30 Rev Time 0.25
Received By eschneid Date 2021-06-24 Time 13:30 Sent To  
Notes
2021-06-24 13:42:42FAILED
  
 1) THE SITE PLAN PROVIDED FOR LEVEL 2 IS NOT THE PLAN
 THAT IS INCLUDED WITH THE MOST RECENT BUILDING PERMIT
 REVISION. THE REST ROOM AND POOL STORAGE AREA TO THE
 WEST OF THE SWIMMING POOL HAVE CHANGED. PROVIDE THE
 ACCURATE BASE DRAWING AND ADJUST ALL PLANS ACCORDINGLY.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  