Plan Review Details - Permit 21060780
Plan Review Stops For Permit 21060780
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-08-18 Cont ID  
Sent By jleahy Date 2021-08-18 Time 11:26 Rev Time 0.00
Received By jleahy Date 2021-08-18 Time 11:26 Sent To  
Notes
2021-08-18 11:27:11LETTER SENT TO STORAGE JLEAHY

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-07-18 Cont ID  
Sent By jwitmer Date 2021-07-18 Time 16:01 Rev Time 0.00
Received By jwitmer Date 2021-07-18 Time 15:00 Sent To  
Notes
2021-07-18 16:00:56TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected] THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-08-21 Cont ID  
Sent By cthroop Date 2021-08-21 Time 07:48 Rev Time 0.00
Received By cthroop Date 2021-08-20 Time 09:56 Sent To  
Notes
2021-08-21 07:49:13FLOORING PROVISO PG. A-1.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-07-18 Cont ID  
Sent By jwitmer Date 2021-07-18 Time 15:59 Rev Time 0.00
Received By jwitmer Date 2021-07-18 Time 15:00 Sent To  
Notes
2021-07-18 15:59:40WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21060780
 ADD: 1801 S. FLAGLER DR. # 903
 CONT: MASTER CONTRACTORS
 TEL: 561-712-8898
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SUN. JULY 18TH/ 2021
 ACTION: DENIED
 1) COVERSHEET:
  
 1A) LISTING FOR WIND DESIGN IS GIVEN AS 2020 ASCE-7-10.
 PLEASE NOTE IN THE 2020 FBC-BUILDING CODE THE REFERENCE
 STANDARD IS ASCE- 7-16. UP DATE PLANS.
  
 1B) UNDER THE ASCE-7 STANDARD THE BUILDING HEIGHT IS
 GIVEN AT 200 FT IN HEIGHT, AND THE BUILDING
 CLASSIFICATION TYPE AS I-B.
 PLEASE NOTE THIS IS A 18 STORY BUILDING. THE HEIGHT OF
 200 FT AND 18 STORY BUILDING WOULD MAKE THIS
 CONSTRUCTION TYPE I-A, SEE THE 2020 FBC-BUILDING TABLES
 504.3 & 504.4. PLEASE UPDATE THE PLAN.
  
 1C) UNDER THE LISTED ASCE-7 THE EXPOSURE GIVEN IS A C
 EXPOSURE. SUBMITTED ON THIS SHEET IS A SATELLITE
 AERIAL. THE LOCATION OF THE UNIT IS NOT IDENTIFIED/
 LOCATED. WITHOUT THIS INFORMATION THE EXPOSURE CAN NOT
 BE DETERMINED NOR IF THE UNIT IS LOCATED IN WALL ZONE 4
 OR WALL ZONE 5 WITH HIGHER PRESSURES. 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED TO BE ABLE TO
 DETERMINE EXPOSURE TYPE AND ASSOCIATED PRESSURES.
  
 1D) DESIGN PRESSURES FOR EXPOSURE C BUILDINGS UP TO 60
 FT. IN HEIGHT WORST CASE ALL OPENINGS, (ZONE 5) 10 SQ.
 FT. +50.6/
 -67.8 PSF VASD.
  
 2) SHEET A-1 THE CONSTRUCTION PLAN. THE FLOOR PLAN
 UNDER THE SCOPE OF WORK NOTE 4 NEW FLOORING AS PER PLAN
 SEE SHEET
 A-1. THE FLOOR PLAN ONLY STATES INSTALL NEW FLOORING,
 NO MENTION OF TYPE OF MATERIAL NOR SOUND UNDERLAYMENT.
 FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE,
 STONE, MARBLE, VINYL AND WOOD FLOORING ALL NEED TO HAVE
 HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO
 THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 2A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 2B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 2C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 2D) THE FLOOR PLAN IS SILENT IF TILE IS GOING TO BE
 INSTALLED ON THE BALCONY. IF TILE IS TO BE INSTALLED ON
 THE BALCONY, THEN A ENGINEER WILL NEED TO INSPECT THE
 BALCONY SLAB FOR CRACKS, SPALLING OF STEEL AND HOW TO
 CORRECT THE SPALLED CONCRETE. THE ENGINEER IS TO
 PROVIDE A SIGNED SEALED REPORT AS TO THE CONDITION OF
 THE BALCONY SLAB AND IF REPAIRS ARE NECESSARY HOW THEY
 WILL BE ACCOMPLISHED. NOTE THIS IS A HIGHRISE BUILDING/
 THRESHOLD INSPECTOR (S. I.) REQUIRED.
  
 3) SHEET A-1 THE MASTER BATHROOM THE TUB IS REMOVED,
 AND THE SHOWER IS EXPANDED. NO MENTION OF THE CODE
 ISSUES LISTED BELOW:
  
 3A) NO MENTION OF HOW THE TUB FLOOR BOX OUT FOR DRAIN
 IS TO COMPLY WITH: THROUGH-PENETRATIONS FIRESTOP
 SYSTEMS (HORIZONTAL ASSEMBLIES). IF A NEW FLOOR
 PENETRATION IS MADE FOR THE FUTURE SHOWER DRAIN, THEN
 YOU NEED TO SHOW COMPLIANCE WITH THE 2020 FBC-B SECTION
 714.5.1.2. THROUGH-PENETRATIONS FIRESTOP SYSTEMS
 (HORIZONTAL ASSEMBLIES). THROUGH PENETRATIONS SHALL BE
 PROTECTED BY A THROUGH PENETRATION FIRESTOP SYSTEM
 INSTALLED IN ACCORDANCE WITH ASTM E814 OR UL 1479. THE
 SYSTEM SHALL HAVE AN F RATING / T RATING OF NOT LESS
 THAN 1 HOUR BUT NOT LESS THAN THE REQUIRED RATING OF
 THE FLOOR PENETRATED.
  
 3B) THE ENLARGED SHOWER THE NEW FLOOR DRAIN AND SIZE OF
 THROUGH PENETRATION, POST TENSION SLAB/ NEW HOLES. THE
 PLAN IS SILENT AS IF THE LOCATION OF THE EXISTING TUB
 DRAIN IS GOING TO BE REUSED IN THE SAME LOCATION. IF
 NOT, THEN THE FLOOR SLAB WILL NEED TO BE X-RAYED TO
 FIND THE POST TENSION CHORD LOCATIONS. 107.2.1.2.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 3C) THE TYPE OF TILE BACKING FOR THE SHOWER. 2020 FBC-B
 2509.2 BASE FOR TILE. MATERIALS USED AS A BASE FOR WALL
 TILE IN TUB AND SHOWER AREAS AND WALLS AND CEILING
 PANELS IN SHOWER AREAS SHALL BE OF MATERIALS LISTED IN
 TABLE 2509.2 AND INSTALLED IN ACCORDANCE WITH
 MANUFACTURER?S RECOMMENDATIONS. WATER RESISTANT GYPSUM
 BACKING BOARD SHALL BE USED AS A BASE FOR TILE IN WATER
 CLOSET COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE
 WITH GA-216 OR ASTM C840 AND THE MANUFACTURE?S
 RECOMMENDATIONS.
  
 3D) IN THE SHOWER THE HEIGHT OF TILE? 2020 FBC-B
 SHOWERS & TUBS 1210.3. SHOWER COMPARTMENTS AND BATHTUBS
 WITH INSTALLED SHOWER HEADS SHALL BE FINISHED WITH A
 NONABSORBENT SURFACE TO A HEIGHT NOT LESS THAN 72
 INCHES ABOVE THE DRAIN INLET.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE
 WORKING FROM CITY HALL
 MY WORK HOURS ARE MON. & TUES. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-08-23 Cont ID  
Sent By jleahy Date 2021-08-23 Time 07:24 Rev Time 0.00
Received By jleahy Date 2021-08-20 Time 12:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-07-08 Cont ID  
Sent By jleahy Date 2021-07-08 Time 16:46 Rev Time 0.00
Received By jleahy Date 2021-07-08 Time 16:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-08-18 Cont ID  
Sent By cwalker Date 2021-08-18 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-06-29 Cont ID  
Sent By cwalker Date 2021-06-29 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-08-23 Cont ID  
Sent By jleahy Date 2021-08-23 Time 07:25 Rev Time 0.00
Received By jleahy Date 2021-08-17 Time 12:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-07-18 Cont ID  
Sent By jwitmer Date 2021-07-18 Time 16:00 Rev Time 0.00
Received By jwitmer Date 2021-06-28 Time 12:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-08-20 Cont ID  
Sent By medwards Date 2021-08-20 Time 16:31 Rev Time 0.00
Received By medwards Date 2021-08-20 Time 16:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-07-08 Cont ID  
Sent By hmoser Date 2021-07-08 Time 13:56 Rev Time 0.00
Received By hmoser Date 2021-07-08 Time 12:43 Sent To  
Notes
2021-07-08 13:56:04PLAN DENIED
 1) PROVIDE GRILLE SIZE OF RETURN AIR IN BEDROOMS.
 SECTION 107 SUBMITTAL DOCUMENTS FBC 2020
 2) PROVIDE A AIR CONDITIONING DUCT PLAN SHOWING
 LOCATION
 OF LINERS AND DUCT SIZE, SHOW HOW THE DUCT IS GETTING
 TO
 THE LINERS. SECTION 107 FBC 2020
 3) PROVIDE THE WRIGHT EQUIPMENT SCHEDULE ON THE PLAN.
 I THINK IT WOULD BE A WATTER COOLED PACKAGE UNIT.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-08-21 Cont ID  
Sent By abelisle Date 2021-08-21 Time 15:58 Rev Time 0.00
Received By abelisle Date 2021-08-21 Time 14:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-07-13 Cont ID  
Sent By abelisle Date 2021-07-13 Time 11:30 Rev Time 0.00
Received By abelisle Date 2021-07-13 Time 10:30 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-08-18 Cont ID  
Sent By jleahy Date 2021-08-18 Time 11:27 Rev Time 0.00
Received By jleahy Date 2021-08-18 Time 11:27 Sent To  
Notes
2021-08-18 11:27:44SIGNED PLANS SENT TO STORAGE JLEAHY

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-07-18 Cont ID  
Sent By jwitmer Date 2021-07-18 Time 16:00 Rev Time 0.00
Received By jwitmer Date 2021-07-18 Time 15:00 Sent To  
Notes
***NONE***