Plan Review Details - Permit 21061065
Plan Review Stops For Permit 21061065
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2023-06-22 Cont ID  
Sent By rmcdouga Date 2023-06-22 Time 15:49 Rev Time 0.00
Received By rmcdouga Date 2023-06-22 Time 15:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-02-02 Cont ID  
Sent By rmcdouga Date 2023-02-02 Time 14:27 Rev Time 0.00
Received By rmcdouga Date 2023-02-02 Time 14:27 Sent To  
Notes
2023-02-02 14:46:52BUILDING PROVISO:
 ROOF CONTRACTOR TO SPECIFY THE METHOD OF ATTACHMENT FOR
 THE TILE ROOF AND SUBMIT PRODUCT APPROVAL FOR ROOF TILE
 ADHESIVE IF IT IS USED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-09-21 Cont ID  
Sent By rmcdouga Date 2022-09-21 Time 11:17 Rev Time 0.00
Received By rmcdouga Date 2022-09-21 Time 08:34 Sent To  
Notes
2022-09-21 11:17:21PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE WINDOW AND DOOR SCHEDULE ON SHEET S-1 HAS A
 FIXED WINDOW AND THE PRODUCT APPROVALS THAT WERE
 SUBMITTED ARE FOR A HORIZONTAL ROLLING WINDOW. PLEASE
 CORRECT. FBC 107.2.1
  
 2) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 HORIZONTAL ROLLING WINDOW AND THE SLIDING GLASS DOOR DO
 NOT SHOW THAT THEY ARE IN COMPLIANCE WITH THE 2020 FBC.
 THEY ARE ALSO REQUIRED TO BE APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. FBC AMEND. 107.3.4 - PROVIDE TWO
 SETS OF PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE
 REGULATED BY FAC 61G20-3.001 PER FLORIDA STATUTE
 553.842 (5) THAT HAVE BEEN REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. PROVIDE TWO COMPLETE
 PRODUCT APPROVALS WITH FL OR NOA NUMBERS INCLUDING
 INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES
 FOR EACH OF THE DIFFERENT ROOFING MATERIALS, WINDOW
 (GLASS TYPES), STRUCTURAL MULLIONS AND EXTERIOR DOOR
 TYPES. THESE ITEMS CAN BE DEFERRED IF REQUESTED ON THE
 PLANS, HOWEVER, THE DOCUMENTS MUST BE SUBMITTED AND
 APPROVED BY THE BUILDING DEPARTMENT BEFORE THEY CAN BE
 INSTALLED. ONLY ONE SET IS REQUIRED TO BE UPLOADED FOR
 ELECTRONICALLY SUBMITTED DOCUMENTS.
  
 3) SUBMIT PRODUCT APPROVALS FOR THE CONCRETE ROOF TILE
 AND TILE ADHESIVE ( IF USED ), THAT HAVE BEEN REVIEWED
 AND APPROVED BY THE DESIGNER OF RECORD. SPECIFY THE
 METHOD THAT WILL BE USED TO ATTACH THE TILE. FBC AMEND.
 107.3.4
  
 4) SUBMIT ENERGY CODE COMPLIANCE FORMS. FBC ENERGY
 COMPLIANCE CHAPTER 4 [RE] RESIDENTIAL ENERGY
 EFFICIENCY. PLANS SPECIFY THE ADDITION AS A FAMILY ROOM
 AND IT MAY BECOME CONDITIONED SPACE IN THE FUTURE.
 THEREFORE IT NEEDS TO BE INSULATED.
  
 5) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-07-30 Cont ID  
Sent By rmcdouga Date 2021-07-30 Time 09:44 Rev Time 0.00
Received By rmcdouga Date 2021-07-29 Time 16:22 Sent To  
Notes
2021-07-30 08:24:45PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS SPECIFY THIS PROJECT AS BEING EXPOSURE
 CATEGORY B. THE DEFAULT EXPOSURE CATEGORY IS C. DUE TO
 THE OPEN AREAS OF THE GOLF COURSE, THE LAKES AND CANALS
 THAT ARE IN CLOSE PROXIMITY TO THE PROJECT SHOULD BE
 CONSIDERED EXPOSURE CATEGORY C. IF YOU DISAGREE,
 PROVIDE AN ANALYSIS OF ALL OF THE WIND DIRECTIONS AT
 THE PROJECT THAT WILL SUPPORT YOUR DETERMINATION.
 FBC-R301.2.1.4 EXPOSURE CATEGORY
  
 2) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 HORIZONTAL ROLLING WINDOW AND THE SLIDING GLASS DOOR DO
 NOT SHOW THAT THEY ARE IN COMPLIANCE WITH THE 2020 FBC.
 THEY ARE ALSO REQUIRED TO BE APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. FBC AMEND. 107.3.4 - PROVIDE TWO
 SETS OF PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE
 REGULATED BY FAC 61G20-3.001 PER FLORIDA STATUTE
 553.842 (5) THAT HAVE BEEN REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. PROVIDE TWO COMPLETE
 PRODUCT APPROVALS WITH FL OR NOA NUMBERS INCLUDING
 INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES
 FOR EACH OF THE DIFFERENT ROOFING MATERIALS, WINDOW
 (GLASS TYPES), STRUCTURAL MULLIONS AND EXTERIOR DOOR
 TYPES. THESE ITEMS CAN BE DEFERRED IF REQUESTED ON THE
 PLANS, HOWEVER, THE DOCUMENTS MUST BE SUBMITTED AND
 APPROVED BY THE BUILDING DEPARTMENT BEFORE THEY CAN BE
 INSTALLED. ONLY ONE SET IS REQUIRED TO BE UPLOADED FOR
 ELECTRONICALLY SUBMITTED DOCUMENTS.
  
 3) SUBMIT PRODUCT APPROVALS FOR THE METAL ROOFING THAT
 HAVE BEEN REVIEWED AND APPROVED BY THE DESIGNER OF
 RECORD. FBC AMEND. 107.3.4
  
 4) SHOW COMPLIANCE WITH FBC-R806 FOR ROOF VENTILATION.
  
 5) SPECIFY THE ROOF COMPONENT AND CLADDING PRESSURES ON
 THE PLANS. R301.2.1 WIND DESIGN CRITERIA
  
 6) PROVIDE A FLASHING DETAIL FOR NEW METAL ROOF TO THE
 EXISTING GABLE WALL. FBC-R903.2 FLASHING
  
 7) SUBMIT ENERGY CODE COMPLIANCE FORMS. FBC ENERGY
 COMPLIANCE CHAPTER 4 [RE] RESIDENTIAL ENERGY EFFICIENCY
  
 8) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-06-14 Cont ID  
Sent By jleahy Date 2023-06-14 Time 11:47 Rev Time 0.00
Received By jleahy Date 2023-06-14 Time 11:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-07-24 Cont ID  
Sent By jleahy Date 2021-07-24 Time 18:38 Rev Time 0.00
Received By jleahy Date 2021-07-24 Time 18:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2023-06-22 Cont ID  
Sent By rmcdouga Date 2023-06-22 Time 15:49 Rev Time 0.00
Received By rmcdouga Date 2023-06-05 Time 08:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-05-31 Cont ID  
Sent By hmoser Date 2023-05-31 Time 16:10 Rev Time 0.00
Received By hmoser Date 2023-05-23 Time 13:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-05-09 Cont ID  
Sent By medwards Date 2023-05-09 Time 09:44 Rev Time 0.00
Received By medwards Date 2023-05-02 Time 11:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-02-07 Cont ID  
Sent By vbroglia Date 2023-02-07 Time 10:58 Rev Time 0.00
Received By vbroglia Date 2023-01-24 Time 15:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-09-21 Cont ID  
Sent By rmcdouga Date 2022-09-21 Time 11:29 Rev Time 0.00
Received By rmcdouga Date 2022-08-16 Time 16:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-08-16 Cont ID  
Sent By jleahy Date 2021-08-16 Time 07:56 Rev Time 0.00
Received By jleahy Date 2021-07-09 Time 14:16 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2023-07-10 Cont ID  
Sent By lmarchan Date 2023-07-10 Time 15:29 Rev Time 0.00
Received By lmarchan Date 2023-06-27 Time 12:09 Sent To  
Notes
2023-07-07 10:54:42RECEIPT MU-2023-029312 - $546.52
2023-06-27 12:09:466/27/23 EMAILED IMPACT OFFICE TO REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-07-29 Cont ID  
Sent By rmcdouga Date 2021-07-29 Time 16:22 Rev Time 0.00
Received By rmcdouga Date 2021-07-29 Time 16:22 Sent To  
Notes
2021-07-29 16:24:37PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2023-05-31 Cont ID  
Sent By hmoser Date 2023-05-31 Time 16:03 Rev Time 0.00
Received By hmoser Date 2023-05-31 Time 15:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2023-05-09 Cont ID  
Sent By medwards Date 2023-05-09 Time 09:40 Rev Time 0.00
Received By medwards Date 2023-05-09 Time 09:40 Sent To  
Notes
2023-05-09 09:42:41DESIGNER OF THE MECHANICAL DRAWING NEEDS TO PRINT THEIR
 NAME AND SIGN THE DRAWING. FBC AMENDMENT 107.2.1
  
 THE A/C TIE DOWN DRAWNING FROM THE ENGINEER HAS A COPY
 OF THE ENGINEERS DIGITAL SIGNATURE. PROVIDE THE
 ORIGINAL DIGITALLY SIGNED DOCUMENT. FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2023-01-27 Cont ID  
Sent By medwards Date 2023-01-27 Time 05:30 Rev Time 0.00
Received By medwards Date 2023-01-27 Time 05:30 Sent To  
Notes
2023-01-27 05:31:013RD REVIEW FMC
 PERMIT: 21061065
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A MECHANICAL DRAWING SHOWING THE LOCATION OF
 THIS MINI-SPLIT SYSTEM, THE CONDENSATE DRAIN
 TERMINATION LOCATION, THE CONDENSING UNIT LOCATION AND
 HOW THIS CONDENSING UNIT WILL BE TIED DOWN. FBC 107.3.5
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-08-22 Cont ID  
Sent By medwards Date 2022-08-22 Time 13:50 Rev Time 0.00
Received By medwards Date 2022-08-22 Time 13:48 Sent To  
Notes
2022-08-22 13:49:36SEE 1ST CYCLE MECHANICAL REVIEW COMMENTS BELOW:
  
 PERMIT DATED 7/7/2021 CHANGES SCOPE OF WORK FROM
 SCREENED IN PORCH TO A FAMILY ROOM.
 1) PLEASE PROVIDE THE ENERGY CALCULATIONS FOR THE
 EDITION. FBC EC R402
 2) PLEASE SHOW HOW YOU WILL CONDITION THIS NEW SPACE.
 FBC R303.10
 3) PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS SIGNED AND SEALED BY AN ENGINEER OR THE
 ARCHITECT, YOU MAY ALSO HAVE THE MECHANICAL CONTRACTOR
 THAT HOLDS THE PERMIT TO INSTALL THE EQUIPMENT ON THIS
 PROJECT TO PRINT THEN SIGN THEIR NAME ON THE FRONT PAGE
 OF THE CALCULATIONS. FBC ECR403.7 & F.S. 471.003(H)
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-07-26 Cont ID  
Sent By medwards Date 2021-07-26 Time 06:44 Rev Time 0.00
Received By medwards Date 2021-07-26 Time 06:44 Sent To  
Notes
2021-07-26 07:05:00PERMIT DATED 7/7/2021 CHANGES SCOPE OF WORK FROM
 SCREENED IN PORCH TO A FAMILY ROOM.
 1) PLEASE PROVIDE THE ENERGY CALCULATIONS FOR THE
 EDITION. FBC EC R402
 2) PLEASE SHOW HOW YOU WILL CONDITION THIS NEW SPACE.
 FBC R303.10
 3) PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS SIGNED AND SEALED BY AN ENGINEER OR THE
 ARCHITECT, YOU MAY ALSO HAVE THE MECHANICAL CONTRACTOR
 THAT HOLDS THE PERMIT TO INSTALL THE EQUIPMENT ON THIS
 PROJECT TO PRINT THEN SIGN THEIR NAME ON THE FRONT PAGE
 OF THE CALCULATIONS. FBC ECR403.7 & F.S. 471.003(H)
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2023-02-02 Cont ID  
Sent By rmcdouga Date 2023-02-02 Time 14:30 Rev Time 0.00
Received By rmcdouga Date 2023-02-02 Time 14:30 Sent To  
Notes
2023-02-02 14:43:47FL 16709 - FLAT ROOF
 NOA NO. 19-0925.03 - CONCRETE ROOF TILE
 NOA NO. 18-0502.03 - TILE UNDERLAYMENT

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2022-09-21 Cont ID  
Sent By rmcdouga Date 2022-09-21 Time 11:17 Rev Time 0.00
Received By rmcdouga Date 2022-09-21 Time 11:17 Sent To  
Notes
2022-09-21 11:28:55STILL MISSING PRODUCT APPROVALS FOR THE TILE ROOF.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2021-07-29 Cont ID  
Sent By rmcdouga Date 2021-07-29 Time 16:23 Rev Time 0.00
Received By rmcdouga Date 2021-07-29 Time 16:23 Sent To  
Notes
2021-07-29 16:23:47NO PRODUCT APPROVALS SUBMITTED FOR THE METAL ROOF.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 7 Status P Date 2023-06-14 Cont ID  
Sent By jleahy Date 2023-06-14 Time 11:47 Rev Time 0.00
Received By jleahy Date 2023-06-14 Time 11:47 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status F Date 2023-05-31 Cont ID  
Sent By hmoser Date 2023-05-31 Time 16:03 Rev Time 0.00
Received By hmoser Date 2023-05-31 Time 16:03 Sent To  
Notes
2023-05-31 16:09:38SIGNATURE FAIL.
 ENGINEER MUST DIGITALLY SIGN EACH DRAWING
 SUBMITTED NONE ARE DIGITALLY SIGNED
 SECTION FS 471/481
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status F Date 2023-05-09 Cont ID  
Sent By medwards Date 2023-05-09 Time 09:42 Rev Time 0.00
Received By medwards Date 2023-05-09 Time 09:42 Sent To  
Notes
2023-05-09 09:43:58THE A/C TIED DOWN DRAWING IS NOT THE ORIGINAL DIGITALLY
 SIGNED DOCUMENT. PROVIDE THE ORIGINAL DIGITALLY SIGNED
 DOCUMENT. FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2023-01-27 Cont ID  
Sent By medwards Date 2023-01-27 Time 05:31 Rev Time 0.00
Received By medwards Date 2023-01-27 Time 05:31 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-09-16 Cont ID  
Sent By rmcdouga Date 2022-09-16 Time 16:01 Rev Time 0.00
Received By rmcdouga Date 2022-09-16 Time 16:01 Sent To  
Notes
2022-09-16 16:02:28DIGITALLY SIGNED PLANS IN SIGNATURE FILE.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-07-29 Cont ID  
Sent By rmcdouga Date 2021-07-29 Time 16:17 Rev Time 0.00
Received By rmcdouga Date 2021-07-29 Time 16:17 Sent To  
Notes
2021-07-29 16:18:35DIGITALLY SIGNED PLANS IN SIGNATURE FILE.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-07-26 Cont ID  
Sent By medwards Date 2021-07-26 Time 07:08 Rev Time 0.00
Received By medwards Date 2021-07-26 Time 07:08 Sent To  
Notes
2021-07-26 07:10:33ENGINEER OF RECORD MUST DIGITALLY SIGN THE DRAWINGS, OR
 YOU MAY BRING TO OUR OFFICE ORIGINAL SIGNED AND SEALED
 PAPER DRAWINGS.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop Z ZONING
Rev No 4 Status P Date 2023-06-20 Cont ID  
Sent By gvolcy Date 2023-06-20 Time 10:55 Rev Time 0.00
Received By vbroglia Date 2023-06-20 Time 10:55 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2023-02-07 Cont ID  
Sent By VBroglia Date 2023-02-07 Time 10:57 Rev Time 0.00
Received By vbroglia Date 2023-02-07 Time 10:57 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2022-08-29 Cont ID  
Sent By vbroglia Date 2022-08-29 Time 13:41 Rev Time 0.00
Received By vbroglia Date 2022-08-29 Time 13:41 Sent To  
Notes
2022-08-29 13:42:468/29/2022 FAILED
  
 PLEASE PROVIDE THE SETBACKS OF THE NEW PROPOSED PROJECT
 TO THE PROPERTY LINES
  
 PLEASE PROVIDE A SITE PLAN OR SURVEY WHICH SHOWS THE
 ENTIRE STRUCTURE ON THE LOT WITH DIMENSIONS AND
 SETBACKS
  
 **** FAILED ****
 VALENTINA BROGLIA
 ASSOCIATE PLANNER
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-08-13 Cont ID  
Sent By kalexand Date 2021-08-13 Time 17:18 Rev Time 0.00
Received By kalexand Date 2021-08-13 Time 17:18 Sent To I
Notes
2021-08-13 17:20:08ZONING PLAN REVIEW
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PROVIDE A CURRENT SURVEY, WHICH INCLUDES THE
 PROPERTY'S ADDRESS AND LEGAL DESCRIPTION. PLEASE
 ILLUSTRATE THE FOLLOWING ON THE SURVEY:
 - LOCATION OF THE PROPOSED WORK.
 - SETBACK DIMENSIONS FROM ANY EXTERIOR IMPROVEMENTS TO
 ALL ADJACENT PROPERTY LINES.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALLY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOG
 IN INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 KIZZI ALEXANDRE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1442
 E: [email protected]
  