Plan Review Details - Permit 21060813
Plan Review Stops For Permit 21060813
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-08-13 Cont ID  
Sent By jleahy Date 2021-08-13 Time 15:34 Rev Time 0.00
Received By jleahy Date 2021-08-13 Time 15:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-06-24 Cont ID  
Sent By jleahy Date 2021-06-24 Time 07:24 Rev Time 0.00
Received By jleahy Date 2021-06-24 Time 07:21 Sent To  
Notes
2021-06-24 07:28:03ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED TO SHOW BRANCH CIRCUIT SIZE , CONDUIT SIZE, AND
 OVER CURRENT PROTECTION SIZE.
  
 NEED TO SHOW VALUE FOR THE NEW WELL AND ELECTRIC.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-08-17 Cont ID  
Sent By lcrespo Date 2021-08-17 Time 11:58 Rev Time 0.00
Received By lcrespo Date 2021-08-12 Time 14:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-06-24 Cont ID  
Sent By jleahy Date 2021-06-24 Time 07:28 Rev Time 0.00
Received By jleahy Date 2021-06-14 Time 11:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-08-17 Cont ID  
Sent By lcrespo Date 2021-08-17 Time 11:48 Rev Time 0.00
Received By lcrespo Date 2021-08-17 Time 11:48 Sent To  
Notes
2021-08-17 11:58:1408/17/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-06-23 Cont ID  
Sent By lcrespo Date 2021-06-23 Time 13:23 Rev Time 0.00
Received By lcrespo Date 2021-06-23 Time 13:23 Sent To  
Notes
2021-06-23 13:27:3706/23/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE PLAN CALLS FOR A WELL. THE PALM BEACH HEALTH
 DEPARTMENT REQUIRES A PERMIT, AND PLEASE SUBMIT
 SUPPORTING DOCUMENTATION PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. AN ELECTRICAL PERMIT IS REQUIRED FOR THE PUMP PER
 THE WPB AMENDMENTS TO THE FBC SEC. 105.1.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-08-17 Cont ID  
Sent By lcrespo Date 2021-08-17 Time 11:58 Rev Time 0.00
Received By lcrespo Date 2021-08-17 Time 11:58 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-06-23 Cont ID  
Sent By lcrespo Date 2021-06-23 Time 13:25 Rev Time 0.00
Received By lcrespo Date 2021-06-23 Time 13:25 Sent To  
Notes
***NONE***