| 2021-07-29 16:36:00 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: |
| | A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| | PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| | PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| | BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| | APPROVAL. |
| | 1. ACCESSIBILITY; SEE A08.01/DETAIL 3: |
| | A. THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR |
| | PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE |
| | OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18 |
| | INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION PER FBC |
| | ACC 604.2 |
| | B. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG |
| | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| | CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES |
| | MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2 |
| | |
| | 2.034-P01_00 W G PIPINING PLAN DEMO AND G PIPINING PLAN |
| | DEMO APPEAR TO BE DUPLICATES OF EACH OTHER. PER WPB FBC |
| | 107.2.1, PLEASE CLARIFY AND REMOVE ANY DUPLICATE PLAN |
| | SHEETS TO AVOID CONFUSION. |
| | |
| | 3.035-P01_01 W G PIPING PLAN AND G PIPING PLAN APPEAR |
| | TO BE DUPLICATES OF EACH OTHER. PER WPB FBC 107.2.1, |
| | PLEASE CLARIFY AND REMOVE ANY DUPLICATE PLAN SHEETS TO |
| | AVOID CONFUSION. |
| | |
| | 4.036-P01_02 W G PIPING ISOMETRIC PLAN AND G PIPING |
| | ISOMETRIC APPEAR TO BE DUPLICATES OF EACH OTHER. PER |
| | WPB FBC 107.2.1, PLEASE CLARIFY AND REMOVE ANY |
| | DUPLICATE PLAN SHEETS TO AVOID CONFUSION. |
| | |
| | 5. REGARDING P01.01 WATER AND GAS PIPING PLAN AND |
| | P01.02 WATER AND GAS PIPING ISOMETRIC: |
| | KEYNOTE 7 STATES ?ADJUST AS REQUIRED AND RECONNECT |
| | EXISTING HOT WATER TANK?. I CANNOT FIND ON THE PLANS |
| | WHERE THIS APPLIES. PER WPB FBC 107.2.1, INDICATE NOTE |
| | 7 ON THE PLANS OR IF IT DOES NOT APPLY, DELETE IT. |
| | |
| | 6. REGARDING P01.00 WATER AND GAS DEMO PLAN: |
| | A.PER WPB FBC 107.2.1, PROVIDE KEYNOTE ADDRESSING |
| | REMOVAL OF CW TO CHILLER AND REMOVAL OF CHW AND |
| | INDICATE ON THE PLAN. |
| | B.I CANNOT FIND ON THE PLANS KEYNOTES 1, 4, 5, 6, 7, 8, |
| | 9, 10, 15, 16 AND 17. PER WPB FBC 107.2.1, INDICATE ON |
| | THE PLANS OR IF A NOTE DOES NOT APPLY, DELETE IT. |
| | KEYNOTE 17 SPECIFICALLY ADDRESSES FW TO EXISTING |
| | MISTING CABINET. THERE IS A NOTE ON PLAN AT EXISTING |
| | PRODUCE CABINETS REGARDING MISTING WITHOUT A KEYNOTE |
| | DESIGNATION. PER WPB FBC 107.2.1, CLARIFY. INDICATE |
| | NOTE 17 ON THE PLANS OR IF IT DOES NOT APPLY, DELETE |
| | IT. |
| | |
| | 7. REGARDING P02.00 SANITARY DEMO PLAN: .I CANNOT FIND |
| | ON THE PLANS KEYNOTES 1 THROUGH 18. PER WPB FBC |
| | 107.2.1, INDICATE ON THE PLANS OR IF A NOTE DOES NOT |
| | APPLY, DELETE IT. |
| | |
| | 8. REGARDING P02.01 SANITARY PIPING PLAN: KEYNOTE 4 |
| | ADDRESSES P-2 AND D-3 IN THE ADDED FAMILY BATHROOM. |
| | PLUMBING FIXTURE AND DRAIN SCHEDULES DO NOT ADDRESS |
| | D-3. PER WPB FBC 107.2.2, CLARIFY AND RECONCILE |
| | DRAWINGS. |
| | |
| | 9.PER WPB FBC 107.2.1, PROVIDE A SLAB REPAIR DETAIL ON |
| | THE PLANS. SHOW THE WIDTH OF THE REPAIR, THE MINIMUM |
| | THICKNESS AND PSI OF THE CONCRETE TO BE REPLACED. SHOW |
| | SIZE, LENGTH, SPACING (ON CENTER), MINIMUM EMBEDMENT |
| | AND ANCHORING/ADHESIVE MATERIAL FOR DOWELS. THE REPAIR |
| | SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AS |
| | WELL AS THE REQUIRED VAPOR BARRIER OVER WELL COMPACTED |
| | SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE |
| | FOR FINAL INSPECTION. |
| | |
| | 10. PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL |
| | WITH A NOTE STATING, "HORIZONTAL PIPE SHALL BE |
| | SUPPORTED IN ACCORDANCE WITH FBC PL TABLE 308.5." |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |
| | |
| | 21060925 8989 OKEECHOBEE BLVD |
| | |
| | |