Plan Review Details - Permit 21060844
Plan Review Stops For Permit 21060844
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2022-08-12 Cont ID  
Sent By rmcdouga Date 2022-08-12 Time 09:48 Rev Time 0.00
Received By rmcdouga Date 2022-08-12 Time 09:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-06-22 Cont ID  
Sent By rmcdouga Date 2022-06-22 Time 11:58 Rev Time 0.00
Received By rmcdouga Date 2022-05-16 Time 15:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-01-27 Cont ID  
Sent By rmcdouga Date 2022-01-27 Time 07:40 Rev Time 0.00
Received By rmcdouga Date 2022-01-27 Time 07:40 Sent To  
Notes
2022-01-27 07:45:44THE BEACH CLUB IS UNDER SEPARATE PERMIT #20120587 AND
 IS NOT PART OF THIS REVISION. THE PLAN SHEETS FOR THE
 BEACH CLUB WERE REMOVED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-12-13 Cont ID  
Sent By rmcdouga Date 2021-12-13 Time 16:32 Rev Time 0.00
Received By rmcdouga Date 2021-12-13 Time 13:30 Sent To  
Notes
2021-12-13 13:30:19PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 REVISION IS DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) [THE BEACH CLUB STRUCTURE IS UNDER SEPARATE BUILDING
 PERMIT (#20120587) WHICH HAS NOT BEEN ISSUED AT THIS
 TIME. THE PERMIT CAN NOT BE REVISED UNTIL THE PERMIT
 HAS BEEN ISSUED. THE PROPOSED REVISION DOES NOT SHOW
 THAT THE BEACH CLUB BUILDING MEETS THE REQUIREMENTS OF
 THE CITY'S FLOOD ORDINANCE, FEMA AND FBC 1612.4. EVEN
 AFTER THE PERMIT IS ISSUED BASED ON THE PREVIOUSLY
 APPROVED PLANS THE REVISION CAN NOT BE APPROVED UNTIL
 THE SPECIAL FLOOD HAZARD ISSUES HAVE BEEN ADDRESSED.]
 THE REVISED ELEVATIONS FOR THE BEACH CLUB SPECIFY TOS
 AS 7.47' NAVD88 AND FFE AS 7.64' NAVD88. IN THIS CASE
 THE FFE DOES NOT COMPLY WITH THE REQUIRED DESIGN FLOOD
 ELEVATION (DFE) OF 9' NAVD 88. PLEASE EXPLAIN HOW
 COMPLIANCE WITH THE CITY'S FLOOD ORDINANCE WILL BE
 ATTAINED. DRY FLOOD-PROOFING OR WET FLOOD PROOFING WITH
 FLOOD VENTS ARE OPTIONS. FBC 1612
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-07-22 Cont ID  
Sent By mcdouga Date 2021-07-22 Time 11:22 Rev Time 0.00
Received By rmcdouga Date 2021-07-19 Time 14:28 Sent To  
Notes
2021-07-22 11:15:49PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 REVISION IS DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE REVISED ELEVATIONS FOR THE GROUND LEVEL OF THE
 RESIDENTIAL TOWERS SPECIFY THE TOP OF SLAB (TOS) AS
 8.9' NAVD 88 AND THE FINISH FLOOR ELEVATION (FFE) AS
 9.07' NAVD 88. THIS PROJECT IS LOCATED IN A SPECIAL
 FLOOD HAZARD AREA (SFHA) AND THE REQUIRED DESIGN FLOOD
 ELEVATION (DFE) IS 9' NAVD 88. ALL OF THE AREAS OF THE
 BUILDINGS AND ALL OF THE EQUIPMENT THAT SERVICE THE
 BUILDINGS ARE REQUIRED TO BE AT OR ABOVE THE 9' DFE. BY
 NOT HAVING THE TOS AT THE 9' NAVD 88 ELEVATION, ALL OF
 THE SLAB INCLUDING EQUIPMENT ROOMS WILL HAVE TO BE
 COVERED WITH SOMETHING SO THAT IT MEETS THE REQUIRED
 ELEVATION. THIS MAY BECOME A PROBLEM WHEN THE PROJECT
 IS NEARING CONSTRUCTION AND TEMPORARY CERTIFICATES OF
 OCCUPANCY OR CERTIFICATES OF OCCUPANCY ARE BEING
 REQUESTED. PLEASE CLARIFY HOW YOU INTEND TO COMPLY WITH
 THE CITY'S FLOOD ORDINANCE. FBC 1612
  
 2) THE REVISED ELEVATIONS FOR THE GROUND LEVEL OF THE
 PARKING GARAGE SPECIFIES THE ELEVATION FOR THE TOP OF
 SLAB (TOS) AS 8.9' NAVD 88. SHOW WHAT WILL BE DONE TO
 THE GARAGE TO MAKE IT COMPLY WITH THE CITY'S FLOOD
 ORDINANCE. FBC 1612
  
 3) THE EQUIPMENT ROOMS AND FUTURE USE RESIDENTIAL ROOMS
 ON THE GROUND FLOOR OF THE GARAGE ARE SPECIFIED WITH
 THE TOP OF SLAB (TOS) AS 8.9' NAVD 88 AND THE FINISH
 FLOOR (FF) AS 9.07' NAVD 88. THESE AREAS ALSO WILL
 REQUIRED SOME TYPE OF TOPPING ON THE SLAB TO REACH THE
 REQUIRED DFE ELEVATION. FBC 1612
  
 4) THE REVISED ELEVATIONS FOR THE BEACH CLUB SPECIFY
 TOS AS 7.47' NAVD88 AND FFE AS 7.64' NAVD88. IN THIS
 CASE THE FFE DOES NOT COMPLY WITH THE REQUIRED DESIGN
 FLOOD ELEVATION (DFE) OF 9' NAVD 88. PLEASE EXPLAIN HOW
 COMPLIANCE WITH THE CITY'S FLOOD ORDINANCE WILL BE
 ATTAINED. DRY FLOOD-PROOFING OR WET FLOOD PROOFING WITH
 FLOOD VENTS ARE OPTIONS. FBC 1612
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2022-08-03 Cont ID  
Sent By jleahy Date 2022-08-03 Time 12:08 Rev Time 0.00
Received By jleahy Date 2022-08-02 Time 12:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-05-19 Cont ID  
Sent By jleahy Date 2022-05-19 Time 15:55 Rev Time 0.00
Received By jleahy Date 2022-05-19 Time 13:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-12-14 Cont ID  
Sent By jleahy Date 2021-12-14 Time 09:41 Rev Time 0.00
Received By jleahy Date 2021-12-13 Time 15:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-07-19 Cont ID  
Sent By jleahy Date 2021-07-19 Time 16:31 Rev Time 0.00
Received By jleahy Date 2021-07-13 Time 15:18 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2021-08-20 Cont ID  
Sent By rrossano Date 2021-08-20 Time   Rev Time 0.00
Received By rrossano Date 2021-08-20 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2022-07-21 Cont ID  
Sent By clfranci Date 2022-07-21 Time   Rev Time 0.00
Received By clfranci Date 2022-07-21 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-04-20 Cont ID  
Sent By clfranci Date 2022-04-20 Time   Rev Time 0.00
Received By clfranci Date 2022-04-20 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-11-15 Cont ID  
Sent By pleduc Date 2021-11-15 Time   Rev Time 0.00
Received By pleduc Date 2021-11-10 Time 12:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-07-08 Cont ID  
Sent By pleduc Date 2021-07-08 Time   Rev Time 0.00
Received By pleduc Date 2021-06-29 Time 14:11 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 6 Status P Date 2022-11-02 Cont ID  
Sent By ccole Date 2022-11-02 Time 10:49 Rev Time 0.00
Received By ccole Date 2022-11-01 Time 16:49 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 5 Status P Date 2022-10-03 Cont ID  
Sent By ccole Date 2022-10-03 Time 11:36 Rev Time 0.00
Received By ccole Date 2022-10-03 Time 10:14 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2022-07-21 Cont ID  
Sent By ccole Date 2022-07-21 Time 15:31 Rev Time 0.00
Received By ccole Date 2022-07-21 Time 11:53 Sent To  
Notes
2022-07-21 15:32:082ND REVIEW FBC-2017 FUEL GAS
 PERMIT- 21060844
 7/21//22
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITION NOTES FOR
 CLARIFICATION. PLEASE CONTACT ME IF YOU HAVE QUESTIONS.
  
 1) FAILED A & B. SHEET P4.11N NOTE CORRECTIONS- SEC.
 107.2.1 WPB: A) NOTE #8 IS INDICATED TO BE OMITTED BUT
 IT IS SHOWN ON THE RISER. B) NOTE #10 SHOWS INCORRECT
 TOTAL GAS LOAD FOR THE SYSTEM. NO CORRECTIONS PROVIDED.
  
 2) FAILED. P4.11N REGULATORS- SEC. 410.1- 410.3: A)
 LABEL ALL LOW-PRESSURE REGULATOR LOCATIONS. B) PROVIDE
 VENTING DETAILS IF APPLICABLE- VENT PIPING MATERIAL,
 PIPING RUNS AND DISCHARGE LOCATIONS. C) SUBMIT
 MANUFACTURER?S SPECIFICATIONS MARKED UP TO SHOW MODEL
 SELECTION AND INPUT AND OUTPUT. PIPE SIZES AND
 PRESSURES. LOW PRESSURE REGULATORS REQUIRED AT POOL
 HEATERS AND BBQ?S NOT LABELED. SPECS CAN BE DEFERRED
 SUBMITTALS.
  
 3) FAILED. P4.11N: SUBMIT MANUFACTURER'S SPECIFICATIONS
 AND INSTALLATION INSTRUCTIONS FOR THE BBQ GRILLS AND
 THE FIREPIT- SECS. 623.1 & 636.1 FBC FG. A) PROVIDE BBQ
 GRILL ELEVATION VIEWS BASED ON THE INSTALL GUIDELINES
 SHOWING CLEARANCES TO COMBUSTIBLES AND THE OVERHEAD
 CANOPY. PLEASE NOTE THAT EXHAUST HOODS MAY BE REQUIRED
 PER THE MANUFACTURER'S GUIDELINES- SECS. 305.1 & 305.8
 B) PROVIDE EQUIPMENT ANCHORING DETAILS FOR ALL OUTDOOR
 APPLIANCES- 301.10. NOT PROVIDED. DRAWINGS ARE REQUIRED
 BUT ANCHORING AND SPECS CAN BE DEFERRED.
  
 4) FAILED. P4.11N: SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE SOLENOID VALVES AND GAS LEAK DETECTORS- SED.
 305.1 FBC FG. CAN BE DEFERRED.
  
 5) FAILED. P4.11N: SUBMIT MANUFACTURER'S SPECIFICATIONS
 AND INSTALLATION MANUAL FOR THE GASTITE PIPING- SEC.
 404.2 FBC FG. CAN BE DEFERRED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2022-05-02 Cont ID  
Sent By ccole Date 2022-05-02 Time 11:08 Rev Time 0.00
Received By ccole Date 2022-04-29 Time 19:02 Sent To  
Notes
2022-05-02 11:09:021ST REVIEW FBC-2017 FUEL GAS
 PERMIT- 21060844
 5/2/22
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P4.11N NOTE CORRECTIONS- SEC. 107.2.1 WPB: A)
 NOTE #8 IS INDICATED TO BE OMITTED BUT IT IS SHOWN ON
 THE RISER. B) NOTE #10 SHOWS INCORRECT TOTAL GAS LOAD
 FOR THE SYSTEM. C) PLACE NOTE #14 AT ALL UNDERGROUND
 GASTITE PIPING LOCATIONS.
  
 2) P4.11N REGULATORS- SEC. 410.1- 410.3: A) LABEL ALL
 LOW-PRESSURE REGULATOR LOCATIONS. B) PROVIDE VENTING
 DETAILS IF APPLICABLE- VENT PIPING MATERIAL, PIPING
 RUNS AND DISCHARGE LOCATIONS. C) SUBMIT MANUFACTURER?S
 SPECIFICATIONS MARKED UP TO SHOW MODEL SELECTION AND
 INPUT AND OUTPUT. PIPE SIZES AND PRESSURES.
  
 3) P4.11N: SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE BBQ GRILLS AND THE
 FIREPIT- SECS. 623.1 & 636.1 FBC FG. A) PROVIDE BBQ
 GRILL ELEVATION VIEWS BASED ON THE INSTALL GUIDELINES
 SHOWING CLEARANCES TO COMBUSTIBLES AND THE OVERHEAD
 CANOPY. PLEASE NOTE THAT EXHAUST HOODS MAY BE REQUIRED
 PER THE MANUFACTURER'S GUIDELINES- SECS. 305.1 & 305.8
 B) PROVIDE EQUIPMENT ANCHORING DETAILS FOR ALL OUTDOOR
 APPLIANCES- 301.10.
  
 4) P4.11N: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 SOLENOID VALVES AND GAS LEAK DETECTORS- SED. 305.1 FBC
 FG.
  
 5) P4.11N: SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION MANUAL FOR THE GASTITE PIPING- SEC. 404.2
 FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2021-11-23 Cont ID  
Sent By lcrespo Date 2021-11-23 Time 09:05 Rev Time 0.00
Received By lcrespo Date 2021-11-23 Time 09:05 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-07-19 Cont ID  
Sent By lcrespo Date 2021-07-19 Time 17:10 Rev Time 0.00
Received By lcrespo Date 2021-07-19 Time 17:10 Sent To  
Notes
2021-07-19 17:13:1107/19/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 ON SHEET 4 P4.11N;
  
 A. THE GAS CHART HAS BEEN DELETED. WOULD YOU PLEASE
 PROVIDE OR PUT A NOTE PER THE 2017 FBC FG SEC. 402.3?
  
 B. THERE WERE TWO BBQ UNITS SHOWN IN THE NEW REVISION,
 FOUR SHOWN IN THE POOL AREA. ARE THESE BBQ?S NOT
 INCLUDED IN THE REVISED GAS SYSTEM BUT ARE IN THE
 KEYNOTES? ARE THEY THE PROPANE TANK TYPE? WOULD YOU
 PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 C. IN GENERAL NOTES, COLOR DETECTION TAPE IS NOT
 APPROVED AN APPROVED BY THE LOCAL AJH. AN 18? GAUGE
 WIRE, A YELLOW INSULATED COPPER TRACER WIRE, WILL BE
 REQUIRED PER THE 2017 FBC SEC. 404.17.3.
  
 D. THE NEW FOUR BBQ SEEM TO BE ENCLOSED AND MAY REQUIRE
 HOOD VENT PER THE MANUFACTURERS SPECIFICATION. IF THAT
 IS THE CASE, PLEASE PROVIDE SPECIFICATIONS OR MAKE
 NOTES ON PLANS PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 E. CSST PIPE IN THE SLEEVE WILL REQUIRE VENTING PER THE
 AJH AND AS SHOWN ON THE MANUFACTURES SPECIFICATION.
 PLEASE PROVIDE A NOTE UNDER GENERAL NOTES PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 F. ON THE FUTURE SERVICES, IT SAYS TWO SERVICES, BUT
 PLANS SHOW THREE. WOULD YOU PLEASE CLARIFY PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date   Cont ID  
Sent By   Date 2022-11-02 Time   Rev Time 0.00
Received By lmarchan Date 2022-10-18 Time 16:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date   Cont ID  
Sent By   Date 2022-10-03 Time   Rev Time 0.00
Received By aoliver Date 2022-09-21 Time 06:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-08-12 Cont ID  
Sent By rmcdouga Date 2022-08-12 Time 10:44 Rev Time 0.00
Received By rmcdouga Date 2022-07-14 Time 13:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-07-12 Cont ID  
Sent By cpuell Date 2022-07-12 Time 06:51 Rev Time 0.00
Received By cpuell Date 2022-04-18 Time 15:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-04-10 Cont ID  
Sent By lmarchan Date 2022-04-10 Time 07:02 Rev Time 0.00
Received By lmarchan Date 2021-10-28 Time 09:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-08-26 Cont ID  
Sent By lmarchan Date 2021-08-26 Time 16:45 Rev Time 0.00
Received By lmarchan Date 2021-06-28 Time 13:59 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2021-07-21 Cont ID  
Sent By rmcdouga Date 2021-07-21 Time 16:22 Rev Time 0.00
Received By rmcdouga Date 2021-07-21 Time 16:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2022-05-13 Cont ID  
Sent By medwards Date 2022-05-13 Time 15:31 Rev Time 0.00
Received By medwards Date 2022-05-13 Time 15:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2022-02-02 Cont ID  
Sent By medwards Date 2022-02-02 Time 09:16 Rev Time 0.00
Received By medwards Date 2022-02-02 Time 09:16 Sent To  
Notes
2022-02-02 09:17:173RD CYCLE REVIEW FBC-2020 MECHANICAL
 PERMIT-21060844
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THIS IS THE 3RD TIME FOR A COMMENT ON OUTDOOR AIR
 CALCULATIONS. PLEASE RESPOND.
  
 SHEET M3.02- UNIT A2: THE DRYER VENT FOR THIS DRYER
 INSTALLATION HAS A TOTAL OF 7 90 DEGREE TURNS IN THE
 DESIGN. PLEASE SHOW FROM THE MANUFACTURER THAT THIS
 DRYER WILL ALLOW THE EXHAUST SYSTEM TO HAVE THAT MANY
 90?S. SHEET M3.03- UNIT B4, UNIT C1, SHEET M3.01- UNIT
 A3 ALL HAVE SIMILAR ISSUES. FBC M 504.8.4.2
  
 2) SHEET M-4.02: PLEASE UNDERSTAND FBC M 403.3.1.1
 TELLS US WE MUST USE THE OCCUPANT DENSITY FOR EACH USE
 OF SPACE AND NOT THE ARCHITECTURAL OCCUPANCY COUNT.
 PLEASE REWORK THE OUTDOOR AIR CALCULATIONS TO REFLECT
 THIS. THERE ARE OCCUPANCIES IN THE COMMON AREAS THAT
 HAVE A LOW OCCUPANT COUNT WHICH IN TURN DOES NOT LINE
 UP WITH THE OCCUPANCY DENSITY OF THE TABLE 403.3.1.1.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-11-08 Cont ID  
Sent By medwards Date 2021-11-08 Time 15:30 Rev Time 0.00
Received By medwards Date 2021-11-08 Time 15:30 Sent To  
Notes
2021-11-08 15:30:492ND REVIEW FBC-2020 MECHANICAL
 PERMIT-21060844
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE TAKE ANOTHER LOOK AT YOUR OUTDOOR AIR
 CALCULATIONS AS SEVERAL SEEM TO BE LOW. THE TV VIEWING
 AREA COULD BE CONSIDERED A DAY ROOM, THE THEATRE COULD
 ALSO. THE MULTIPURPOSE ROOMS SEEM TO HAVE A LOW
 OCCUPANT COUNT. PLEASE USE THE OCCUPANT DENSITY COLUMN
 FOR EACH USE OF SPACE. ASHRAE 62.1-2013 TABLE 6.2.2.1
  
 2) COMMENT 2 OF PREVIOUS CYCLE REVIEW. - SHEET M2.01G:
 PLEASE PROVIDE MECHANICAL SIZING CALCULATIONS FOR THIS
 NEW HP-G1.6. THE RESPONSE LETTER SAID THE LOAD
 CALCULATION WAS ATTACHED BUT I DO NOT SEE IT.
  
 3) CLOTHES DRYER EXHAUST IS COVERED IN FBC M 504 AND I
 WOULD NOT THINK TO LOOK AT THE A SHEETS FOR DRYER
 INFORMATION. PLEASE PROVIDE THE SHEET NUMBERS THAT THE
 DRYER INFORMATION IS LOCATED.
  
 4) THE DRYER VENT TABLE LISTED ON SHEET M3.02 ONLY
 LISTS INFORMATION FOR UP TO 4- 90 DEGREE TURNS. PLEASE
 PROVIDE MANUFACTURER?S INSTALLATION INSTRUCTIONS FOR
 THE ADDITIONAL 90 DEGREE TURNS SHOWN ON YOUR DRAWINGS.
 FBC M 504.8.4.2
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-07-15 Cont ID  
Sent By medwards Date 2021-07-15 Time 08:04 Rev Time 0.00
Received By medwards Date 2021-07-12 Time 10:31 Sent To  
Notes
2021-07-15 08:04:321ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21060844
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR THE
 CHANGED FLOOR PLAN FOR SHEET M2.01S
  
 2) SHEET M2.01G- PLEASE PROVIDE MECHANICAL EQUIPMENT
 SIZING CALCULATIONS FOR THIS NEW HP-G1.6.
  
 3) SHEET M2.01G- PLEASE PROVIDE OUTDOOR AIR
 CALCULATIONS FOR THE NEW HP-G1.6 AND SHOW HOW THE
 OUTDOOR AIR WILL BE PROVIDED.
  
 4) SHEET M2.01N- PLEASE EXPLAIN THE MISSING SPF-1-1 IN
 THE STAIRWAY.
  
 5) SHEET M3.01- UNIT A3 THE DRYER DUCT ROUTE HAS
 CHANGED WHICH NOW SHOWS 6 90 DEGREE ELBOWS. PLEASE
 PROVIDE DRYER MANUFACTURE INSTALLATION INSTRUCTIONS
 SHOWING THAT THIS MANY 90 DEGREE ELBOWS ARE ALLOWED FOR
 THE SPECIFIC DRYER USED. FBC M 504.8.4.2
  
 6) SHEET M3.02- UNIT B6-THE NEW PATH FOR THE DRYER
 EXHAUST DUCT HAS CHANGED. PLEASE PROVIDE THE NEW DUCT
 LENGTH. FBC M 504.8.4.2
  
 7) SHEET M3.02- UNIT B1- PLEASE PROVIDE THE NEW DRYER
 DUCT LENGTH. FBC M 504.8.4.2
  
 8) SHEET M3.02- UNIT A2- THE NEW DRYER DUCT PATH HAS 7
 90 DEGREE TURNS IN THE DUCT. PLEASE PROVIDE
 INSTALLATION INSTRUCTIONS FROM THE DRYER MANUFACTURER
 STATING THAT THE DUCT WORK CAN HAVE THIS MANY 90 DEGREE
 TURNS.
  
 9) SHEET M3.03- UNIT C1- PLEASE SHOW DRYER DUCT LENGTH
 AND PROVIDE INFORMATION FROM DRYER MANUFACTURER THAT 5
 90 DEGREE ELBOWS ARE ALLOWED IN THE DRYER DUCT. FBC M
 504.8.4.2
  
 10) SHEET M3.03- UNIT B5- PLEASE PROVIDE DEVELOPMENTAL
 LENGTH OF THE DRYER DUCT. FBC M 504.8.4.2
  
 11) SHEET M3.03- UNIT B4- PLEASE PROVIDE THE DEVELOPED
 LENGTH OF DRYER DUCT AND INFORMATION FROM DRYER
 MANUFACTURER ALLOWING THE NUMBER OF 90 DEGREE ELBOWS
 SHOW ON THE DRAWING. FBC M 504.8.4.2
  
 12) SHEET M4.02- PLEASE PROVIDE OUTDOOR AIR
 CALCULATIONS BASED ON 2017 FBC M 403.3.1.1 AND TABLE
 403.3.1.1. AS AN ALTERNATE MEANS AND METHODS YOU CAN
 SUBMIT A COMPLETE DESIGN BASED ON THE ASHRAE 62.1-2013.
 THIS WOULD MEAN A COMPLETE DESIGN NOT JUST THE OUTDOOR
 AIR CALCULATIONS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 6 Status P Date 2022-11-02 Cont ID  
Sent By ccole Date 2022-11-02 Time 10:48 Rev Time 0.00
Received By ccole Date 2022-11-01 Time 16:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status F Date 2022-10-03 Cont ID  
Sent By ccole Date 2022-10-03 Time 11:36 Rev Time 0.00
Received By ccole Date 2022-10-03 Time 10:14 Sent To  
Notes
2022-10-03 13:10:515TH REVIEW FBC-2017 PLUMBING
 PERMIT- 21060844
 10/3/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. THE PLANS WERE NOT
 CORRECTED ACCORDING TO PREVIOIUS COMMENTS #6, 10, & 11
 BELOW. PLEASE NOTE NO BACKFLOW PERMIT APPLICATIONS HAVE
 NOT BEEN SUBMITTED FOR POTABLE WATER SERVICES,
 FIRELINES, COOLING TOWERS, BOILERS, AND IRRIGATION AND
 POOL RECIRCULATION SYSTEMS SUPPLIED BY POTABLE WATER
 LINES- SECS. C, D, & E WPB UTILITES CROSS CONNECTION
 MANUAL, AND SEC. 608.3 FBC P.
 THE CITY OF WPB BUILDING DEPT. REQUIRES THAT PERMIT
 APPLICATIONS FOR POTABLE WATER BACKFLOW PREVENTERS AND
 GREASE INTERCEPTORS ARE REQUIRED TO BE SUBMITTED PRIOR
 TO ISSUANCE OF THE PRIMARY PERMIT. YOU CAN SUBMIT AN
 APPLICATION "TBD" (TO BE DETERMINED) IF YOU DO NOT HAVE
 A CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT
 APPLICATION TO [email protected] . YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER
 YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL
 AND I WILL CHANGE THE REVIEW STATUS TO PASS.
  
 6) FAILED. P4.05N: AN RPZ BACKFLOW PREVENTER DEVICE IS
 REQUIRED FOR THE WATER SUPPLY TO THE COOLING TOWERS-
 SEC. 608.3 FBC P AND SEC E, TABLE 1.1 WPB UTILITIES
 CROSS-CONNECTION MANUAL. PLEASE NOTE A SEPARATE PERMIT
 IS REQUIRED- SEC. 105.1 WPB. PLEASE PROVIDE NOTES ON
 THE DRAWINGS TO INDICATE COMPLIANCE. NOT PROVIDED.
  
 10) FAILED. P5.05S: RPZ BACKFLOW PREVENTER DEVICES ARE
 REQUIRED AT EACH WATER SUPPLY PIPE TO THE COOLING
 TOWERS- SECS. 608.3 FBC P AND SEC E, TABLE 1.1 WPB
 UTILITIES CROSS-CONNECTION MANUAL. PLEASE NOTE SEPARATE
 PERMITS ARE REQUIRED- SEC. 105.1 WPB. PLEASE PROVIDE
 NOTES ON THE DRAWINGS TO INDICATE COMPLIANCE. NOT
 PROVIDED.
  
 11) FAILED. P5.05S: PROVIDE ASSE 1012 OR CSA B64.3
 APPROVED BACKFLOW PREVENTERS WITH INTERMEDIATE
 ATMOSPHERIC VENTS TO THE BOILERS- SEC. 608.1.7.2 FBC P.
 NOT PROVIDED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status F Date 2022-07-21 Cont ID  
Sent By ccole Date 2022-07-21 Time 14:56 Rev Time 0.00
Received By ccole Date 2022-07-21 Time 11:53 Sent To  
Notes
2022-07-21 14:56:402ND REVIEW FBC-2017 PLUMBING
 PERMIT- 21060844
 7/21/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS ARE LISTED
 BELOW WITH ADDITIONAL NOTES IN CAPS. THE SUBMITTED
 NARRATIVE DID NOT APPEAR TO ADDRESS ALL OF THE
 COMMENTS. PLEASE CONTACT ME IF YOU HAVE QUESTIONS.
  
 1) FAILED. REVISE SHEETS A1.201N & A1.201S TO MATCH THE
 REVISED PLUMBING AND GAS PLANS SHOWING THE NEW OUTDOOR
 KITCHEN AND THE MULTI-PURPOSE FIXTURES AND APPLIANCES-
 SEC. 107.2.1 WPB. THE ARCHITECT REVISED THE PLANS BUT
 DID NOT ADD THE OUTDOOR KITCHEN ON THE DRAWINGS AS
 REQUESTED.
  
 3) FAILED. SHEETS P2.01N & P2.01S: PROVIDE CANOPY
 DRAINAGE DETAILS- DRAIN LOCATIONS, DRAIN PIPE RUNS AND
 DISCHARGE LOCATIONS- SEC. 1101.2 FBC P. NOT PROVIDED.
  
 4) FAILED. P4.05N: SUBMIT MANUFACTURER'S SPECIFICATIONS
 AND INSTALLATION GUIDELINES FOR THE EYE WASH STATION-
 SECS. 411.2 FBC P. THE STATION SHALL MEET THE IZ358.1
 STANDARD. PROVIDE DETAILS ON THE PLAN SHOWING
 COMPLIANCE WITH THE GUIDELINE. PLEASE NOTE THAT TEPID
 WATER- TEMPERATURE BETWEEN 60 DEGREES F AND 100 DEGREES
 F- SHALL BE DELIVERED FROM THE STATION PER THE
 STANDARD. NOT PROVIDED.
  
 5) FAILED. P4.05N: SUBMIT MANUFACTURER'S SPECIFICATIONS
 AND INSTALLATION GUIDELINES FOR THE STEAM GENERATOR-
 SEC. 502.1 FBC P. A) PROVIDE A WATER HAMMER ARRESTOR
 FOR THE SUPPLY LINE, AND INDICATE THE TYPE OF BACKFLOW
 PREVENTER TO BE INSTALLED- SECS. 604.9 & 608.3 FBC P.
 NOT PROVIDED.
  
 6) FAILED. P4.05N: AN RPZ BACKFLOW PREVENTER DEVICE IS
 REQUIRED FOR THE WATER SUPPLY TO THE COOLING TOWERS-
 SEC. 608.3 FBC P AND SEC E, TABLE 1.1 WPB UTILITIES
 CROSS-CONNECTION MANUAL. PLEASE NOTE A SEPARATE PERMIT
 IS REQUIRED- SEC. 105.1 WPB. PLEASE PROVIDE NOTES ON
 THE DRAWINGS TO INDICATE COMPLIANCE. NOT PROVIDED.
  
 10) FAILED. P5.05S: RPZ BACKFLOW PREVENTER DEVICES ARE
 REQUIRED AT EACH WATER SUPPLY PIPE TO THE COOLING
 TOWERS- SECS. 608.3 FBC P AND SEC E, TABLE 1.1 WPB
 UTILITIES CROSS-CONNECTION MANUAL. PLEASE NOTE SEPARATE
 PERMITS ARE REQUIRED- SEC. 105.1 WPB. PLEASE PROVIDE
 NOTES ON THE DRAWINGS TO INDICATE COMPLIANCE. NOT
 PROVIDED.
  
 11) FAILED. P5.05S: PROVIDE ASSE 1012 OR CSA B64.3
 APPROVED BACKFLOW PREVENTERS WITH INTERMEDIATE
 ATMOSPHERIC VENTS TO THE BOILERS- SEC. 608.1.7.2 FBC P.
 NOT PROVIDED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2022-04-29 Cont ID  
Sent By ccole Date 2022-04-29 Time 18:57 Rev Time 0.00
Received By ccole Date 2022-04-28 Time 14:08 Sent To  
Notes
2022-04-29 18:58:431ST REVIEW FBC-2017 PLUMBING
 PERMIT- 21060844
 4/29/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REVISE SHEETS A1.201N & A1.201S TO MATCH THE REVISED
 PLUMBING AND GAS PLANS SHOWING THE NEW OUTDOOR KITCHEN
 AND THE MULTI-PURPOSE FIXTURES AND APPLIANCES- SEC.
 107.2.1 WPB.
  
 2) PROVIDE ENLARGED DRAWINGS FOR OUTDOOR KITCHEN AND
 MULTIPURPOSE KITCHEN SHOWING COMPLIANCE WITH THE FBC
 ACC. PLEASE INCLUDE:
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR SINKS-
 SEC. 606.2.
 B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR
 APPLIANCES- SEC. 804.6.
 C) HEIGHTS OF SINKS MEASURED FROM THE FINISHED FLOORS
 TO THE SINK RIM OR COUNTER- SEC. 606.2.
 D) REACH HEIGHTS FOR APPLIANCE CONTROLS- SEC. 308.1.
  
 3) SHEETS P2.01N & P2.01S: PROVIDE CANOPY DRAINAGE
 DETAILS- DRAIN LOCATIONS, DRAIN PIPE RUNS AND DISCHARGE
 LOCATIONS- SEC. 1101.2 FBC P.
  
 4) P4.05N: SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION GUIDELINES FOR THE EYE WASH STATION- SECS.
 411.2 FBC P. THE STATION SHALL MEET THE IZ358.1
 STANDARD. PROVIDE DETAILS ON THE PLAN SHOWING
 COMPLIANCE WITH THE GUIDELINE. PLEASE NOTE THAT TEPID
 WATER- TEMPERATURE BETWEEN 60 DEGREES F AND 100 DEGREES
 F- SHALL BE DELIVERED FROM THE STATION PER THE
 STANDARD.
  
 5) P4.05N: SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION GUIDELINES FOR THE STEAM GENERATOR- SEC.
 502.1 FBC P. A) PROVIDE A WATER HAMMER ARRESTOR FOR THE
 SUPPLY LINE, AND INDICATE THE TYPE OF BACKFLOW
 PREVENTER TO BE INSTALLED- SECS. 604.9 & 608.3 FBC P.
  
 6) P4.05N: AN RPZ BACKFLOW PREVENTER DEVICE IS REQUIRED
 FOR THE WATER SUPPLY TO THE COOLING TOWERS- SEC. 608.3
 FBC P AND SEC E, TABLE 1.1 WPB UTILITIES
 CROSS-CONNECTION MANUAL. PLEASE NOTE A SEPARATE PERMIT
 IS REQUIRED- SEC. 105.1 WPB. PLEASE PROVIDE NOTES ON
 THE DRAWINGS TO INDICATE COMPLIANCE.
  
 7) P412N: THIS SHEET IS CALLED OUT IN THE NARRATIVE BUT
 WAS NOT UPLOADED FOR REVIEW- SEC. 107.2.1 WPB.
  
 8) P5.01S: THE RISER INDICATES WASTE WATER FROM THE
 POOL EQUIPMENT ROOM DISCHARGING TO THE SANITARY SYSTEM.
 PLEASE NOTE THAT SWIMMING POOL WASTEWATER IS PROHIBITED
 FROM DRAINING INTO THE SANITARY SYSTEM- SEC. 90-126(5).
 SWIMMING POOL WATER SHALL NOT BE DISCHARGED TO SANITARY
 SEWER WITHOUT PRIOR APPROVAL FROM THE PUBLIC UTILITIES
 DEPARTMENT.
 SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY
 STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED
 ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM
 BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER'S
 SPECIFICATION FOR THE DECHLORINATION SYSTEM FOR REVIEW
 AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL
 WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED:
 A) THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH
 TO KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE
 INLET).
 B) NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE
 INLET TO DISCHARGE EFFLUENT.
 C) WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE
 ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL OWNERS
 PROPERTY BEFORE DISCHARGING ON CITY PROPERTY.
 D) DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING
 PROPERTY.
 E) FOR TECHNICAL QUESTIONS, DON'T HESITATE TO CONTACT
 O&M SUPERINTENDENT STEPHON HARRIS AT [email protected] OR
 561-822-2168.
 F) FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS,
 PLEASE CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE
 SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561)
 822-2062 OR [email protected].
  
 SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY
 STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED
 ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM
 BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER'S
 SPECIFICATION FOR THE DECHLORINATION SYSTEM FOR REVIEW
 AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL
 WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED:
 THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH TO
 KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE
 INLET).
 NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE
 INLET TO DISCHARGE EFFLUENT.
 WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE ALLOWED
 TO FILTER THROUGH GRASS AREA ON THE POOL OWNERS
 PROPERTY BEFORE DISCHARGING ON CITY PROPERTY.
 DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING
 PROPERTY.
 FOR TECHNICAL QUESTIONS, DON'T HESITATE TO CONTACT O&M
 SUPERINTENDENT STEPHON HARRIS AT [email protected] OR
 561-822-2168.
 FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS, PLEASE
 CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE
 SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561)
 822-2062 OR [email protected].
  
 9) P5.01S: PROVIDE AN EQUIPMENT SCHEDULE FOR THE SUMP
 PUMP AND PIT, AND AN ENLARGED PIPING DETAIL- SEC.
 712.2- 712.3.3.2 FBC P.
  
 10) P5.05S: RPZ BACKFLOW PREVENTER DEVICES ARE REQUIRED
 AT EACH WATER SUPPLY PIPE TO THE COOLING TOWERS- SECS.
 608.3 FBC P AND SEC E, TABLE 1.1 WPB UTILITIES
 CROSS-CONNECTION MANUAL. PLEASE NOTE SEPARATE PERMITS
 ARE REQUIRED- SEC. 105.1 WPB. PLEASE PROVIDE NOTES ON
 THE DRAWINGS TO INDICATE COMPLIANCE.
  
 11) P5.05S: PROVIDE ASSE 1012 OR CSA B64.3 APPROVED
 BACKFLOW PREVENTERS WITH INTERMEDIATE ATMOSPHERIC VENTS
 TO THE BOILERS- SEC. 608.1.7.2 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-11-23 Cont ID  
Sent By lcrespo Date 2021-11-23 Time 09:05 Rev Time 0.00
Received By lcrespo Date 2021-11-22 Time 12:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-07-19 Cont ID  
Sent By lcrespo Date 2021-07-19 Time 17:09 Rev Time 0.00
Received By lcrespo Date 2021-07-14 Time 16:07 Sent To  
Notes
2021-07-19 17:10:2007/19/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET 2.01N;
 A. THE RESTROOM WAS MOVED, AND N-105 A LABEL IS NOT
 PRESENT. WOULD YOU PLEASE LABEL PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS?
  
 B. THE SINK IN THE MULTI-PURPOSE ROOM IS NOT SHOWN, AND
 NEITHER ARE THE REFRIGERATOR AND ICE MACHINE. WOULD YOU
 PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 C. THE SINK LAYOUT, BBQ, AND SHOWER ARE NOT SHOWN, AND
 THE SANITARY IS STILL SHOWS. WHERE WERE THEY MOVE TO?
 WOULD YOU PLEASE SHOW THE NEW LOCATION AND LABEL PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS?
  
 D. IT SHOWS TWO BBQ AND A SINK IN A DIFFERENT LOCATION.
 WOULD YOU PLEASE PROVIDE THE DRAINAGE AND GAS TO IT? IF
 THE BBQ IS ENCLOSED IN A ROOM, THEY MAY REQUIRE A HOOD
 SYSTEM. THAT WILL NEED TO BE DETERMINED AND NOTED ON
 PLANS PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 E. PUMP ROOM/ MECHANICAL ROOM, NOT LABELS AND WORD PUMP
 ROOM NOT TOO VISIBLE WOULD YOU PLEASE MOVE AND LABEL
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 F. THE STORM HAS 16,820 SF 874 GPM IN THE PREVIOUS
 VERSION; NOW, IT HAS 7,990 419 GPM, AND THERE ARE TWO
 8? SD DELETED. IF SO, PLEASE CLARIFY HOW THIS WATER
 WILL BE CAUGHT PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 G. IN THE RESIDENTIAL ACTIVE USE AREA, THERE ARE WALLS
 MISSING WALLS ALL THE WAY UP TO THE STAFF LOCKER. WOULD
 YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 2. ON SHEET 2.01S;
 A. IN THE RESIDENTIAL ACTIVE USE AREA, THERE ARE WALLS
 MISSING WALLS. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 B. ON KEYNOTE 15 BY POOL EQUIPMENT SAYS IT IS A
 CONTINUATION OF P201N. THAT IS NOT AN APPARENT
 REFERENCE TO THAT NUMBER. WOULD YOU PLEASE CORRECT OR
 CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. IN THE TRASH ROOM AREA, PLEASE LABEL THE 4-INCH
 FLOOR DRAIN WITH A REMOVABLE BASKET PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 C. IT SHOWS TWO BBQ AND A SINK IN A DIFFERENT LOCATION.
 WOULD YOU PLEASE PROVIDE THE DRAINAGE AND GAS TO IT? IF
 THE BBQ IS ENCLOSED IN A ROOM, THEY MAY REQUIRE A HOOD
 SYSTEM. THIS WILL NEED TO BE DETERMINED AND NOTED ON
 PLANS PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 D. THE SINK IN THE MULTI-PURPOSE ROOM IS NOT SHOWN, AND
 NEITHER ARE THE REFRIGERATOR AND ICE MACHINE. THERE IS
 A WALL MISSING AS WELL. WOULD YOU PLEASE CORRECT PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS? PLEASE MOVE THE LABEL FOR
 THE MULTI-PURPOSE ROOM OVER AS IT HAS THE WATER LINES
 OVER IT.
  
 E. NUMBER 25 ON STAIRWELL 4 HAS A STORM DRAIN IN A
 STAIRWELL. IF THIS IS A PRESSURIZED STAIRWELL, IT IS
 NOT ALLOWED UNLESS IT IS IN A CHASE. WOULD YOU PLEASE
 CLARIFY OR MOVE PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 F. PUMP ROOM WAS MOVED, AND THERE SEEMS TO BE ONE SIDE
 THAT DOES NOT HAVE THE INCHES REQUIRED IN CLEARANCE PER
 THE MANUFACTURERS SPECIFICATION. WOULD YOU PLEASE MOVE
 THE PUMP ROOM LABEL SO IT CAN BE READ FOR CLARITY?
 WOULD YOU PLEASE SHOW THE FORCE DRAIN DUMPING INTO THE
 FD PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 G. IN THE LOBBY AREA, THERE WERE TWO RESTROOMS AND ONE
 DRINKING FOUNTAIN DELETED. ARE THEY PART OF THE POOL
 AREA CONFIGURATION? WOULD YOU PLEASE CLARIFY PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS? IF SO, WHERE WERE THEY LOCATED
 TOO?
  
 H. IN THE DROP-OFF LOBBY, THERE IS A STORM DRAIN IN THE
 STAIRWELL IN THE PREVIOUS CONFIGURATION, AND NOW THE
 STAIRWELL MOVED BUT DID THE FLOOR DRAIN NEED TO MOVE AS
 WELL. WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS?
  
 I. ON SDS/1 THAT POINTS TO THE PACKAGE LOCKERS, THERE
 IS A CURB STOP OVER IT. WOULD YOU PLEASE MOVE IT FOR
 CLARITY PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 J. THERE ARE ITEMS MOVED AROUND AND LABELS ON TOP OF
 EACH OTHER ON THIS AND THE PREVIOUS PAGES. WOULD YOU
 PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 L. NEXT TO THE LOBBY, IT HAS THE DROP-OFF AREA AND
 DOORS THAT ARE MISSING WALLS. WOULD YOU PLEASE CORRECT
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 3. ON SHEET P201N-CLG;
 A. THERE ARE TWO VEHICLES, AND ONE IS OVER THE VERBIAGE
 FOR THE 6? RD. WOULD YOU PLEASE MOVE IT FOR CLARITY PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS?
  
 B. EMPLOYEE BREAKROOM NOT LABELED. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 4. ON SHEET P201S-CLG;
 A. THERE IS A MECHANICAL AND PLUMBING SECTION FOR
 CONCRETE IN THE POOL AREA THAT IS FLOATING AND DOES NOT
 NEED TO BE THERE. WOULD YOU PLEASE REMOVE IT PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 B. IN THE JANITORS ROOM AREA, WORDS ARE ON TOP OF EACH
 OTHER AND NOT LEGIBLE. WOULD YOU PLEASE CORRECT THEM BY
 MOVING THEM SO THEY CAN BE READ PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS?
  
 C. THERE ARE HOSE BIBBS SHOWN IN THE NEW RESTROOMS, AND
 THERE IS NO ISOMETRIC THAT SHOWS A WATER DISTRIBUTION
 REVISION FOR THE SOUTH TOWER. WOULD YOU PLEASE PROVIDE
 ONE AND SHOW THE SHUT OFF VALVES FOR THE HOSE BIBBS PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS?
  
 5. ON SHEET P2.02N;
 A. RN/9 UNIT S1 IS POINTING TO A DOOR THEY HAVE BEEN
 MOVED BEHIND THE WASHING MACHINE. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. SN/9 UNIT A2 HAS THE WASHING MACHINES LINES OUT OF
 THE WALL. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 C. IN STAIRWELL 1, THERE ARE TWO NEW LIGHTS THE ARE
 OVER S/N 11,13 AND SN/2. WOULD YOU PLEASE CORRECT PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS?
  
 D. SN/34 UNIT A-1 IS MISSING A WALL IN THE WASHING
 MACHINE AREA. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 6. ON SHEET P2.02S
 A. RS/9 UNIT S1 IS POINTING TO A DOOR THEY HAVE BEEN
 MOVED BEHIND AHU. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 B. SS/31 UNIT A-1 IS MISSING A WALL IN THE WASHING
 MACHINE AREA. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 C. IN STAIRWELL 3, THERE ARE TWO NEW LIGHTS THE ARE
 OVER S/S 1 AND NOTE 1. WOULD YOU PLEASE CORRECT PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 7. ON SHEET P2.02NA AND P2.02NB;
 A. SN/34 UNIT A-1 IS MISSING A WALL IN THE WASHING
 MACHINE AREA. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 B. IN-UNIT A-4, THE STACK FOR THE WASHING MACHINE AND
 BATHROOM ARE NOT LABELED. WOULD YOU PLEASE CORRECT PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS?
  
 C. SN/9 UNIT A2 HAS THE WASHING MACHINES LINES OUT OF
 THE WALL. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS? NOT IN P2.02 NB
  
 D. IN STAIRWELL 1, THERE ARE TWO NEW LIGHTS THE ARE
 OVER S/N 11,13 AND SN/2. WOULD YOU PLEASE CORRECT PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS? NOT IN P2.02 NB
  
 8. ON SHEET P2.02SA P2.02 SB;
 A. ON UNIT C1 THE WATER LINE IN THE SHOWER IS NOT IN
 THE WALL. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS? IN P2.02 SB, THE SHOWER LAYOUT
 IS DIFFERENT. IS THIS TYPICAL OF ALL OTHER UNITS UP AND
 DOWN. WOULD YOU PLEASE CLARIFY PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS?
  
 B. IN-UNIT A-4, THE STACK FOR THE WASHING MACHINE AND
 BATHROOM ARE NOT LABELED. WOULD YOU PLEASE CORRECT PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS?
  
 C. SN/31 UNIT A-1 IS MISSING A WALL IN THE WASHING
 MACHINE AREA. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 9. ON SHEET P2.03N, SN/34 UNIT A-1 IS MISSING A WALL IN
 THE WASHING MACHINE AREA. WOULD YOU PLEASE CORRECT PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS?
  
 10. ON SHEET P2.03S;
 A. IN STAIRWELL 3, THERE IS ONE NEW LIGHT THAT IS OVER
 NOTE 1 AND 2. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 B. SS/31 UNIT A-1 IS MISSING A WALL IN THE WASHING
 MACHINE AREA. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 C. ON UNIT C1 THE WATER LINE IN THE SHOWER IS NOT IN
 THE WALL. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 11. ON SHEET P2.04N;
 A. SN/34 UNIT A-1 IS MISSING A WALL IN THE WASHING
 MACHINE AREA. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 B. SN/9 UNIT A2 HAS THE WASHING MACHINES LINES OUT OF
 THE WALL. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 12. ON SHEET 2.04S;
 A. SS/31 UNIT A-1 IS MISSING A WALL IN THE WASHING
 MACHINE AREA. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 B. NO SHOWER HEAD LOCATION SHOWN IN THE ENTIRE DRAWING,
 WHICH WILL NEED TO COMPLY WITH THE FAIR HOUSING ACT
 LOCATION SHOWN ON OTHER FLOORS. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 13. ON SHEET 2.05N;
 A. SN/34 UNIT A-1 IS MISSING A WALL IN THE WASHING
 MACHINE AREA. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 B. SN/9 UNIT A2 HAS THE WASHING MACHINES LINES OUT OF
 THE WALL. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 C. IN STAIRWELL 1, THERE ARE TWO NEW LIGHTS THE ARE
 OVER S/N 11. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 D. ON STAIRWELL 2, THERE IS ONE NEW LIGHT THAT IS OVER
 NOTE 1 AND 2. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 14. ON SHEET 2.05S;
 A. SS/31 UNIT A-1 IS MISSING A WALL IN THE WASHING
 MACHINE AREA. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 B. IN STAIRWELL 3, THERE IS ONE NEW LIGHT THAT IS OVER
 NOTE 1 AND 2. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 15. ON SHEET P2.06;
 A. IN STAIRWELL 3, THERE IS ONE NEW LIGHT THAT IS OVER
 NOTE 1 AND 2. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 16. ON SHEET 4.05N;
 A. NUMBER 37 ON ISOMETRIC IS MISSING AIR ARRESTORS ON
 ICEMAKER AND SINK. WHERE THEY REMOVED AS THEY ARE
 REQUIRED ON ICEMAKER. WOULD YOU PLEASE CORRECT PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 B. IN NUMBER 28, THE AIR ARRESTOR HAS BEEN REMOVED AND
 THE WATER COOLER AND REQUIRED ON THE WATER COOLER. IN
 THAT SAME BATHROOM GROUP, IT SHOWS TWO HOSE BIBBS AND
 ONE SHUT OFF. EACH SILLCOCK SHALL HAVE ITS OWN SHUT-OFF
 PER THE 2017 FBC SECTION 606.2 (2) LOCATION OF SHUTOFF
 VALVES. THEY SHALL BE ACCESSIBLE.
  
 17. ON SHEET 4 P4.11N;
 A. THE GAS CHART HAS BEEN DELETED. WOULD YOU PLEASE
 PROVIDE OR PUT A NOTE PER THE 2017 FBC FG SEC. 402.3?
  
 B. THERE WERE TWO BBQ UNITS SHOWN IN THE NEW REVISION,
 FOUR SHOWN IN THE POOL AREA. ARE THESE BBQ?S NOT
 INCLUDED IN THE REVISED GAS SYSTEM BUT ARE IN THE
 KEYNOTES? ARE THEY THE PROPANE TANK TYPE? WOULD YOU
 PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 C. IN GENERAL NOTES, COLOR DETECTION TAPE IS NOT
 APPROVED AN APPROVED BY THE LOCAL AJH. AN 18? GAUGE
 WIRE, A YELLOW INSULATED COPPER TRACER WIRE, WILL BE
 REQUIRED PER THE 2017 FBC SEC. 404.17.3.
  
 D. THE NEW FOUR BBQ SEEM TO BE ENCLOSED AND MAY REQUIRE
 HOOD VENT PER THE MANUFACTURERS SPECIFICATION. IF THAT
 IS THE CASE, PLEASE PROVIDE SPECIFICATIONS OR MAKE
 NOTES ON PLANS PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 E. CSST PIPE IN THE SLEEVE WILL REQUIRE VENTING PER THE
 AJH AND AS SHOWN ON THE MANUFACTURES SPECIFICATION.
 PLEASE PROVIDE A NOTE UNDER GENERAL NOTES PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 F. ON THE FUTURE SERVICES, IT SAYS TWO SERVICES, BUT
 PLANS SHOW THREE. WOULD YOU PLEASE CLARIFY PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 18. ON SHEET P5.01S;
 A. THE SANITARY FOR THE SINK IN THE POOL AREA HAS BEEN
 MOVED, AND THE NEW LOCATION IS NOT SHOWN. WOULD YOU
 PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. IN THE NORTH TOWER, THE SINK FOR THE POOL AREA, WAS
 ALSO MOVED, AND NO ISOMETRIC FOR SANITARY OR WATER WAS
 SHOWN. WOULD YOU PLEASE PROVIDE PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS?
  
 C. PLEASE PROVIDE THE LOCATION FOR THE SHOWER OUTSIDE
 AND CONNECTION TO DRAINAGE PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS?
  
 19. ON SHEET P5.05P;
 A. LOBBY RESTROOM HAS A HOSE BIBB, AND IT REQUIRES A
 SHUTOFF VALVE ON THE SILLCOCK PER THE 2017 FBC SEC. P
 606.2 (2).
  
 B. THE PUMP SHOWS CONDENSATE (CD) DARING INTO THE
 SANITARY PER THE CITY OF WEST PALM BEACH IT IS NOT
 ALLOWED. WOULD YOU PLEASE PROVIDE DRAINAGE TO THE
 OUTSIDE OF THE STORM PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 C. PLEASE PROVIDE ISOLATION BACKFLOW ON MECHANICAL
 EQUIPMENT (PUMP, IRRIGATION POOL PUMP, CHILLER, ETC.)
 PER THE 2017 FBC TABLE 608.1.
  
 D. THE MAINTENANCE RESTROOM SHOWS A HOSE BIBB ON SHEET
 201S CELLING BUT NOT SHOWN ON ISOMETRIC, REQUIRING A
 SILLCOCK. WOULD YOU PLEASE PROVIDE AN ISOMETRIC PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 20. ON SHEET P5.07S ON DETAIL 1 SHOWS TWO DOUBLE HOSE
 BIBBS ON LEVEL 25, AND EACH SHALL BE ON ITS OWN
 SILLCOCK PER THE 2017 FBC SEC. P 606.2 (2).
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status N Date 2021-07-01 Cont ID  
Sent By shill Date 2021-07-01 Time 19:55 Rev Time 0.00
Received By shill Date 2021-07-01 Time 19:55 Sent To  
Notes
2021-07-01 19:55:33INSPECTIONS ONLY
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2021-07-21 Cont ID  
Sent By rmcdouga Date 2021-07-21 Time 16:22 Rev Time 0.00
Received By rmcdouga Date 2021-07-21 Time 16:22 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2022-11-02 Cont ID  
Sent By ccole Date 2022-11-02 Time 10:48 Rev Time 0.00
Received By ccole Date 2022-11-01 Time 16:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status F Date 2022-10-03 Cont ID  
Sent By ccole Date 2022-10-03 Time 12:54 Rev Time 0.00
Received By ccole Date 2022-10-03 Time 10:14 Sent To  
Notes
2022-10-03 12:55:24ELECTRONIC/DIGITAL SIGNATURE REVIEW FBC- 2020
 PERMIT- 21060844
 10/3/2022
  
 CODES IN EFFECT:
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE FOLLOWING LIST OF PLAN SHEETS WERE NOT DIGITALLY
 SIGNED AND SEALED BY THE ENGINEER OF RECORD AS REQUIRED
 BY FL. STATUTE 471.025 AND FAC SEC. 61G15-23.005.
 P2.01N, P2.01S, P2.01S-CLG, P2.07N, P2.076S, P4.11N,
 P5.11S.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-08-12 Cont ID  
Sent By rmcdouga Date 2022-08-12 Time 10:43 Rev Time 0.00
Received By rmcdouga Date 2022-08-12 Time 10:43 Sent To  
Notes
2022-08-03 12:22:01ELECTRICAL PAGES SIGNATURES ARE APPROVED JL

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-06-22 Cont ID  
Sent By rmcdouga Date 2022-06-22 Time 11:58 Rev Time 0.00
Received By rmcdouga Date 2022-06-22 Time 11:58 Sent To  
Notes
2022-05-19 16:04:47ELECTRICAL SIGNATURE OK JLEAHY

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-12-13 Cont ID  
Sent By rmcdouga Date 2021-12-13 Time 13:44 Rev Time 0.00
Received By rmcdouga Date 2021-12-13 Time 16:52 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-07-22 Cont ID  
Sent By rmcdouga Date 2021-07-22 Time 07:44 Rev Time 0.00
Received By rmcdouga Date 2021-07-22 Time 07:44 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2022-07-11 Cont ID  
Sent By jroach Date 2022-07-11 Time 15:55 Rev Time 0.00
Received By jroach Date 2022-07-11 Time 15:39 Sent To  
Notes
2022-07-11 15:55:53THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. ALL DEVELOPMENT WITHIN THE MARINA COMMERCIAL MARINE
 PLANNED DEVELOPMENT (CMPD) SHALL BE SUBJECT TO ALL
 DEVELOPMENT ORDER CONDITIONS, DESIGN GUIDELINES, ETC.,
 AS OUTLINED IN RESOLUTION NO. 66-22, AND AS MAY BE
 AMENDED. ALL CONDITIONS OF APPROVAL IMPOSED BY THE
 DEVELOPMENT ORDER SHALL BE ADDRESSED WITHIN THE
 APPROPRIATE SPECIFIED TIMEFRAMES.
 _______________________________________________________
 _____________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 2 Status F Date 2022-04-08 Cont ID  
Sent By jroach Date 2022-04-08 Time 12:40 Rev Time 0.00
Received By jroach Date 2022-04-08 Time 12:40 Sent To  
Notes
2022-04-08 12:41:02CHANGES ARE BEING SUBMITTED, ZONING REVIEW WILL BE
 COMPLETED WITH THE RESUBMITTAL.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-08-26 Cont ID  
Sent By jroach Date 2021-08-26 Time 16:25 Rev Time 0.00
Received By jroach Date 2021-08-26 Time 16:20 Sent To  
Notes
2021-08-26 16:26:10ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 08.23.2021
 PERMIT NO.: 18100526 (REVISION NO. 21060844)
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. THE FOLLOWING COMMENTS WERE ISSUED REGARDING THE
 PLANS SUBMITTED AS PART OF THE MINOR AMENDMENT TO THE
 CMPD, DATED JUNE 2, 2021. MANY (IF NOT ALL) OF THE
 COMMENTS BELOW ARE APPLICABLE TO THE PLANS SUBMITTED AS
 PART OF THIS BUILDING PERMIT.
  
 2. THE SIZE OF THE BEACH CLUB (OVERHANG) HAS INCREASED.
 PURSUANT TO THE DESIGN GUIDELINES, THE BEACH CLUB IS TO
 BE A MINIMUM OF 20 FEET FROM THE SEAWALL. AS THE
 OVERHANG HAS SUPPORT POSTS, THE MINIMUM 20 FOOT SETBACK
 (AS DEFINED BY THE ZLDRS) IS TO BE FROM THE SUPPORT
 COLUMN TO THE SEAWALL. EITHER THE PLAN SHALL BE REVISED
 TO MEET THE MINIMUM SETBACK REQUIREMENT, OR A MAJOR
 AMENDMENT TO THE CMPD SHALL BE APPROVED TO MODIFY THE
 SETBACK REQUIREMENTS.
  
 3. IT IS STAFF?S UNDERSTANDING THAT NUMEROUS PARKING
 SPACES ARE PROPOSED TO BE ASSIGNED (TO RYBOVICH, ETC.).
 AS THE PROJECT WAS DESIGNED UTILIZING THE SHARED
 PARKING PROVISIONS OF SEC. 94-484 OF THE CITY?S ZLDRS,
 PARKING SPACES WHICH ARE RESERVED FOR USE BY SPECIFIED
 INDIVIDUALS OR CLASSES OF INDIVIDUALS SHALL NOT BE
 COUNTED TOWARD MEETING PARKING REQUIREMENTS. THE
 PARKING TABLE/CALCULATION SHALL BE REVISED TO INDICATE
 THE NUMBER OF ASSIGNED SPACES, AND THAT THE PROJECT
 CONTINUES TO COMPLY WITH THE MINIMUM PARKING
 REQUIREMENTS (LESS THE RESERVED SPACES). THE RESERVED
 SPACES SHALL ALSO BE IDENTIFIED ON THE SITE PLAN.
  
 4. THE SITE PLAN INDICATES ADDITIONAL PARKING SPACES
 BEING CONSTRUCTED ON THE FORMER RYBOVICH HELIPAD. THESE
 SPACES SHALL BE DESIGNED TO COMPLY WITH THE CITY?S
 ZLDRS, INCLUDING THE PROVISION OF LANDSCAPE ISLANDS,
 BUFFERS, ETC.
  
 5. THE OVERHANG (WITH SUPPORT POSTS/COLUMNS) FOR THE
 NORTH TOWER ENCROACHES INTO THE REQUIRED SETBACK FROM
 THE NORTH PROPERTY LINE. PURSUANT TO THE CMPD DESIGN
 GUIDELINES, A MINIMUM SETBACK OF 55 FEET SHALL BE
 PROVIDED. ROOF OVERHANGS, BALCONIES, ETC. (WITH NO
 SUPPORT COLUMNS) ARE PERMITTED TO ENCROACH SIX (6) FEET
 INTO THE REQUIRED SETBACK. EITHER THE PLAN SHALL BE
 REVISED TO MEET THE MINIMUM SETBACK REQUIREMENT, OR A
 MAJOR AMENDMENT TO THE CMPD SHALL BE APPROVED TO MODIFY
 THE SETBACK REQUIREMENTS.
  
 6. ALL PLANS NEED TO CLEARLY IDENTIFY ALL ELEMENTS
 SHOWN ON THE PLAN. THERE ARE MANY SHEETS WHERE ELEMENTS
 ARE NOT IDENTIFIED; MANY SHEETS DO NOT HAVE ELEMENTS
 LABELED, OR NOT SHOWN AT ALL (SUCH AS THE OVERHANG ON
 THE NORTH SIDE OF THE NORTH TOWER).
  
 7. PLEASE NUMBER THE PARKING SPACES, AS WAS PROVIDED ON
 PREVIOUS VERSIONS OF THE PLANS.
  
 8. PLEASE EXPLAIN HOW THE DROP-OFF COURT IS PROPOSED TO
 FUNCTION. CARS SHOULD NOT BE COMPELLED TO STOP IN THE
 MIDDLE OF THE DRIVE-AISLE.
  
 9. THE PARKING NUMBERS SHOWN ON SHEET 00.201 DO NOT
 SEEM TO MATCH. IN SOME AREAS ITS INDICATED THAT 654
 SPACES ARE PROVIDED, OTHER AREAS INDICATED 658 SPACES
 ARE PROVIDED. ENSURE THAT ALL INFORMATION SHOWN IN THE
 DATA TABLES, ETC. IS ACCURATE AND MATCHES THAT WHICH IS
 SHOWN ON THE PLAN.
  
 10. AS AREAS OF THE SITE HAVE BEEN CHANGED, REVISED
 LANDSCAPE PLANS SHALL BE PROVIDED AS PART OF THE MINOR
 AMENDMENT, AS WELL AS REVISIONS TO ANY EXISTING
 LANDSCAPE PERMITS.
  
 11. IT APPEARS THAT ADDITIONAL INFORMATION IS BEING
 SHOWN REGARDING THE PROPOSED DOCK. WHAT IS THE STATUS
 OF MOVING FORWARD WITH THIS? RESIDENTIAL DOCKS SHALL
 CONFORM TO THE REQUIREMENTS OF SEC. 94-313 OF THE
 CITY?S ZLDRS.
  
 12. PLEASE INDICATE IN THE DATA TABLE THE NUMBER OF
 ELECTRIC CAR CHARGING SPACES AND CARPOOL SPACES ARE
 BEING PROVIDED. AS PROVIDED IN THE DESIGN GUIDELINES, A
 MINIMUM OF 5% OF THE NON-RESIDENTIAL PARKING SHALL BE
 ELECTRIC CAR CHARGING SPACE (AND SHALL BE OPEN TO THE
 PUBLIC) AND CARPOOL SPACES (EQUIVALENT TO 2% OF THE
 NON-RESIDENTIAL PARKING) SHALL BE PROVIDED.
  
 13. THE EASTERN END OF THE PARKING ROW SOUTH OF THE
 SOUTH TOWER DOES NOT APPEAR TO PROVIDE THE REQUIRED
 TERMINAL LANDSCAPE ISLAND (SPECIFICALLY ON SHEET
 A1.101). THIS AREA SEEMS TO BE INCOMPLETE AND NOT ALL
 OF THE IMPROVEMENTS ARE SHOWN (AS DEPICTED ON SHEET
 A1.100).
  
 14. A TURNAROUND SPACE WILL NEED TO BE PROVIDED AT THE
 EASTERN END OF THE PARKING ROW SOUTH OF THE SOUTH
 TOWER.
  
 15. THE REVISED PEDESTRIAN PATHWAYS SOUTH OF THE SOUTH
 TOWER ARE UNCLEAR. IT IS HARD TO IDENTIFY WHAT IS
 SIDEWALK, LANDSCAPE AREA, ETC. PURSUANT TO THE DESIGN
 GUIDELINES, A CONTINUOUS SIDEWALK (OPEN TO THE PUBLIC)
 SHALL BE PROVIDED SOUTH OF THE SOUTH TOWER ? CONNECTING
 NORTH FLAGLER DRIVE TO THE PUBLIC PROMENADE.
  
 16. THE ARE LOCATIONS WHERE THE LABELS FOR BIKE RACKS
 ARE POINTING TO PARKING SPACES. PLEASE ENSURE THAT ALL
 LABELS ARE CORRECTLY POINTING TO THE INTENDED ELEMENT.
 PURSUANT TO THE DESIGN GUIDELINES, BIKE RACKS ARE TO BE
 DISTRIBUTED AMONGST BUILDING ENTRANCES, ETC. THE
 REVISED PLAN APPEARS TO HAVE REMOVED THE BIKE RACKS
 THAT WERE IN FRONT OF THE SOUTH TOWER, AND NO RACKS ARE
 LABELED IN FRONT OF THE ENTRANCE TO THE NORTH TOWER.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  