| 2021-06-17 10:40:58 | 06/17/21 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | |
| | 1. GAS RISER DIAGRAM REQUIRED PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL GAS. PLEASE |
| | CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE |
| | PER 2020 FBC RES. SECS. G2413.4.1, G2413.4.2. THE |
| | EXISTING GAS SYSTEM IS NOTED TO BE 949 BTU'S PLEASE |
| | SHOW EXISTING LIST OF BTU?S TO EACH EQUIPMENT. LIST THE |
| | BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON |
| | THE SYSTEM. REFER TO THE 2020 FBC RES. SEC. G2413. |
| | |
| | 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| | PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| | CORRUGATED STAINLESS-STEEL TUBING (IF APPLICABLE) FOR |
| | EACH PIPE SIZE PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 3. PLEASE SHOW THE GENERATOR ON SURVEY AND DISTANCE |
| | THAT IS REQUIRED FROM THE HOUSE, FIVE, THE PROPERTY |
| | LINE, EXHAUST FROM ANY OPENING PER THE MANUFACTURES |
| | SPECIFICATION INSTRUCTIONS. |
| | |
| | 4. PLEASE PROVIDE THE SIGNATURE OF ALL INFORMATION, |
| | DRAWINGS, SPECIFICATIONS, AND ACCOMPANYING DATA THAT |
| | SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN PER THE WPB AMENDMENTS TO |
| | THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 5. PLEASE SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR |
| | THE PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | BUILDING'S EXTERIOR SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION PER THE 2020 FBC RES. SEC. G2421.1. |
| | |
| | 6. PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1 FOOT |
| | OF EITHER SIDE PER THE 2020 FBC RES. SEC G2421.2. |
| | |
| | 7. PLEASE SHOW DRIP LEG AD SHUTOFF VALVES ON GAS |
| | ISOMETRIC PER THE 2020 FBC RES. SEC. G2419.2. |
| | |
| | 8. PLEASE SUBMIT MANUFACTURER'S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR GENERATOR EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH 2020 FBC RES. SEC. G2408.1. |
| | |
| | 9. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| | INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| | SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2020 |
| | FBC RES. SEC. G2413.2 AND G2404.3. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |