Plan Review Details - Permit 21060921
Plan Review Stops For Permit 21060921
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-12-22 Cont ID  
Sent By jgomez Date 2021-12-22 Time 11:26 Rev Time 0.00
Received By jgomez Date 2021-12-22 Time 08:24 Sent To  
Notes
2021-12-22 09:55:41RESIDENTIAL (R3) DECK ADDITION, SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21060921
  
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 ARCHITECTS WITH RESPECT TO EVALUATION OF DESIGN
 PROFESSIONALS DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT
 NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH THE
 FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT
 DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE
 TIMES FOR FAILURE TO CORRECT A CODE VIOLATION
 SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION,
 INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION,
 STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING,
 VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS
 SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF
 THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO
 CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH
 TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED
 FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT
 OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS
 REVIEW
  
  
 1- OK.
 2- OK.
  
 3- SHEET S-1:
  
 ORIGINAL COMMENT:
 A)NEW ALUMINUM POSTS SHOWN ON THE EXISTING 4" CONCRETE
 SLAB DON'T PROVIDE THE MINIMUM SIDECOVER CLEARANCE
 REQUIRED BY DETAIL S2. REVISE AS REQUIRED.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 REVISED DECK FRAMING PLAN SHOWS 4"X4" PT. WD. POSTS ON
 THE EXISTING CONCRETE SLAB. THERE IS NOT
 DETAIL/SPECIFICATIONS SHOWING HOW THE WOOD POSTS ARE
 ATTACHED TO THE CONCRETE SLAB. ENGINEER TO PROVIDE
 COMPLETE DETAIL/SPECIFICATIONS. SEC. R301.1
 FBC-RESIDENTIAL.
  
 ORIGINAL COMMENT:
 B) THIS IS NOT AN ALTERATION LEVEL 3. THIS IS A PORCH
 ADDITION. REVISE INFORMATION AS REQUIRED. SEC. 606
 FBC-EXISTING BUILDING.
  
 RESPONSE:
 THIS IS NOT AN ALTERATION LEVEL 1 EITHER. SCOPE OF WORK
 WAS CHANGED TO DECK ADDITION. THE PORCH WILL NOT BE
 BUILT. THEREFORE, THIS IS DECK ADDITION NOT ALTERATION
 LEVEL 1. REVISE INFORMATION AS REQUIRED. SEC. 606
 FBC-EXISTING BUILDING.
  
 ORIGINAL COMMENT:
 C)DESIGN CRITERIA SPECIFIES ASCE 7-10. THIS IS
 INCORRECT. THE CURRENT CODE 2020 FBC REFERENCES THE
 ASCE 7-16 NOT ASCE 7-10. REVISE AS REQUIRED.
 CHAPTER 553 F.S.
  
 RESPONSE:
 REPEAT COMMENT. NOT REVISED.
  
 4- DETAIL 1/S-2 ON SHEET S-2:
 A)OK
  
 ORIGINAL COMMENT:
 B)THERE IS NOT EXISTING CONCRETE STEM WALL. REVISE
 FASTENING OF 2X8 WD. BEAM TO THE COLUMN PEDESTAL. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. FOOTING TYPE AND BEAM SIZE WAS REVISED
 BUT THERE IS NOT EXISTING 8" CONC. STEM WALL. THEREFORE
 FASTENING OF THE (2)2"X6" WD. BEAM CAN NOT BE DONE WITH
 SCREWS AT 18" O.C. ENGINEER TO REVISE DETAIL AS
 REQUIRED.
  
 NEW COMMENT BASED ON REVISED DETAILS:
 C)FLOOR JOISTS SIZE WAS CHANGED TO 2X6 PT. WD. JOISTS.
 NEED TO REVISE THE JOIST HANGER SIZE. SIMPSON LUS28 IS
 TOO BIG. ENGINEER TO REVISE AS REQUIRED. SEC. R301.1
 FBC-RESIDENTIAL.
 NOTE: THIS APPLIES TO ENLARGED CONNECTION DETAIL SHOWN
 ON THE NEW DECK FRAMING PLAN ON SAME SHEET.
  
 ORIGINAL COMMENT:
 5-DECK RAILING DETAILS ON SHEET S-2: SPECIFY FASTENER
 TYPE AND SIZE FOR EACH WOOD MEMBER.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. FASTENERS NO SPECIFIED. ALSO, NEED TO
 PROVIDE DETAIL/SPECIFICATIONS SHOWING HOW THE NEW
 GUARDRAIL IS ATTACHED TO THE EXISTING WALL. SEC. R301.1
 FBC-RESIDENTIAL.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-07-15 Cont ID  
Sent By jgomez Date 2021-07-15 Time 13:57 Rev Time 0.00
Received By jgomez Date 2021-07-15 Time 11:04 Sent To  
Notes
2021-07-15 13:58:42RESIDENTIAL (R3) PORCH ADDITION, BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21060921
  
 1- BASED ON PLANS SUBMITTED THIS IS A PORCH ADDITION
 NOT JUST A DECK ADDITION. REVISE SCOPE OF WORK
 DESCRIPTION SPECIFIED ON THE PERMIT APPLICATION.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 2- INSULATED ROOF DETAIL ON SHEET S-3 IS A GENERIC
 DETAIL.
 A) ENGINEER OF RECORD NEEDS TO SPECIFY ALL FRAMING
 MEMBERS AND FASTENERS. ENGINEER TO SPECIFY BEAM SIZE,
 AND FASTENING TO THE COLUMNS. INSULATED PANEL SIZE AND
 FASTENERS TO THE BEAM AND TO THE EXISTING STRUCTURE.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 B) ENGINEER OF RECORD TO PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR THE " SCREEN WALL SYSTEM
 SEC. R301.1 FBC-RESIDENTIAL.
  
 C) SPECIFY ROOF SLOPE. SEC. R903.4 FBC-RESIDENTIAL.
  
 3- SHEET S-1:
 A)NEW ALUMINUM POSTS SHOWN ON THE EXISTING 4" CONCRETE
 SLAB DON'T PROVIDE THE MINIMUM SIDECOVER CLEARANCE
 REQUIRED BY DETAIL S2. REVISE AS REQUIRED.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 B) THIS IS NOT AN ALTERATION LEVEL 3. THIS IS A PORCH
 ADDITION. REVISE INFORMATION AS REQUIRED. SEC. 606
 FBC-EXISTING BUILDING.
  
 C)DESIGN CRITERIA SPECIFIES ASCE 7-10. THIS IS
 INCORRECT. THE CURRENT CODE 2020 FBC REFERENCES THE
 ASCE 7-16 NOT ASCE 7-10. REVISE AS REQUIRED.
 CHAPTER 553 F.S.
  
 4- DETAIL 1/S-2 ON SHEET S-2:
 A)PROVIDE COMPLETE SPECIFICATIONS FOR ALUMINUM COLUMN.
 SPECIFY ALUMINUM THICKNESS AND FASTENING AT TOP AND
 BOTTOM. PROVIDE SPECIFICATIONS FOR WELDING OF ALUMINUM
 COLUMN TO BASE. SPECIFY TOP AND BOTTOM PLATE SIZE.
 NOTE: SPECIFY BASE PLATE FOR CORNER COLUMNS.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 B)THERE IS NOT EXISTING CONCRETE STEM WALL. REVISE
 FASTENING OF 2X8 WD. BEAM TO THE COLUMN PEDESTAL.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 C)THERE IS NOT EXISTING CONCRETE STEM WALL. REVISE
 FASTENING OF THE FLOATING DECK.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 5-DECK RAILING DETAILS ON SHEET S-2: SPECIFY FASTENER
 TYPE AND SIZE FOR EACH WOOD MEMBER.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 6-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 ALUMINUM PANELS SPECIFIED BY THE ENGINEER OF RECORD.
  
 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 8- VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW.
 VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S
 OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS
 REQUIRED BY SEC. 109.3 CITY AMENDMENTS. VALUATION WAS
 UPDATED TO $10,000. THE PERMIT FEE BALANCE IS $154.62.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-01-03 Cont ID  
Sent By vbroglia Date 2022-01-03 Time 09:35 Rev Time 0.00
Received By vbroglia Date 2021-12-14 Time 14:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-07-15 Cont ID  
Sent By jgomez Date 2021-07-15 Time 13:59 Rev Time 0.00
Received By jgomez Date 2021-06-17 Time 08:15 Sent To I
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2021-12-22 Cont ID  
Sent By jgomez Date 2021-12-22 Time 12:52 Rev Time 0.00
Received By jgomez Date 2021-12-22 Time 12:52 Sent To  
Notes
2021-12-22 12:53:00REVISION, DECK ADDITION ONLY NO PORCH. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-07-15 Cont ID  
Sent By jgomez Date 2021-07-15 Time 13:59 Rev Time 0.00
Received By jgomez Date 2021-07-15 Time 13:58 Sent To  
Notes
2021-07-15 13:59:54IMPACT FEES
  
 PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT.
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2021-12-22 Cont ID  
Sent By jgomez Date 2021-12-22 Time 12:53 Rev Time 0.00
Received By jgomez Date 2021-12-22 Time 12:53 Sent To  
Notes
2021-12-22 12:53:25REVISION, DECK ADDITION ONLY NO PORCH. JG.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2021-07-13 Cont ID  
Sent By jgomez Date 2021-07-13 Time 13:54 Rev Time 0.00
Received By jgomez Date 2021-07-13 Time 13:54 Sent To  
Notes
2021-07-13 13:58:25ROOFING COMMENTS:
  
 1- -PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR THE ALUMINUM ROOF PANELS AS SPECIFIED
 BY THE ENGINEER OF RECORD.
  
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-12-17 Cont ID  
Sent By lcrespo Date 2021-12-17 Time 07:40 Rev Time 0.00
Received By lcrespo Date 2021-12-17 Time 07:39 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-06-17 Cont ID  
Sent By medwards Date 2021-06-17 Time 14:41 Rev Time 0.00
Received By medwards Date 2021-06-17 Time 14:39 Sent To  
Notes
2021-06-17 14:41:43ORIGINAL SIGNED AND SEALED PAPER DRAWING ROUTED TO
 STORAGE.ME

Review Stop Z ZONING
Rev No 2 Status F Date 2022-01-03 Cont ID  
Sent By vbroglia Date 2022-01-03 Time 09:33 Rev Time 0.00
Received By vbroglia Date 2022-01-03 Time 09:33 Sent To  
Notes
2022-01-03 09:35:1401/3/22 FAILED- PLEASE REVIEW PREVIOUS COMMENTS FOR
 ZONING ON 07/08/21
  
 VALENTINA BROGLIA
 ASSOCIATE PLANNER
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-07-08 Cont ID  
Sent By kalexand Date 2021-07-08 Time 19:02 Rev Time 0.00
Received By kalexand Date 2021-07-08 Time 19:02 Sent To  
Notes
2021-07-08 19:02:51ZONING PLAN REVIEW
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PROVIDE A CURRENT SURVEY, WHICH INCLUDES THE
 PROPERTY'S ADDRESS AND LEGAL DESCRIPTION. PLEASE
 ILLUSTRATE THE FOLLOWING ON THE SURVEY:
 - LOCATION OF PROPOSED DECK
 - DISTANCE FROM DECK TO PROPERTY LINES
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALLY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOG
 IN INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 KIZZI ALEXANDRE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1442
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved