| 2021-07-06 10:11:31 | 04/07/21 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. ON SHEET E0.0 FOR THE CODE REFERENCE IT SATES 2017 |
| | FBC; PLEASE PROVIDE THE CORRECT AND CURRENT GAS CODE |
| | CYCLE PER THE WPB AMENDMENTS TO THE FBC SEC. 102.3 |
| | APPLICATION OF REFERENCES. |
| | |
| | 2. GAS RISER DIAGRAM REQUIRED PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.3.5.1.5 (9) COMMERCIAL GAS. |
| | |
| | A. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| | PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| | CORRUGATED STAINLESS-STEEL TUBING (IF APPLICABLE) FOR |
| | EACH PIPE AND CLEARLY SHOWS THE LENGTH OF ALL CUT |
| | SECTIONS OF PIPE PER 2020 FBC FG SECS. 402.4.1, |
| | 402.4.2. |
| | |
| | B. TYPE OF GAS (LP OR NATURAL) PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | C. PLEASE LABEL AND SHOW ALL SHUT-OFF, DRIP LEG, AND |
| | UNIONS IN FRONT OF REGULATOR 1? OF EITHER SIDE PER THE |
| | 2020 FBC RES. SEC G2421.2. |
| | |
| | D. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE PLAN PER THE 2020 FBC FG SEC. 402.2. |
| | |
| | E. PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1' OF |
| | EITHER SIDE PER THE 2020 FBC FG SEC 410.2. |
| | |
| | F. PLEASE LABEL THE SHUTOFF VALVE ON GAS ISOMERIC PER |
| | THE 2020 FBC FG SEC. 409.5. |
| | |
| | 3. A SUB GAS PERMIT IS REQUIRED BY A LICENSED |
| | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 105.1. |
| | |
| | 4. SUBMIT SIZING TABLE USED IN THE DESIGN FOR THE GAS |
| | SYSTEM OR PLACE A NOTE ON BOTH SETS OF PLANS LISTING |
| | THE SIZING TABLES FROM GAS CODES OR ANOTHER STANDARD |
| | THAT WERE USED IN THE DESIGN OF THIS SYSTEM PER THE |
| | 2017 FBC FG SEC. 402.3 OR 2017 FBC RES. SEC. G2413.3. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |