Plan Review Details - Permit 21060413
Plan Review Stops For Permit 21060413
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2021-09-09 Cont ID  
Sent By cpuell Date 2021-09-09 Time 13:23 Rev Time 0.00
Received By cpuell Date 2021-09-09 Time 13:23 Sent To  
Notes
2021-09-09 13:24:02HALF ADDRESS READDRESSED TO 322 EDGEWOOD DR

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2021-08-16 Cont ID  
Sent By cpuell Date 2021-08-16 Time 14:18 Rev Time 0.00
Received By cpuell Date 2021-08-16 Time 14:18 Sent To  
Notes
2021-08-16 14:20:27REVIEWED THE RESPONSE TO COMMENTS, THE WARRANTY DEED
 HAS NO REFLECTION ON THE NEED TO READDRESS THE HALF
 ADDRESS SOUTH BUILDING. PLEASE HAVE OWNER = CONTACT
 [email protected] OR CALL 561-805-6659 SO THAT THE HALF
 ADDRESS CAN BE READDRESSED.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-07-14 Cont ID  
Sent By cpuell Date 2021-07-14 Time 09:27 Rev Time 0.00
Received By cpuell Date 2021-07-14 Time 09:27 Sent To  
Notes
2021-07-14 09:28:27THE REAR PROPERTY HAS A HALF ADDRESS WHICH WILL NEED TO
 BE READDRESSED, PLEASE HAVE OWNER COORDINATE WITH
 [email protected] OR CALL 561-805-6659 FOR THE REAR
 PROPERTY TO BE GIVEN A NEW ADDRESS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status N Date 2021-09-24 Cont ID  
Sent By dbattles Date 2021-09-24 Time 09:37 Rev Time 0.00
Received By dbattles Date 2021-09-24 Time 09:37 Sent To  
Notes
2021-09-24 09:38:36BUILDING PORTION REMOVED FROM SCOPE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-09-03 Cont ID  
Sent By rmcdouga Date 2021-09-03 Time 09:47 Rev Time 0.00
Received By rmcdouga Date 2021-09-03 Time 09:47 Sent To  
Notes
2021-09-03 09:47:40PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO, CFM
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE SCOPE OF WORK IS STILL NOT CLEAR. PRODUCT
 APPROVALS FOR A FIXED WINDOW AND A DOUBLE FRENCH DOOR
 WERE SUBMITTED. BASED ON THE FLOOR PLAN IT APPEARS THAT
 YOU ARE REPLACING A WINDOW WITH A DOUBLE FRENCH DOOR.
 IF THIS IS THE CASE THE PRODUCT APPROVAL FOR THE WINDOW
 IS NOT NEEDED. IF ANY WINDOWS ARE TO BE REPLACED,
 SPECIFY THEIR LOCATIONS AND SIZES ON THE FLOOR PLAN.
 [THE SCOPE OF WORK FOR THE WINDOW AND DOOR IS NOT
 CLEAR. PLEASE CLARIFY WHAT YOU ARE PROPOSING TO DO. FBC
 AMEND. 107.2.1]
  
 2) THE ADDRESS OF THE PROJECT AND THE NAME AND
 SIGNATURE OF THE PERSON RESPOSIBLE FOR THE DRAWING ARE
 REQUIRED TO BE ON THE PLAN. FBC 107.2.1 - INFORMATION
 ON CONSTRUCTION DOCUMENTS. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. [SUBMIT A FLOOR PLAN THAT SHOWS THE LOCATIONS,
 TYPES AND SIZES OF THE WINDOW AND DOOR THAT ARE BEING
 REPLACED. FBC AMEND. 107.2.1]
  
 3) IF YOU ARE INSTALLING A DOUBLE FRENCH DOOR IN THE
 EXISTING OPENING FOR A WINDOW, THE SIZE OF THE OPENING
 WILL NEED TO BE INCREASED. SUBMIT A DRAWING WITH
 FRAMING DETAILS FOR A WOOD WALL OR BUCK DETAILS FOR
 CONCRETE BLOCK WALL. PROVIDE EXTERIOR FLASHING DETAILS.
 FBC-R703.4
  
 4) SPECIFY THE MEAN ROOF HEIGHT OF THE BUILDING AND THE
 WIND DESIGN DATA ON THE DRAWINGS. FBC-R301.2.1
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-07-07 Cont ID  
Sent By rmcdouga Date 2021-07-07 Time 08:08 Rev Time 0.00
Received By rmcdouga Date 2021-07-07 Time 08:08 Sent To  
Notes
2021-07-07 08:24:10PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO, CFM
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE SCOPE OF WORK FOR THE WINDOW AND DOOR IS NOT
 CLEAR. PLEASE CLARIFY WHAT YOU ARE PROPOSING TO DO. FBC
 AMEND. 107.2.1
  
 2) SUBMIT A FLOOR PLAN THAT SHOWS THE LOCATIONS, TYPES
 AND SIZES OF THE WINDOW AND DOOR THAT ARE BEING
 REPLACED. FBC AMEND. 107.2.1
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2021-08-31 Cont ID  
Sent By rrossano Date 2021-08-31 Time   Rev Time 0.00
Received By rrossano Date 2021-08-31 Time   Sent To  
Notes
2021-08-31 12:53:46PASSED WITH PROVISOS: MAXIMUM DRIVEWAY WIDTHS AT RIGHT
 OF WAY SHALL NOT EXCEED 20 FT.PLUS TWO 3 FT. FLARES.
  
 CONSTRUCT CURB AND/OR DRIVEWAY PER CITY OF WPB STANDARD
 DETAILS GC-2 THROUGH GC-6.
  
 CALL FOR LOCATES, DIAL 811 BEFORE YOU DIG. FOR MORE
 INFO ON "CALL BEFORE YOU DIG", GO TO
 HTTP://WWW.SUNSHINE811.COM (REF: UNDERGROUND FACILITY
 DAMAGE PREVENTION AND SAFETY ACT, FLORIDA STATUTE,
 CHAPTER 556.)
  
  
 THANKS,
 RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR, WEST PALM BEACH, FL
 33401
 DIRECT: (561) 494-1098, FAX: (561) 494-1116, MOBILE:
 (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2021-06-11 Cont ID  
Sent By rrossano Date 2021-06-11 Time   Rev Time 0.00
Received By rrossano Date 2021-06-11 Time   Sent To  
Notes
2021-06-11 16:58:29CALL OUT DIMENSIONS AND CONSTRUCTION DETAILS OF ALL
 PAVING CURBS, HANDICAP RAMPS, AND PUBLIC OR PRIVATE
 SIDEWALKS. ALL SIDEWALK, RAMP AND CURB REPAIRS SHALL BE
 COMPLIANT WITH CITY OF WPB CONSTRUCTION STANDARD
 DETAILS GC-1 THROUGH GC-4.
  
 THANKS,
 RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR, WEST PALM BEACH, FL
 33401
 DIRECT: (561) 494-1098, FAX: (561) 494-1116, MOBILE:
 (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2021-07-14 Cont ID  
Sent By fmittner Date 2021-07-14 Time 08:33 Rev Time 0.00
Received By fmittner Date 2021-07-14 Time 08:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-09-24 Cont ID  
Sent By dbattles Date 2021-09-24 Time 09:38 Rev Time 0.00
Received By dbattles Date 2021-09-24 Time 09:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-09-23 Cont ID  
Sent By cpuell Date 2021-09-23 Time 12:49 Rev Time 0.00
Received By cpuell Date 2021-08-16 Time 08:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-07-14 Cont ID  
Sent By fmittner Date 2021-07-14 Time 09:28 Rev Time 0.00
Received By cpuell Date 2021-06-07 Time 13:11 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-07-07 Cont ID  
Sent By rmcdouga Date 2021-07-07 Time 08:24 Rev Time 0.00
Received By rmcdouga Date 2021-07-07 Time 08:24 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2021-09-23 Cont ID  
Sent By fmittner Date 2021-09-23 Time 12:39 Rev Time 0.00
Received By fmittner Date 2021-09-23 Time 12:39 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-07-14 Cont ID  
Sent By rthermid Date 2021-06-22 Time   Rev Time 0.00
Received By fmittner Date 2021-07-14 Time 08:33 Sent To I
Notes
2021-06-22 09:15:15ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 6/22/2021
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PLEASE PROVIDE A MARKED SURVEY SHOWING THE
 DIMENSIONS OF THE PROPOSED DRIVEWAY. PER THE CITY
 ZONING CODE, DRIVEWAYS CANNOT EXCEED 20 FEET IN WIDTH
 FOR A STRAIGHT DRIVEWAY, OR 10 FEET IN WIDTH FOR EACH
 LEG OF A CIRCULAR DRIVEWAY.
 2. 75% OR 1000SF OF THE FRONT YARD MUST BE LANDSCAPE.
 3. ADDRESS ENGINEERING COMMENTS.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOGIN
 INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
  
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 RAFAELA THERMIDOR, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561-822-1443
 TTY: 800.955.8771
 E: [email protected]
 W: WPB.ORG
  