Plan Review Details - Permit 21060412
Plan Review Stops For Permit 21060412
Review Stop AD ADDRESSING
Rev No 1 Status N Date 2021-06-09 Cont ID  
Sent By scwelter Date 2021-06-09 Time 14:45 Rev Time 0.00
Received By scwelter Date 2021-06-09 Time 14:46 Sent To  
Notes
***NONE***

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status N Date 2021-06-09 Cont ID  
Sent By scwelter Date 2021-06-09 Time 14:56 Rev Time 0.00
Received By scwelter Date 2021-06-09 Time 14:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-09-16 Cont ID  
Sent By rmcphers Date 2021-09-16 Time 08:04 Rev Time 0.00
Received By rmcphers Date 2021-09-16 Time 08:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-08-25 Cont ID  
Sent By rmcphers Date 2021-08-25 Time 08:38 Rev Time 0.00
Received By rmcphers Date 2021-08-25 Time 08:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-07-20 Cont ID  
Sent By rmcphers Date 2021-07-20 Time 13:24 Rev Time 0.00
Received By rmcphers Date 2021-07-20 Time 12:19 Sent To  
Notes
2021-07-20 12:59:23NEW 1 STORY BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) DRAWING S1 - THERE IS A CUT SECTION (1/ S1) WHICH
 SHOWS THE COVERED PATIO WITH NO SLAB AND A STEP DOWN
 FROM THE INTERIOR FLOOR ELEVATION - PLEASE CLARIFY.
 2) DRAWING G1.0 - WIND DESIGN DATA DOES NOT MATCH THE
 STRUCTURAL DRAWING S5 - EXPOSURE AND RISK CATEGORY -
 PLEASE CORRECT.
 3) PLEASE PROVIDE A GEOTECHNICAL REPORT (SOIL REPORT)
 FBC 1803
 4) PLEASE PROVIDE THE FRONT PAGES OF THE FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR DOORS AND WINDOWS -
 INSTALLATION INSTRUCTIONS HAVE BEEN PROVIDED.
 5) SURVEY PROVIDED SHOWS PROPERTY IN AN SPECIAL FLOOD
 HAZARD AREA - PLEASE PROVIDE A PROPOSED BUILDING
 ELEVATION CERTIFICATE.
 6) SEPARATE PERMITS ARE REQUIRED FOR PARKING LOT,
 DUMPSTER ENCLOSURES, FENCES - PLEASE ACKNOWLEDGE THIS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-08-30 Cont ID  
Sent By jleahy Date 2021-08-30 Time 15:58 Rev Time 0.00
Received By jleahy Date 2021-08-30 Time 15:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-06-16 Cont ID  
Sent By jleahy Date 2021-06-16 Time 08:39 Rev Time 0.00
Received By jleahy Date 2021-06-16 Time 08:26 Sent To  
Notes
2021-06-16 08:45:34ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) FAULT CURRENT CALCULATION FOR SERVICE AND PANEL NOT
 SHOWN ON PLANS. PLEASE INDICATE THE FAULT CURRENT AT
 THE SERVICE AND PANEL. 110.10, 110.24
  
 PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
  
 2) ALL 125V 15, AND 20 AMPERE RECEPTACLES INSTALLED IN
 THE KITCHEN NEED TO BE GFCI PROTECTED. 210.8(B)
  
 210.8(B) OTHER THAN DWELLING UNITS. ALL SINGLE-PHASE
 RECEPTACLES RATED 150 VOLTS TO GROUND OR LESS, 50
 AMPERES OR LESS AND THREEPHASE RECEPTACLES RATED 150
 VOLTS TO GROUND OR LESS, 100 AMPERES OR LESS INSTALLED
 IN THE FOLLOWING LOCATIONS SHALL HAVE GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL.
 (2) KITCHENS
  
  

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2023-02-28 Cont ID  
Sent By jleahy Date 2023-02-28 Time 15:43 Rev Time 0.00
Received By jleahy Date 2023-02-28 Time 15:43 Sent To  
Notes
2023-02-28 15:44:26VOICE , DATA, AND TV AS PER PLAN JLEAHY

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2021-09-08 Cont ID  
Sent By rrossano Date 2021-09-08 Time   Rev Time 0.00
Received By rrossano Date 2021-09-08 Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2021-08-31 Cont ID  
Sent By rrossano Date 2021-08-31 Time   Rev Time 0.00
Received By rrossano Date 2021-08-31 Time   Sent To  
Notes
2021-08-31 13:32:25A FORMAL ENGINEERING SUBMITTAL IS REQUIRED.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2021-06-29 Cont ID  
Sent By rrossano Date 2021-06-29 Time   Rev Time  
Received By rrossano Date 2021-06-29 Time   Sent To  
Notes
2021-06-29 08:07:23A FORMAL ENGINEERING SUBMITTAL IS REQUIRED ONCE SITE
 PLAN APPROVAL HAS BEEN ISSUED.
  
 THANKS,
 RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR, WEST PALM BEACH, FL
 33401
 DIRECT: (561) 494-1098, FAX: (561) 494-1116, MOBILE:
 (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-08-18 Cont ID  
Sent By pleduc Date 2021-08-18 Time   Rev Time 0.00
Received By pleduc Date 2021-08-18 Time 09:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-06-22 Cont ID  
Sent By pleduc Date 2021-06-22 Time   Rev Time 0.00
Received By pleduc Date 2021-06-17 Time 09:07 Sent To  
Notes
2021-06-17 09:47:12FIRE PROVISO:
  
 ** A FIRE ALARM SYSTEM IS INDICATED ON SHEET G1.0,
 HOWEVER, IT IS NOT NOTED ON THE ELECTRICAL SHEETS.
  
 ** ALL FIRE ALARM WORK SHALL BE SUBMITTED UNDER
 SEPARATE PERMIT & SHOP DRAWINGS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2021-08-28 Cont ID  
Sent By abelisle Date 2021-08-28 Time 09:21 Rev Time 0.00
Received By abelisle Date 2021-08-28 Time 07:35 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-06-21 Cont ID  
Sent By abelisle Date 2021-06-21 Time 19:13 Rev Time 0.00
Received By abelisle Date 2021-06-21 Time 19:13 Sent To  
Notes
2021-06-21 19:16:091ST REVIEW FBC-2020 PLUMBING
 PERMIT-21060412
 6/21/21
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020
 FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH
 EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1- PLAN PAGE A-1.0 INDICATES A GAS TANKLESS WATER
 HEATER IS TO BE INSTALLED IN THE STORAGE UTILITY ROOM.
 ON PLAN PAGE P0-1 AN ELECTRIC TANK TYPE WATER HEATER IS
 SHOWN. PLEASE CLARIFY. WPB AMENDMENTS TO THE FBC SEC.
 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS.
 2- ARE THE KITCHEN APPLIANCES GOING TO BE GAS OR
 ELECTRIC? WPB AMENDMENTS TO THE FBC SEC. 107.2.1.
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-09-16 Cont ID  
Sent By rmcphers Date 2021-09-16 Time 08:16 Rev Time 0.00
Received By rmcphers Date 2021-09-07 Time 14:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-09-07 Cont ID  
Sent By lmarchan Date 2021-09-07 Time 10:49 Rev Time 0.00
Received By lmarchan Date 2021-08-17 Time 16:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-07-20 Cont ID  
Sent By rmcphers Date 2021-07-20 Time 13:25 Rev Time 0.00
Received By rmcphers Date 2021-06-15 Time 11:51 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-09-17 Cont ID  
Sent By lmarchan Date 2021-09-17 Time 14:04 Rev Time 0.00
Received By lmarchan Date 2021-09-07 Time 10:52 Sent To  
Notes
2021-09-17 12:48:31RECEIPT MU-2021-044627 - $8423.13 - PAID
2021-09-07 10:52:429/7/21 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-07-14 Cont ID  
Sent By pvalenti Date 2021-07-14 Time 08:22 Rev Time 0.00
Received By pvalenti Date 2021-07-12 Time 07:54 Sent To  
Notes
2021-07-14 08:23:32****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-08-25 Cont ID  
Sent By medwards Date 2021-08-21 Time 09:00 Rev Time 0.00
Received By medwards Date 2021-08-21 Time 09:00 Sent To  
Notes
2021-08-21 09:04:00 
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-07-20 Cont ID  
Sent By medwards Date 2021-07-20 Time 08:58 Rev Time 0.00
Received By medwards Date 2021-07-20 Time 08:58 Sent To  
Notes
2021-07-20 08:58:482ND REVIEW FBC-2020 MECHANICAL
 PERMIT-21060412
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET LS1.0 OCCUPANT LOAD TABLE AND SHEET M6-1
 SQUARE FOOTAGE OF EACH SPACE DO NOT MATCH. PLEASE
 PROVIDE A PLAN WHERE THE SHEETS ARE CONSISTENT. I CAN
 NOT COMPLETE A MECHANICAL REVIEW UNTIL THE CORRECT
 NUMBERS ARE SHOWN. THE ENERGY CALCULATIONS AND THE
 MECHANICAL EQUIPMENT SIZING CALCULATIONS SHOW THAT THE
 KITCHEN HAS A SQ. FT. OF 655 AND THE DINING ROOM HAS A
 SQ FT. OF 1600. FBC 107.2.1
  
 2) SHEET M6-1: THE 2020 FMC M TABLE 403.3.1.1 REQUIRES
 .7 CFM X SQ. FT. TO BE EXHAUSTED FROM THE KITCHEN. I DO
 NOT SEE THAT THE CALCULATIONS HAVE REFLECTED THIS.
 PLEASE SHOW THIS IN THE CALCULATIONS.
  
 3) PLEASE ADDRESS NOTE 1 OF PREVIOUS REVIEW COMMENTS:
 PLEASE ADD A NOTE TO THE MECHANICAL DRAWINGS STATING
 THAT THE HOOD AND ANY REFRIGERATION SHALL BE SUBMITTED
 AS SEPARATE PERMITS AND WILL REQUIRE SEPARATE REVIEWS.
 THEY WILL NOT BE REVIEWED UNDER THIS PERMIT.
  
 4) ACCORDING TO THE ENERGY AND MECHANICAL SIZING
 CALCULATIONS THE OUTDOOR AIR FOR THE DINING ROOM SHALL
 BE 1128 CFM, THE OUTDOOR AIR FOR THE KITCHEN SHALL BE
 184 WITH THE KITCHEN TO ALSO HAVE 459 CFM OF EXHAUST.
 FBC M 403.3.1.1 AND TABLE 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-06-17 Cont ID  
Sent By medwards Date 2021-06-17 Time 08:28 Rev Time 0.00
Received By medwards Date 2021-06-17 Time 08:28 Sent To  
Notes
2021-07-20 09:05:19 
  
2021-06-17 08:29:011ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21060412
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1) PLEASE ADD A NOTE TO THE DRAWINGS STATING THAT THE
 HOOD AND ANY REFRIGERATION SHALL BE SUBMITTED AS
 SEPARATE PERMITS AND WILL REQUIRE SEPARATE REVIEWS.
 THEY WILL NOT BE REVIEWED UNDER THIS PERMIT.
  
 2) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON
 FBC 403.3.1.1 AND TABLE 403.3.1.1 AND NOT FROM THE
 ARCHITECTURAL OCCUPANT LOAD.
  
 403.3.1.1 OUTDOOR AIRFLOW RATE. THE OCCUPANT LOAD
 UTILIZED FOR DESIGN OF THE VENTILATION
 SYSTEM SHALL BE NOT LESS THAN THE NUMBER DETERMINED
 FROM THE ESTIMATED MAXIMUM OCCUPANT LOAD RATE INDICATED
 IN TABLE 403.3.1.1.
  
 3) MECHANICAL EQUIPMENT SIZING CALCULATIONS FOR RTU-2;
 PLEASE CORRECT THE OUTDOOR AIR VENTILATION AIR DATA TO
 MEET FBC 403.3.1.1 AND TABLE 403.3.1.1.
  
 4) THE MECHANICAL SYSTEMS ARE REFERENCED AS ROOF TOP
 UNITS BUT SHEET M2.2 DOES NOT SHOW THE RTU?S ON THE
 ROOF. PLEASE PROVIDE CLARIFICATION AS TO WHERE THE
 MECHANICAL EQUIPMENT WILL BE LOCATED. FBC 107.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 3 Status P Date 2021-09-16 Cont ID  
Sent By rmcphers Date 2021-09-16 Time 08:03 Rev Time 0.00
Received By rmcphers Date 2021-09-16 Time 08:00 Sent To  
Notes
2021-09-16 08:03:40BUILDING IS IN A FLOOD ZONE A WITH NO BASE FLOOD
 ELEVATION
 PROPOSED LOWEST FLOOR ELEVATION 15.50 NAVD
 CITY STORM WATER ENGINEER PROVIDED A SURROUNDING
 CONTOUR ELEVATION OF 13.00 NAVD

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status F Date 2021-08-25 Cont ID  
Sent By rmcphers Date 2021-08-25 Time 08:46 Rev Time 0.00
Received By rmcphers Date 2021-08-25 Time 08:38 Sent To  
Notes
2021-08-25 08:46:07BUILDING IS IN A FLOOD ZONE A
 PROPOSED LOWEST FLOOR ELEVATION 15.50 NAVD
 PLEASE PROVIDE A PROPOSED ELEVATION CERTIFICATE PER FBC
 WPB 107.3.5.1.1
 PLEASE PROVIDE BASE FLOOD ELEVATION DATA PREPARED IN
 ACCORDANCE WITH CURRENTLY ACCEPTED ENGINEERING
 PRACTICES. ORD: 4729-17 SEC. 18-284

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2021-07-20 Cont ID  
Sent By rmcphers Date 2021-07-20 Time 12:59 Rev Time 0.00
Received By rmcphers Date 2021-07-20 Time 12:59 Sent To  
Notes
2021-07-20 12:59:55SEE BUILDING PLAN REVIEW

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-08-28 Cont ID  
Sent By abelisle Date 2021-08-28 Time 09:17 Rev Time 0.00
Received By abelisle Date 2021-08-28 Time 06:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-07-20 Cont ID  
Sent By abelisle Date 2021-07-20 Time 15:15 Rev Time 0.00
Received By abelisle Date 2021-07-20 Time 15:10 Sent To  
Notes
2021-07-20 15:11:371ST REVIEW FBC-2020 PLUMBING
 PERMIT-21060412
 6/21/21
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020
 FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH
 EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1- PLAN PAGE A-1.0 INDICATES A GAS TANKLESS WATER
 HEATER IS TO BE INSTALLED IN THE STORAGE UTILITY ROOM.
 ON PLAN PAGE P0-1 AN ELECTRIC TANK TYPE WATER HEATER IS
 SHOWN. PLEASE CLARIFY. WPB AMENDMENTS TO THE FBC SEC.
 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS.
 2-- INTERCEPTORS SHALL BE DESIGNED AND SIZED BY THE
 GREASE INTERCEPTOR MANUFACTURE. FACTORY SIZING
 CALCULATIONS REQUIRED FROM THE MANUFACTURE FBC 2020 P
 1003.2
 3- THE PLAN PAGE A1.2 INDICATES THE GRAB BARS BEING
 MEASURED TO THE CENTER OF THE GRAB BARS. 609.4POSITION
 OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE,
 4- THE PLAN PAGE A1.2 INDICATES THE MIRRORS ARE NOT
 MEASURED 40" TO THE 603.3MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR
 5- A MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED PER
 FBCACCESS. SEC. 211.2 & FBC-PLUMBING SEC. 410.3.
 6- PLEASE PROVIDE INFORMATION ON THE BOTTOM LOADING
 WATER COOLER
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-06-21 Cont ID  
Sent By abelisle Date 2021-06-21 Time 19:39 Rev Time 0.00
Received By abelisle Date 2021-06-21 Time 19:11 Sent To  
Notes
2021-06-21 19:35:281ST REVIEW FBC-2020 PLUMBING
 PERMIT-21060412
 6/21/21
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020
 FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH
 EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1- PLAN PAGE A-1.0 INDICATES A GAS TANKLESS WATER
 HEATER IS TO BE INSTALLED IN THE STORAGE UTILITY ROOM.
 ON PLAN PAGE P0-1 AN ELECTRIC TANK TYPE WATER HEATER IS
 SHOWN. PLEASE CLARIFY. WPB AMENDMENTS TO THE FBC SEC.
 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS.
 2-- INTERCEPTORS SHALL BE DESIGNED AND SIZED BY THE
 GREASE INTERCEPTOR MANUFACTURE. FACTORY SIZING
 CALCULATIONS REQUIRED FROM THE MANUFACTURE FBC 2020 P
 1003.2
 3- THE PLAN PAGE A1.2 INDICATES THE GRAB BARS BEING
 MEASURED TO THE CENTER OF THE GRAB BARS. 609.4POSITION
 OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE,
 4- THE PLAN PAGE A1.2 INDICATES THE MIRRORS ARE NOT
 MEASURED 40" TO THE 603.3MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 2 Status P Date 2021-07-16 Cont ID  
Sent By rgathrig Date 2021-07-16 Time 12:13 Rev Time 0.00
Received By rgathrig Date 2021-07-16 Time 12:13 Sent To  
Notes
2021-07-16 12:15:08APPROVED FOR PRIVATE PROVIDER INSPECTIONS ONLY
 RICHARD GATHRIGHT

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status F Date 2021-07-13 Cont ID  
Sent By rgathrig Date 2021-07-13 Time 16:13 Rev Time 0.00
Received By rgathrig Date 2021-07-13 Time 16:13 Sent To  
Notes
2021-07-13 16:17:07PRIVATE PROVIDER REVIEW FAILED F.S. 553.791
 NOTICE TO BUILDING OFFICIAL SUBMITTED WITH PLANS FOR
 INSPECTIONS ONLY, NO OTHER REQUIRED DOCUMENTS
 SUBMITTED. 1. INSURANCE, 2. NAMES OF INSPECTORS AND
 RESUMES.
  
 RICHARD GATHRIGHT
 561 805 6679

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2021-07-20 Cont ID  
Sent By rmcphers Date 2021-07-20 Time 13:00 Rev Time 0.00
Received By rmcphers Date 2021-07-20 Time 13:00 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2021-07-14 Cont ID  
Sent By pvalenti Date 2021-07-14 Time 08:20 Rev Time 0.00
Received By pvalenti Date 2021-07-12 Time 07:54 Sent To  
Notes
2021-07-14 08:21:45 
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 A ROOFING SUB-PERMIT IS REQUIRED PRIOR TO ROOF WORK.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-08-21 Cont ID  
Sent By medwards Date 2021-08-21 Time 09:08 Rev Time 0.00
Received By medwards Date 2021-08-21 Time 09:08 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-06-17 Cont ID  
Sent By medwards Date 2021-06-17 Time 09:07 Rev Time 0.00
Received By medwards Date 2021-06-17 Time 08:29 Sent To  
Notes
2021-06-17 09:09:06THIS IS A DIGITAL SUBMITTAL FOR THE PROJECT. PLEASE
 SUBMIT DIGITALLY SIGNED CIVIL AND LANDSCAPE SHEETS AS
 THEY HAVE A WATER STAMP BUT ARE NOT SIGNED DIGITALLY.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2021-09-09 Time   Rev Time 0.00
Received By   Date 2021-09-09 Time   Sent To  
Notes
2021-09-10 16:05:54*********************ZONING NOTE**********************
  
 APPLICANT SUBMITTED A SEPARATE PERMIT FOR THE APPROVED
 LANDSCAPE PLAN (21090463).
  
 ALANA WOOTEN
 PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]
2021-09-09 12:10:28**************************************ZONING REVIEW
 FAILED************************************
  
  
 A CONDITION OF SITE PLAN APPROVAL IS THE COMCAST
 SERVICE LETTER. PLEASE PROVIDE.(SATISFIED)
  
 APPROVED PLANS HAS THE LAST REVISION DATE AS 7/1/2021.
 PLEASE SUBMIT THAT SITE PLAN. (SATISFIED)
  
 MAKE SURE THAT THE SITE PLAN AND THE ARCHITECTURAL SITE
 PLAN ARE CONSISTENT.(SATISFIED)
  
 SUBMIT A SEPARATE PERMIT FOR THE APPROVED LANDSCAPE
 PLAN. (PENDING)
  
 ALANA WOOTEN
 PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2021-08-27 Cont ID  
Sent By awooten Date 2021-08-27 Time 15:13 Rev Time 0.00
Received By awooten Date   Time   Sent To  
Notes
2021-08-27 15:13:30**************************************ZONING REVIEW
 FAILED************************************
  
  
 A CONDITION OF SITE PLAN APPROVAL IS THE COMCAST
 SERVICE LETTER. PLEASE PROVIDE.
  
 APPROVED PLANS HAS THE LAST REVISION DATE AS 7/1/2021.
 PLEASE SUBMIT THAT SITE PLAN. (SATISFIED)
  
 MAKE SURE THAT THE SITE PLAN AND THE ARCHITECTURAL SITE
 PLAN ARE CONSISTENT.
  
 SUBMIT A SEPARATE PERMIT FOR THE LANDSCAPE PLAN.
  
 ALANA WOOTEN
 PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2021-06-29 Cont ID  
Sent By awooten Date 2021-06-29 Time   Rev Time  
Received By awooten Date 2021-06-29 Time   Sent To  
Notes
2021-06-29 11:18:43**************************ZONING
 REVIEW*********************************
  
 THIS PROPERTY IS A PART OF AN INFORMAL SITE PLAN
 APPROVAL. PLEASE SUBMIT THE SITE PLAN APPROVAL LETTER
 AND ASSOCIATED APPROVED PLANS.
  
 ALANA WOOTEN
 PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]


Account Summary | Usage Policy | Privacy Policy