Plan Review Details - Permit 21060954
Plan Review Stops For Permit 21060954
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-09-24 Cont ID  
Sent By rmcdouga Date 2021-09-24 Time 12:44 Rev Time 0.00
Received By rmcdouga Date 2021-09-24 Time 12:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-07-15 Cont ID  
Sent By rmcdouga Date 2021-07-15 Time 15:06 Rev Time 0.00
Received By rmcdouga Date 2021-07-15 Time 14:27 Sent To  
Notes
2021-07-15 15:12:19PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 THE VALUATION FOR THIS PROJECT APPEARS TO BE UNDER
 VALUED. FOR THE PURPOSE OF PERMITTING THE VALUATION IS
 TO INCLUDE THE COST OF THE SIGN AND ALL ASSOCIATED
 COSTS, INCLUDING, ENGINEERING AND INSTALLATION. SUBMIT
 A COST BREAK DOWN FOR THIS PROJECT. BUILDING PERMIT
 VALUATION. FOR PERMITTING PURPOSES, VALUATION OF FBC
 109.3 BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-12-14 Cont ID  
Sent By jleahy Date 2021-12-14 Time 15:18 Rev Time 0.00
Received By jleahy Date 2021-12-14 Time 15:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-10-04 Cont ID  
Sent By jleahy Date 2021-10-04 Time 12:54 Rev Time 0.00
Received By jleahy Date 2021-10-04 Time 12:47 Sent To  
Notes
2021-10-04 12:56:03ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 VALUE OF WORK IS TOO LOW, PLEASE SUBMIT A COMPLETE
 VALUE FOR SIGN AND LABOR.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-06-28 Cont ID  
Sent By jleahy Date 2021-06-28 Time 15:33 Rev Time 0.00
Received By jleahy Date 2021-06-28 Time 15:26 Sent To  
Notes
2021-06-28 15:34:11NO ELECTRICAL DETAIL SHOWN JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-12-14 Cont ID  
Sent By jleahy Date 2021-12-14 Time 15:18 Rev Time 0.00
Received By jleahy Date 2021-11-18 Time 15:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-10-04 Cont ID  
Sent By jleahy Date 2021-10-04 Time 12:56 Rev Time 0.00
Received By jleahy Date 2021-09-07 Time 12:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-07-15 Cont ID  
Sent By rmcdouga Date 2021-07-15 Time 15:12 Rev Time 0.00
Received By rmcdouga Date 2021-06-17 Time 10:05 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-09-24 Cont ID  
Sent By rmcdouga Date 2021-09-24 Time 12:52 Rev Time 0.00
Received By rmcdouga Date 2021-09-24 Time 12:52 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-07-15 Cont ID  
Sent By rmcdouga Date 2021-07-15 Time 15:06 Rev Time 0.00
Received By rmcdouga Date 2021-07-15 Time 14:27 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2021-09-23 Cont ID  
Sent By llouie Date 2021-09-23 Time   Rev Time 0.00
Received By llouie Date 2021-09-23 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2021-06-30 Cont ID  
Sent By llouie Date 2021-06-30 Time   Rev Time  
Received By llouie Date 2021-06-30 Time   Sent To  
Notes
2021-06-30 13:01:48** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) PERMIT PLANS SHALL PROVIDE BUILDING FA?ADE
 DIMENSIONS. PLANS MUST DOCUMENT THE DIMENSIONS AND
 STAFF MUST BE ABLE TO CALCULATE THE MAXIMUM ALLOWABLE
 SIGN AREA BASED ON THE BUILDING FACADE DIMENSIONS FOR
 COMPLIANCE WITH THE CITY'S ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDRS). [ZLDR S.94-409]
  
 2.) IS THE PERMIT FOR THE PROPOSED SIGNAGE THE ONLY
 WALL SIGNAGE PROVIDED ON THE EXISTING BUILDING? IF NOT,
 PLEASE PROVIDE PHOTOGRAPHS OF THE EXISTING SIGNAGE.
 PLEASE NOTE THAT PER ZLDR S.94-408(D), ONLY 3 WALL
 SIGNS ARE PERMITTED FOR THE ENTIRE BUILDING (BASED ON
 SINGLE-TENANT STAND-ALONE BUILDING).
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: NORTHPOINT PARKWAY CPD.
  
  