Plan Review Details - Permit 21060503
Plan Review Stops For Permit 21060503
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2021-06-23 Cont ID  
Sent By pvalenti Date 2021-06-23 Time 11:20 Rev Time 0.00
Received By pvalenti Date 2021-06-23 Time 11:20 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-06-22 Cont ID  
Sent By pvalenti Date 2021-06-22 Time 14:36 Rev Time 0.00
Received By pvalenti Date 2021-06-22 Time 14:36 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-06-18 Cont ID  
Sent By pvalenti Date 2021-06-18 Time 08:12 Rev Time 0.00
Received By pvalenti Date 2021-06-18 Time 07:16 Sent To  
Notes
2021-06-18 08:13:16****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 ASBESTOS REQUIREMENTS:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-06-29 Cont ID  
Sent By pvalenti Date 2021-06-29 Time 14:02 Rev Time 0.00
Received By pvalenti Date 2021-06-29 Time 14:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-06-23 Cont ID  
Sent By pvalenti Date 2021-06-23 Time 11:10 Rev Time 0.00
Received By pvalenti Date 2021-06-23 Time 11:10 Sent To  
Notes
2021-06-23 11:11:22****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW DENIED:
  
 THE FOLLOWING ARE REQUIRED PRIOR TO ISSUANCE OF A DEMO
 PERMIT PER FLORIDA BUILDING CODE, BUILDING 3303:
  
 3) PLEASE PROVIDE THE METHOD OF WATER DOWN DURING
 DEMOLITION:
 A) IF A WATER TRUCK IS DESIRED, PROVIDE A LETTER
 STATING THE GALLON CAPACITY OF WATER TANK AND A
 STATEMENT THAT THE WATER USED WILL BE POTABLE WATER
 FROM AN OFF?SITE LOCATION ONLY AND THE WATER TRUCK WILL
 BE ON?SITE AT ALL TIMES DURING DEMOLITION.
 B) IF A HYDRANT METER IS DESIRED THAN A
 PERMIT/REGISTRATION NEEDS TO BE OBTAINED FROM THE CITY
 OF WEST PALM BEACH PUBLIC UTILITIES DEPARTMENT.
 C) IF A BACK FLOW PREVENTER IS DESIRED, THEN A SEPARATE
 BACKFLOW PERMIT INCLUDING THE FINAL INSPECTION FROM THE
 BUILDING DEPARTMENT (PLUMBING) IS REQUIRED.
 IF SELECTING THE BACKFLOW OPTION; BEFORE SCHEDULING THE
 FINAL PLUMBING INSPECTION, THE BACKFLOW DEVICE NEEDS TO
 BE TESTED AND CERTIFIED BY THE PUBLIC UTILITIES
 DEPARTMENT, 561 822 2244.
  
 4) THE SEWER LATERAL CAPPING PERMIT HAS BEEN OBTAINED
 (21060646). THE APPROVED FINAL PLUMBING INSPECTION IS
 REQUIRED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-06-18 Cont ID  
Sent By pvalenti Date 2021-06-18 Time 08:22 Rev Time 0.00
Received By pvalenti Date 2021-06-18 Time 07:16 Sent To  
Notes
2021-06-18 09:07:19****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW DENIED:
  
 THE FOLLOWING ARE REQUIRED PRIOR TO ISSUANCE OF A DEMO
 PERMIT PER FLORIDA BUILDING CODE, BUILDING 3303:
  
 2) UTILITY RELEASE - FLORIDA PUBLIC UTILITIES (GAS)
 RELEASE OF SERVICE CONFIRMATION. THIS RELEASE NEEDS TO
 COME FROM FLORIDA PUBLIC UTILITIES ON THEIR FORM.
  
 3) PLEASE PROVIDE THE METHOD OF WATER DOWN DURING
 DEMOLITION:
 A) IF A WATER TRUCK IS DESIRED, PROVIDE A LETTER
 STATING THE GALLON CAPACITY OF WATER TANK AND A
 STATEMENT THAT THE WATER USED WILL BE POTABLE WATER
 FROM AN OFF-SITE LOCATION ONLY AND THE WATER TRUCK WILL
 BE ON-SITE AT ALL TIMES DURING DEMOLITION.
 B) IF A HYDRANT METER IS DESIRED THAN A
 PERMIT/REGISTRATION NEEDS TO BE OBTAINED FROM THE CITY
 OF WEST PALM BEACH PUBLIC UTILITIES DEPARTMENT.
 C) IF A BACK FLOW PREVENTER IS DESIRED, THEN A SEPARATE
 BACKFLOW PERMIT INCLUDING THE FINAL INSPECTION FROM THE
 BUILDING DEPARTMENT (PLUMBING) IS REQUIRED.
 IF SELECTING THE BACKFLOW OPTION; BEFORE SCHEDULING THE
 FINAL PLUMBING INSPECTION, THE BACKFLOW DEVICE NEEDS TO
 BE TESTED AND CERTIFIED BY THE PUBLIC UTILITIES
 DEPARTMENT, 561 822 2244.
  
 4) THE SEWER LATERAL CAPPING PERMIT HAS BEEN OBTAINED
 (21060646). THE APPROVED FINAL PLUMBING INSPECTION IS
 REQUIRED.
  
 6) PLEASE COMPLETE AND UPLOAD THE DEMO DEBRIS REMOVAL
 FORM. IF THE FORM IS NOT AVAILABLE ON LINE, SEND A
 REQUEST FOR THE FORM TO [email protected].
  
 9) PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEB-SITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THE NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBEST-DEMOLITION-RE
 NOVATION.HTML
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2021-06-11 Cont ID  
Sent By rrossano Date 2021-06-11 Time   Rev Time  
Received By rrossano Date 2021-06-11 Time   Sent To  
Notes
2021-06-11 16:48:19PASSED WITH PROVISO: INDICATE METHOD OF STORMWATER
 POLLUTION PROTECTION ON PLAN; SILT FENCE, ETC.
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2021-06-15 Cont ID  
Sent By aborngra Date 2021-06-15 Time 10:29 Rev Time 0.00
Received By aborngra Date 2021-06-15 Time 10:28 Sent To  
Notes
2021-06-15 10:29:02REMOVAL OF TREES ON THE PROPERTY MAY REQUIRE A TREE
 ALTERATION PERMIT. ? AB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-06-23 Cont ID  
Sent By pvalenti Date 2021-06-23 Time 11:20 Rev Time 0.00
Received By pvalenti Date 2021-06-22 Time 12:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-06-18 Cont ID  
Sent By pvalenti Date 2021-06-18 Time 09:07 Rev Time 0.00
Received By pvalenti Date 2021-06-09 Time 05:22 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-06-18 Cont ID  
Sent By pvalenti Date 2021-06-18 Time 08:21 Rev Time 0.00
Received By pvalenti Date 2021-06-18 Time 07:16 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2021-06-15 Cont ID  
Sent By aborngra Date 2021-06-15 Time 10:28 Rev Time 0.00
Received By aborngra Date 2021-06-15 Time 10:28 Sent To  
Notes
***NONE***