Plan Review Details - Permit 21060723
Plan Review Stops For Permit 21060723
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-07-09 Cont ID  
Sent By rmcdouga Date 2021-07-09 Time 10:08 Rev Time 0.00
Received By rmcdouga Date 2021-07-09 Time 10:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-06-28 Cont ID  
Sent By rmcdouga Date 2021-06-28 Time 09:26 Rev Time 0.00
Received By rmcdouga Date 2021-06-28 Time 09:26 Sent To  
Notes
2021-06-28 09:29:18PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PARTS OF THE LOUVER'S PRODUCT APPROVAL ARE
 ILLEGIBLE. FBC AMEND. 107.2.1

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-07-09 Cont ID  
Sent By rmcdouga Date 2021-07-09 Time 10:09 Rev Time 0.00
Received By rmcdouga Date 2021-06-29 Time 08:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-06-28 Cont ID  
Sent By rmcdouga Date 2021-06-28 Time 09:27 Rev Time 0.00
Received By rmcdouga Date 2021-06-11 Time 13:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-07-06 Cont ID  
Sent By hmoser Date 2021-07-06 Time 14:03 Rev Time 0.00
Received By hmoser Date 2021-07-06 Time 13:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-06-21 Cont ID  
Sent By ccole Date 2021-06-21 Time 09:59 Rev Time 0.00
Received By hmoser Date 2021-06-21 Time 08:43 Sent To  
Notes
2021-06-21 09:58:55PLAN DENIED.
 REFER TO SECTION 107.2.1.3 QUALITY OF PLANS.
 CAN'T READ SHOP DRAWINGS.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2021-07-09 Cont ID  
Sent By rmcdouga Date 2021-07-09 Time 09:37 Rev Time 0.00
Received By rmcdouga Date 2021-07-09 Time 09:37 Sent To  
Notes
2021-07-09 09:53:06THE ARCHITECTURAL DRAWINGS ARE MARKED FOR REFERENCE.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-06-28 Cont ID  
Sent By rmcdouga Date 2021-06-28 Time 09:26 Rev Time 0.00
Received By rmcdouga Date 2021-06-28 Time 09:26 Sent To  
Notes
2021-06-28 09:38:26THE ARCHITECTURAL DRAWINGS THAT WERE SUBMITTED ARE NOT
 DIGITALLY SIGNED BY THE DESIGNER. ELECTRONICALLY
 SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT
 OR ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ARCHITECT OR ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE
 AND SEAL IS REQUIRED TO BE ON THE DRAWINGS. NO
 PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE
 ACCEPTABLE. FS 481 & 61G1 OR FS 471 & 61G15