| Plan Review Stops For Permit 21060775 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2021-09-17 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-09-17 |
Time |
14:54 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-09-17 |
Time |
14:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-07-12 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-07-12 |
Time |
07:33 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-07-12 |
Time |
07:33 |
Sent To |
|
|
| Notes |
| 2021-07-12 07:38:32 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT A SURVEY THAT SHOWS THE LOCATION OF THE POOL | | | AND THE POOL EQUIPMENT. FBC AMEND. 107.2.1 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2021-09-01 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2021-09-01 |
Time |
08:25 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2021-09-01 |
Time |
08:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2021-06-16 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2021-06-16 |
Time |
13:26 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2021-06-16 |
Time |
13:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-09-17 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-09-17 |
Time |
14:55 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-08-25 |
Time |
12:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-07-12 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-07-12 |
Time |
07:40 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-06-14 |
Time |
07:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2021-09-10 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-09-10 |
Time |
13:36 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-09-10 |
Time |
13:36 |
Sent To |
|
|
| Notes |
| 2021-09-10 13:37:32 | 09/10/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING/POOL) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2021-06-29 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-06-29 |
Time |
17:39 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-06-29 |
Time |
17:39 |
Sent To |
|
|
| Notes |
| 2021-06-29 17:40:03 | 06/29/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. THE TOTAL DYNAMIC HEAD CALCULATIONS FOR THE MAXIMUM | | | SYSTEM FLOW HAVE A HEATER AND A CHLORINATOR. THE TDH | | | CALCULATIONS MUST INCLUDE ALL THE SYSTEM COMPONENTS | | | THAT ARE TO BE INSTALLED. PLEASE CORRECT PER THE WPB | | | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON | | | CONSTRUCTION DOCUMENTS. | | | | | | 2. PLEASE SHOW ON THE POOL PUMP CURVE. IDENTIFY ON THE | | | PUMP CURVE WHICH CURVE KEY IS SPECIFIC TO THE PUMP | | | BEING INSTALLED ON THIS POOL. THIS IS NEEDED TO CONFIRM | | | THE MAXIMUM SYSTEM FLOW FROM THE TDH CALCULATIONS PER | | | THE ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. | | | INDICATE ON THE PUMP CURVE WHICH CURVE KEY IS FOR THE | | | PUMP BEING INSTALLED ON THIS SYSTEM PER THE WPB AMEND. | | | TO FBC SEC. 107.2.1. | | | | | | 3. PLEASE SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR | | | THE HEATER AND CHLORINATOR IF USED PER THE WPB | | | AMENDMENTS TO FBC SEC. 107.2.1. | | | | | | 4. ON-PAGE ONE, UNDER THE NOTES, AN OVERFLOW LINE IS | | | MENTIONED. IS THAT A POOL FILL, AND IF SO, IT WILL | | | REQUIRE A PVB BACKFLOW. PLEASE CLARIFY PER THE WPB | | | AMENDMENTS TO FBC SEC. 107.2.1. | | | | | | | | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. | | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2021-09-17 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-09-17 |
Time |
14:55 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-09-17 |
Time |
14:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2021-07-12 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-07-12 |
Time |
07:38 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-07-12 |
Time |
07:38 |
Sent To |
|
|
| Notes |
| 2021-07-12 07:39:52 | SHEET 1 OF 4 IS NOT SIGNED BY THE ENGINEER. | | | ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE | | | THE ARCHITECT OR ENGINEER'S DIGITAL SIGNATURE ON THEM. | | | YOU ALSO HAVE THE OPTION TO SUBMIT THE SIGNED AND | | | SEALED PAPER VERSION OF DRAWINGS. AFTER THE ELECTRONIC | | | PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT THE | | | CORRESPONDING PAPER DRAWINGS AT THE BUILDING DEPARTMENT | | | TO BE VERIFIED. THE ARCHITECT OR ENGINEER'S ORIGINAL | | | HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE | | | DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE | | | SIGNATURE ARE ACCEPTABLE. FS 487 & 61G1 OR FS 471 & | | | 61G15 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2021-09-01 |
|
|
Cont ID |
|
| Sent By |
kalexand |
Date |
2021-09-01 |
Time |
13:53 |
Rev Time |
0.00 |
| Received By |
kalexand |
Date |
2021-09-01 |
Time |
13:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2021-07-08 |
|
|
Cont ID |
|
| Sent By |
kalexand |
Date |
2021-07-08 |
Time |
10:00 |
Rev Time |
0.00 |
| Received By |
kalexand |
Date |
2021-07-08 |
Time |
10:00 |
Sent To |
|
|
| Notes |
| 2021-07-08 10:04:21 | ZONING PLAN REVIEW | | | ________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. PROVIDE A CURRENT SURVEY, WHICH INCLUDES THE | | | PROPERTY'S ADDRESS AND LEGAL DESCRIPTION. PLEASE | | | ILLUSTRATE THE FOLLOWING ON THE SURVEY: | | | - LOCATION OF PROPOSED POOL AND EQUIPMENT | | | - DISTANCE FROM POOL AND EQUIPMENT TO ADJACENT PROPERTY | | | LINES | | | ________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD | | | LIKE TO RESUBMIT ELECTRONICALLY, EMAIL | | | [email protected] AND REQUEST TO HAVE YOUR | | | PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOG | | | IN INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL. | | | PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU | | | ARE FINISHED UPLOADING. | | | ________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | KIZZI ALEXANDRE, ASSOCIATE PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1442 | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|