Plan Review Details - Permit 21060769
Plan Review Stops For Permit 21060769
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-10-12 Cont ID  
Sent By jgomez Date 2021-10-12 Time 18:19 Rev Time 0.00
Received By jgomez Date 2021-10-12 Time 09:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-07-12 Cont ID  
Sent By jgomez Date 2021-07-12 Time 15:43 Rev Time 0.00
Received By jgomez Date 2021-07-12 Time 11:23 Sent To  
Notes
2021-07-12 15:57:03TRIPLEX (R2) ALTERATION, BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21060769.
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 1- NEW STAIRWAY CONSTRUCTION:
 A) PROVIDE COMPLETE FRAMING PLAN AND FOUNDATION PLAN
 SHOWING ALL BEAMS, JOISTS, COLUMNS AND FOOTINGS.
 SEC. 107.3.5.1.1(8) CITY AMENDMENTS.
  
 B)PROVIDE SPECIFICATIONS FOR TYPE OF WOOD USED FOR THE
 STAIRWAY CONSTRUCTION (POSTS, BEAMS, STRINGERS, ETC.)
 SHOWING COMPLIANCE WITH THE PROTECTION AGAINST DECAY
 AND TERMITES AS REQUIRED BY SEC. 2304.12 FBC-BUILDING.
  
 C)SPECIFY STAIRWAY WIDTH.
 SEC. 1011.2 FBC-BUILDING.
  
 D)SPECIFY RISERS AND TREADS DIMENSIONS.
 SEC. 1011.5.2 FBC-BUILDING.
  
 E)SPECIFY STAIRS NOSING PROFILE.
 SEC. 1011.5.5 FBC-BUILDING.
  
 F) SPECIFY HANDRAIL ON EACH SIDE OF STAIRWAY.
 SEC. 1011.11 FBC-BUILDING.
  
 G)SPECIFY HANDRAIL HEIGHT.
 SEC. 1014.2 FBC-BUILDING.
  
 H) CONTINUOUS 2X6 TOP RAIL DOESN'T COMPLY WITH THE
 HANDRAIL GRASPABILITY REQUIREMENTS. REVISE AS REQUIRED.
 SEC. 1014.3 FBC-BUILDING.
  
 I)SPECIFY ATTACHMENT OF 4X4 POST TO STAIR STRINGER.
 SEC. 107.3.5.1.1(8) CITY AMENDMENTS.
  
 J)SPECIFY ATTACHMENT OF NEW STAIRWAY TO EXISTING WALL.
 SEC. 107.3.5.1.1(8) CITY AMENDMENTS.
  
 K)SPECIFY ATTACHMENT OF GUARDRAIL TO EXISTING WALL.
 SEC. 107.3.5.1.1(8) CITY AMENDMENTS.
  
 2- ROOF RAFTER REPAIRS SECTION AT DAMAGED AREA DETAIL:
 PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 EXTERIOR WALL STUCCO FINISH:
 A) SPECIFY STUCCO THICKNESS AS REQUIRED BY ASTM C926.
 SEE SEC. 2512.1 FBC-BUILDING.
 B)SPECIFY TWO LAYERS OF WATER RESISTIVE BARRIERS. SEE
 SEC. 2510.6 FBC-BUILDING.
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW.
 VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S
 OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS
 REQUIRED BY SEC. 109.3 CITY AMENDMENTS.
 REVISE VALUATION TO INCLUDE ALL THE SCOPE OF WORK.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-10-21 Cont ID  
Sent By jleahy Date 2021-10-21 Time 11:24 Rev Time 0.00
Received By jleahy Date 2021-10-21 Time 11:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-06-16 Cont ID  
Sent By jleahy Date 2021-06-16 Time 15:19 Rev Time 0.00
Received By jleahy Date 2021-06-16 Time 15:14 Sent To  
Notes
2021-06-16 15:25:25ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) PANEL CAN NOT BE IN A CLOSET.
  
 240.24(D) NOT IN VICINITY OF EASILY IGNITIBLE MATERIAL.
 OVERCURRENT DEVICES SHALL NOT BE LOCATED IN THE
 VICINITY OF EASILY IGNITIBLE MATERIAL, SUCH AS IN
 CLOTHES CLOSETS.
  
 2) OUTLET REQUIRED AT THE FRONT AND REAR OF UNIT
 OUTSIDE.
  
 210.52(E)(1) ONE-FAMILY AND TWO-FAMILY DWELLINGS. FOR A
 ONE-FAMILY DWELLING AND EACH UNIT OF A TWO-FAMILY
 DWELLING THAT IS AT GRADE LEVEL, AT LEAST ONE
 RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND NOT
 MORE THAN 2.0 M (6 1?2 FT) ABOVE GRADE LEVEL SHALL BE
 INSTALLED AT THE FRONT AND BACK OF THE DWELLING.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-10-12 Cont ID  
Sent By pleduc Date 2021-10-12 Time   Rev Time 0.00
Received By pleduc Date 2021-10-12 Time 13:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-07-12 Cont ID  
Sent By pleduc Date 2021-07-12 Time   Rev Time 0.00
Received By pleduc Date 2021-07-12 Time 12:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-10-21 Cont ID  
Sent By jleahy Date 2021-10-21 Time 11:24 Rev Time 0.00
Received By jleahy Date 2021-09-27 Time 14:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-07-12 Cont ID  
Sent By jgomez Date 2021-07-12 Time 15:57 Rev Time 0.00
Received By jgomez Date 2021-06-11 Time 15:37 Sent To I
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-09-28 Cont ID  
Sent By lcrespo Date 2021-09-28 Time 15:16 Rev Time 0.00
Received By lcrespo Date 2021-09-28 Time 15:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-06-15 Cont ID  
Sent By medwards Date 2021-06-15 Time 06:12 Rev Time 0.00
Received By medwards Date 2021-06-15 Time 06:07 Sent To  
Notes
2021-06-15 06:11:42SHEET S-1 IS AN ORIGINAL SIGNED AND SEALED PAPER
 DRAWING, APPROVED.
 SHEETS E0,E1 AND DAMAGED AREA SHEET ARE COPIES OF
 ENGINEER'S DIGITAL SIGNATURES. WE CANNOT ACCEPT COPIES
 OF DIGITAL SIGNATURES. THIS SUBMITTAL WAS A PAPER
 SUBMITTAL CONVERTED TO DIGITAL AT OUR OFFICE. PLEASE
 PROVIDE ORIGINAL SIGNED AND SEALED PAPER DRAWINGS.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2021-07-06 Cont ID  
Sent By rthermid Date 2021-07-06 Time   Rev Time  
Received By rthermid Date 2021-07-06 Time   Sent To I
Notes
***NONE***