| Plan Review Stops For Permit 21060414 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2023-04-20 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2023-04-20 |
Time |
07:51 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2023-04-20 |
Time |
07:34 |
Sent To |
|
|
| Notes |
| 2023-04-20 07:55:07 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II/INSPECTOR | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | | | | BUILDING REVIEW APPROVAL PENDING APPROVAL OF SIGNATURE | | | REVIEW. | | | | | | | | | ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: | | | | | | NOTICE: ALL PLAN PAGES ARE MISSING THE ARCHITECTS | | | SIGNATURE/SEAL. | | | | | | 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND | | | SUBMITTED ELECTRONICALLY FOR PUBLIC RECORD SHALL HAVE A | | | VALID DIGITAL SIGNATURE. A SCAN OF A WET SEAL AND | | | SIGNATURE OR DIGITAL SIGNATURE IS NOT CONSIDERED A | | | VALID DIGITAL SIGNATURE. | | | ALL ELECTRONIC DOCUMENTS PREPARED BY ARCHITECTS OR | | | ENGINEERS MUST BE DIGITALLY SIGNED, IN ACCORDANCE WITH | | | 61G1-16 AND 61G15, F.A.C. | | | | | | 2. SUBMIT PLANS WITH A VALID DIGITAL SIGNATURE. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2022-07-28 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-07-28 |
Time |
07:02 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-07-28 |
Time |
06:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2021-12-13 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2021-12-13 |
Time |
08:39 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2021-12-13 |
Time |
06:19 |
Sent To |
|
|
| Notes |
| 2021-12-13 08:45:18 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | BUILDING REVIEW DENIED: | | | | | | 1.) OK | | | 2.) FBC B 107.2.1, PROVIDE THE ENERGY CALCULATIONS. | | | 3.) FBC B 109.3, PLEASE PROVIDE RESPONSE TO VALUATION | | | IN QUESTION. THE VALUATION MAY NEED TO CHANGE, AS | | | CHANGING THE SCREENED ENCLOSED PORCH TO A HABITABLE | | | SPACE MUST MEET THE ELECTRIC AND MECHANICAL | | | REQUIREMENTS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-06-24 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2021-06-24 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2021-06-24 |
Time |
08:50 |
Sent To |
|
|
| Notes |
| 2021-06-24 10:47:37 | ****CORRECTIONS**** | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | BUILDING REVIEW DENIED: | | | | | | 1) FBC B 107.2.1, THE WINDOW SCHEDULE ON SHEET A-1 | | | INDICATES THAT THE FIXED WINDOWS ARE TO BE IMPACT | | | RESISTANT, BUT THE SUBMITTED N.O.A. (FIXED WINDOWS) IS | | | FOR NON-IMPACT RATED WINDOWS. PLEASE CORRECT PLAN | | | SHEETS OR PROVIDE AN N.O.A FOR IMPACT RESISTANT FIXED | | | WINDOWS. | | | | | | 2) FBC B 107.2.1, PLEASE PROVIDE THE ENERGY | | | CALCULATIONS. | | | | | | 3) NOTE: THE VALUATION MAY NEED TO CHANGE, AS CHANGING | | | THE SCREENED ENCLOSED PORCH TO A HABITABLE SPACE MUST | | | MEET THE ELECTRIC AND MECHANICAL REQUIREMENTS. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2023-04-20 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-04-20 |
Time |
15:08 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-04-20 |
Time |
15:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
N |
Date |
2021-06-25 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-06-25 |
Time |
11:46 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-06-25 |
Time |
11:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
4 |
Status |
F |
Date |
2023-05-02 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2023-05-02 |
Time |
16:47 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2023-05-02 |
Time |
16:47 |
Sent To |
|
|
| Notes |
| 2023-05-02 16:48:01 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S) | | | | | | PROJECT STILL REQUIRES HPB APPROVAL. | | | | | | ANNE HAMILTON | | | HISTORIC PRESERVATION PLANNER | | | [email protected] | | | 561.822.1428 | | | | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
3 |
Status |
F |
Date |
2022-06-22 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2022-06-22 |
Time |
10:53 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2022-06-22 |
Time |
10:53 |
Sent To |
|
|
| Notes |
| 2022-06-22 10:53:33 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S) | | | | | | PROJECT STILL REQUIRES HPB APPROVAL. | | | | | | ANNE HAMILTON | | | HISTORIC PRESERVATION PLANNER | | | [email protected] | | | 561.822.1428 | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
2 |
Status |
F |
Date |
2021-12-08 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2021-12-08 |
Time |
10:18 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2021-12-08 |
Time |
10:18 |
Sent To |
|
|
| Notes |
| 2021-12-08 10:19:59 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S) | | | | | | THE ENCLOSURE OF A SCREENED PORCH REQUIRES APPROVAL | | | FROM THE HISTORIC PRESERVATION BOARD. PLEASE CONTACT | | | FOR A COA APPLICATION. | | | | | | ANNE HAMILTON | | | HISTORIC PRESERVATION PLANNER | | | [email protected] | | | 561.822.1428 |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
F |
Date |
2021-07-13 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2021-07-13 |
Time |
15:58 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2021-07-13 |
Time |
15:58 |
Sent To |
|
|
| Notes |
| 2021-07-13 15:59:57 | PORCH ENCLOSURE WITH WINDOWS AND CHANGE IN STYLE ON | | | OTHERS REQUIRES BOARD APPROVAL. SENT COA FORM TO | | | CONTRACTOR. | | | | | | QUESTIONS, CONTACT: | | | | | | FRIEDERIKE MITTNER, CITY HISTORIC PRESERVATION PLANNER | | | (561) 822-1457 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2023-05-03 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2023-05-03 |
Time |
10:35 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2023-04-19 |
Time |
08:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-07-28 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-07-28 |
Time |
07:04 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-06-06 |
Time |
06:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-12-13 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2021-12-13 |
Time |
08:45 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2021-11-30 |
Time |
13:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-07-13 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2021-07-13 |
Time |
16:03 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2021-06-07 |
Time |
13:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2021-06-24 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2021-06-24 |
Time |
11:29 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2021-06-24 |
Time |
11:29 |
Sent To |
|
|
| Notes |
| 2021-06-24 11:31:37 | | | | ****CORRECTIONS**** | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | IMPACT FEES - DIGITAL SUBMITTALS | | | | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON | | | APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO | | | YOUR PROJECT OR EMAIL IT TO [email protected] . | | | | | | IMPACT FEES - PAPER SUBMITTALS | | | | | | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL | | | (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE | | | PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE | | | RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS | | | APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE | | | QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE | | | FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD | | | MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2021-06-25 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-06-25 |
Time |
16:35 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-06-25 |
Time |
16:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
F |
Date |
2023-04-20 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2023-04-20 |
Time |
07:28 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2023-04-20 |
Time |
07:25 |
Sent To |
|
|
| Notes |
| 2023-04-20 07:31:43 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II/INSPECTOR | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | SIGNATURE REVIEW DENIED: | | | | | | THE PAPER PLAN SHEETS A-1 & E-1 HAVE BEEN SUBMITTED | | | WITH NO ORIGINAL HAND SIGNATURES/SEALS. NO OTHER PLAN | | | SHEETS HAVE BEEN SUBMITTED. | | | FS 471/FS 481 DOCUMENTS PREPARED BY AN | | | ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE | | | TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A | | | SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL. | | | PLEASE UPLOAD OR EMAIL ALL PLANS (DIGITALLY SIGNED & | | | THIRD PARTY VERIFIED) : | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | BUILDING DIVISION | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET, 1ST FLOOR | | | WEST PALM BEACH, FL 33401 | | | FEEL FREE TO CONTACT ME AT 561 805 6673. | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2022-07-28 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-07-28 |
Time |
07:02 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-07-28 |
Time |
06:21 |
Sent To |
|
|
| Notes |
| 2022-07-28 07:03:41 | SIGNATURE REVIEW DENIED: | | | | | | FS 471/FS 481 DOCUMENTS PREPARED BY AN | | | ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE | | | TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A | | | SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL. | | | UPLOAD OR EMAIL A DIGITALLY SIGNED (THIRD PARTY | | | VERIFIED) PLAN: | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | BUILDING DIVISION | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET, 1ST FLOOR | | | WEST PALM BEACH, FL 33401 | | | FEEL FREE TO CONTACT ME AT 561 805 6673. | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2021-12-01 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-12-01 |
Time |
09:53 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-12-01 |
Time |
09:53 |
Sent To |
|
|
| Notes |
| 2021-12-01 10:01:12 | THE PAPER PLANS DO NOT HAVE THE HANDWRITTEN SIGNATURE | | | OF THE ARCHITECT AS REQUIRED BY FS 481 & FAC 61G1. SENT | | | TO DENIED SIGNATURE BOX. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2021-06-07 |
|
|
Cont ID |
|
| Sent By |
equinone |
Date |
2021-06-07 |
Time |
13:41 |
Rev Time |
0.00 |
| Received By |
equinone |
Date |
2021-06-07 |
Time |
13:41 |
Sent To |
|
|
| Notes |
| 2021-06-07 13:42:15 | PAPER DRAWINGS SUBMITTED WITH ORIGINAL SEAL AND | | | SIGNATURE. ROUTED TO STORAGE. EQ |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2021-07-13 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2021-07-13 |
Time |
15:58 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2021-07-13 |
Time |
15:58 |
Sent To |
|
|
| Notes |
|
|