Plan Review Details - Permit 21060473
Plan Review Stops For Permit 21060473
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 4 Status P Date 2021-08-13 Cont ID  
Sent By rmcphers Date 2021-08-13 Time 14:05 Rev Time 0.00
Received By rmcphers Date 2021-08-13 Time 14:05 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status F Date 2021-08-02 Cont ID  
Sent By rmcphers Date 2021-08-02 Time 15:30 Rev Time 0.00
Received By rmcphers Date 2021-08-02 Time 15:30 Sent To  
Notes
2021-08-02 15:33:18PLEASE SIGN THE ASBESTOS LETTER AND PROVIDE THE
 FOLLOWING STATEMENT ON THE LETTER -
  
 "THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY"
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2021-07-23 Cont ID  
Sent By shill Date 2021-07-23 Time 15:07 Rev Time 0.00
Received By shill Date 2021-07-23 Time 15:07 Sent To  
Notes
2021-07-23 15:08:13THE LETTER UPLOADED DOES NOT HAVE THE REQUIRED
 LANGUAGE.
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-07-21 Cont ID  
Sent By shill Date 2021-07-21 Time 10:51 Rev Time 0.00
Received By shill Date 2021-07-21 Time 10:51 Sent To  
Notes
2021-07-21 10:52:52PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2021-08-18 Cont ID  
Sent By rmcphers Date 2021-08-18 Time 15:22 Rev Time 0.00
Received By rmcphers Date 2021-08-18 Time 15:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2021-08-13 Cont ID  
Sent By rmcphers Date 2021-08-13 Time 14:04 Rev Time 0.00
Received By rmcphers Date 2021-08-13 Time 13:52 Sent To  
Notes
2021-08-13 14:00:19FLOORING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) THE FLAME SPREAD TEST REPORT PROVIDED IS FOR
 WHISPERMAT HW. (THE UNDERLAYMENT IS WHISPER MAT CS) THE
 FLAME SPREAD TEST REPORT NEEDS TO BE ON THE PRODUCT
 THAT YOU ARE USING.
 2) THE PROFLEX FLAME SPREAD TEST REPORT IS FOR TILE.
 3) PLEASE PROVIDE A FLAME SPREAD TEST REPORT FOR THE
 PRODUCT THAT YOU ARE USING. NOT SURE WHICH PRODUCT YOU
 ARE USING THERE ARE A FEW IN PROJECTDOX FOLDER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-08-02 Cont ID  
Sent By rmcphers Date 2021-08-02 Time 15:34 Rev Time 0.00
Received By rmcphers Date 2021-08-02 Time 15:34 Sent To  
Notes
2021-08-02 15:37:29FLOORING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) THE FLAME SPREAD TEST REPORT PROVIDED NEEDS TO
 INCLUDE THE UNDERLAYMENT IN THE TESTED ASSEMBLY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-07-23 Cont ID  
Sent By shill Date 2021-07-23 Time 15:04 Rev Time 0.00
Received By shill Date 2021-07-23 Time 15:04 Sent To  
Notes
2021-07-23 15:07:02****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. A TEST REPORT WAS PROVIDED, BUT IT IS FOR STC AND
 IIC, NOT FLAME SPREAD (SEE PREVIOUS COMMENT LIST). THE
 STC/IIC WERE TESTED WITH AN ASSEMBLY THAT INCLUDED
 FIBERGLASS INSULATION AND DRYWALL IN THE UNIT BELOW.
 THIS TEST IS CANNOT BE USED BUT WE HAVE A STC/IIC TEST
 ON FILE, BUT NOT FLAME SPREAD FOR WHISPERMAT CS ALONE
 OR WITH A WOOD FLOOR.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-07-21 Cont ID  
Sent By shill Date 2021-07-21 Time 10:48 Rev Time 0.00
Received By shill Date 2021-07-21 Time 10:48 Sent To  
Notes
2021-07-21 10:50:18****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. WHISPERMAT CS IS PROPOSED, WOOD FLOORING. PROVIDE
 THE FOLLOWING TEST REPORTS:
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 THE TEST NEEDS TO BE ON UNDERLAYMENT ALONE OR WITH WOOD
 FLOOR.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-07-21 Cont ID  
Sent By jleahy Date 2021-07-21 Time 19:39 Rev Time 0.00
Received By jleahy Date 2021-07-21 Time 19:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-08-05 Cont ID  
Sent By cwalker Date 2021-08-05 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-07-08 Cont ID  
Sent By cwalker Date 2021-07-08 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-08-18 Cont ID  
Sent By rmcphers Date 2021-08-18 Time 15:22 Rev Time 0.00
Received By rmcphers Date 2021-08-18 Time 07:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-08-13 Cont ID  
Sent By rmcphers Date 2021-08-13 Time 14:05 Rev Time 0.00
Received By rmcphers Date 2021-08-03 Time 11:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-08-02 Cont ID  
Sent By rmcphers Date 2021-08-02 Time 15:37 Rev Time 0.00
Received By rmcphers Date 2021-07-27 Time 09:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-07-23 Cont ID  
Sent By shill Date 2021-07-23 Time 15:08 Rev Time 0.00
Received By shill Date 2021-07-22 Time 15:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-07-21 Cont ID  
Sent By jleahy Date 2021-07-21 Time 19:39 Rev Time 0.00
Received By jleahy Date 2021-07-06 Time 14:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-07-19 Cont ID  
Sent By lcrespo Date 2021-07-19 Time 08:12 Rev Time 0.00
Received By lcrespo Date 2021-07-19 Time 08:07 Sent To  
Notes
2021-07-19 08:12:5907/19/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-07-21 Cont ID  
Sent By shill Date 2021-07-21 Time 10:53 Rev Time 0.00
Received By shill Date 2021-07-21 Time 10:53 Sent To  
Notes
***NONE***