Plan Review Details - Permit 21060464
Plan Review Stops For Permit 21060464
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-09-22 Cont ID  
Sent By pvalenti Date 2021-09-22 Time 05:50 Rev Time 0.00
Received By pvalenti Date 2021-09-22 Time 05:41 Sent To  
Notes
2021-09-22 05:51:58 
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW APPROVED WITH PROVISO:
  
 UNDERLAYMENT MUST BE APPLIED IN (2) LAYERS PER FBC R
 905.1.1.1.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-09-17 Cont ID  
Sent By pvalenti Date 2021-09-17 Time 11:06 Rev Time 0.00
Received By pvalenti Date 2021-09-17 Time 10:54 Sent To  
Notes
2021-09-17 11:10:49CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW DENIED:
  
 FBC R 905.1.1.1, PLEASE SPECIFY THE SECONDARY WATER
 BARRIER THAT WILL BE USED FOR THE SLOPED ROOF; DOUBLE
 UP BASE SHEET OR COVER THE WOOD ROOF SEEMS AND FULLY
 APPLY UNDERLAYMENT. IF COVERING THE WOOD SEEMS, PLEASE
 PROVIDE THE PRODUCT APPROVAL FOR MATERIAL TO BE USED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-08-17 Cont ID  
Sent By rmcdouga Date 2021-08-17 Time 14:01 Rev Time 0.00
Received By rmcdouga Date 2021-08-17 Time 14:00 Sent To  
Notes
2021-08-17 14:00:50PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PRODUCT APPROVAL THAT WAS SUBMITTED FL16709-R3,
 STATES THAT IT IS PENDING 2020 FBC APPROVAL. SUBMIT A
 PRODUCT APPROVAL THAT IS APPROVED FOR THE 2020 FBC.
  
 2) THIS PROJECT IS EXPOSURE C, ENCLOSED WITH A 15' ROOF
 HEIGHT AND 170 MPH ULTIMATE WIND SPEED. I BELIEVE THAT
 YOU WANT TO USE SYSTEM W-4. THE PRODUCT APPROVAL IS
 MISSING PAGE 19 OF 25. I BELIEVE THAT THE INFOMATION
 FOR AN ENCLOSED STRUCTURE IN EXPOSURE C FOR SYSTEM W-4
 IS ON THE MISSING PAGE. PLEASE SUBMIT THE MISSING PAGE.
 FBC AMEND. 107.2.1
  
 3) SPECIFY WHICH METHOD OF A SECONDARY WATER BARRIER AS
 REQUIRED BY FBC-R905.1.1.1 WILL BE INSTALLED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-07-21 Cont ID  
Sent By ccole Date 2021-07-21 Time 14:25 Rev Time 0.00
Received By ccole Date 2021-07-21 Time 14:25 Sent To  
Notes
2021-07-21 14:25:211ST REVIEW FBC-2020 RES. BUILDING.
 PERMIT- 21060464
 7/21/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THERE ARE TWO DIFFERENT MIAMI-DADE NOA'S SUBMITTED-
 ONE FOR WOOD DECKS, AND ONE FOR CEMENTITIOUS WOOD
 DECKS. PLEASE CHOSE ONE SYSTEM OR THE OTHER. IF USING
 THE WOOD DECK NOA 18-0919.12, THE APPROVED ASSEMBLIES
 ARE LOCATED ON PAGES 9- 66. PLEASE HIGHLIGHT ON MARK
 WHICH ASSEMBLY IS TO BE INSTALLED OR SUBMIT ONLY THE
 PAGE THAT THE ASSEMBLY DETAILS ARE ON. PLEASE REFER TO
 THE GENERAL LIMITATIONS NOTES WHICH ARE FOUND AT THE
 LAST PAGE OF EACH NOA. UNDER NOTE #7 EACH NOA HAS A
 REQUIREMENT FOR ENGINEERED CALCULATIONS FOR INCREASED
 MECHANICAL FASTENING OF BASE SHEETS AT PERIMETER AND
 CORNER AREAS OF THE ROOF. THE CALCULATIONS AND
 FASTENING DETAILS SHALL BE PREPARED BY A FL. REGISTERED
 DESIGN OR REGISTERED ROOF CONSULTANT. CALCULATIONS AND
 DETAILS BY FL. LICENSED ENGINEERS OR ARCHITECTS SHALL
 BEAR THE SEAL AND SIGNATURE OF THE DESIGN PROFESSIONAL.
 THE ENGINEERING MAY BE SUBMITTED IN DUPLICATE PAPER
 FORM (TWO COPIES SIGNED AND SEALED) TO WPB BUILDING
 DEPARTMENT OR CAN BE SENT ELECTRONICALLY WITH THE
 DIGITAL SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL-
 FL. STATUTES 471.025 AND 481.221.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-09-17 Cont ID  
Sent By pvalenti Date 2021-09-17 Time 11:11 Rev Time 0.00
Received By pvalenti Date 2021-09-08 Time 08:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-08-17 Cont ID  
Sent By rmcdouga Date 2021-08-17 Time 14:01 Rev Time 0.00
Received By rmcdouga Date 2021-08-16 Time 08:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-07-21 Time   Rev Time 0.00
Received By cdecoeur Date 2021-07-20 Time 08:34 Sent To  
Notes
***NONE***