Plan Review Details - Permit 21060214
Plan Review Stops For Permit 21060214
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-06-22 Cont ID  
Sent By jleahy Date 2021-06-22 Time 13:49 Rev Time 0.00
Received By jleahy Date 2021-06-22 Time 13:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-06-03 Cont ID  
Sent By equinone Date 2021-06-03 Time 13:38 Rev Time 0.00
Received By equinone Date 2021-06-03 Time 11:44 Sent To  
Notes
2021-06-03 13:39:37CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW:
  
 1) NO ELECTRICAL PLANS PROVIDED. PLEASE PROVIDE
 ELECTRICAL PLANS FOR EQUIPMENT BEING INSTALLED. FBC 107
  
 ENRIQUE QUINONEZ PE
 ELECTRICAL PLANS EXAMINER
 DEVELOPMENT SERVICES
 CITY OF WEST PAM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6746.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2021-06-23 Time   Rev Time 0.00
Received By aoliver Date 2021-06-18 Time 09:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-06-04 Time   Rev Time 0.00
Received By ccarvaja Date 2021-06-02 Time 16:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-06-21 Cont ID  
Sent By medwards Date 2021-06-21 Time 11:27 Rev Time 0.00
Received By medwards Date 2021-06-21 Time 11:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-06-03 Cont ID  
Sent By medwards Date 2021-06-03 Time 13:14 Rev Time 0.00
Received By medwards Date 2021-06-03 Time 12:54 Sent To  
Notes
2021-06-03 13:14:541ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21060214
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE REQUIRED INFORMATION FROM FBC M
 1102.1 (1-6)
 1102.1 GENERAL. THE SYSTEM CLASSIFICATION, ALLOWABLE
 REFRIGERANTS, MAXIMUM QUANTITY, ENCLOSURE REQUIREMENTS,
 LOCATION LIMITATIONS, AND FIELD PRESSURE TEST
 REQUIREMENTS SHALL BE DETERMINED AS FOLLOWS:
 1. DETERMINE THE REFRIGERATION SYSTEM'S CLASSIFICATION,
 IN ACCORDANCE WITH SECTION 1103.3.
 2. DETERMINE THE REFRIGERANT CLASSIFICATION IN
 ACCORDANCE WITH SECTION 1103.1.
 3. DETERMINE THE MAXIMUM ALLOWABLE QUANTITY OF
 REFRIGERANT IN ACCORDANCE WITH SECTION 1104, BASED ON
 TYPE OF
 REFRIGERANT, SYSTEM CLASSIFICATION AND OCCUPANCY.
 4. DETERMINE THE SYSTEM ENCLOSURE REQUIREMENTS IN
 ACCORDANCE WITH SECTION 1104.
 5. REFRIGERATION EQUIPMENT AND APPLIANCE LOCATION AND
 INSTALLATION SHALL BE SUBJECT TO THE LIMITATIONS OF
 CHAPTER 3.
 6. NON FACTORY-TESTED, FIELD-ERECTED EQUIPMENT AND
 APPLIANCES SHALL BE PRESSURE TESTED IN ACCORDANCE WITH
 SECTION
 1108.
 2) PLEASE PROVIDE THE CERTIFICATE OF TEST FOR ALL
 SYSTEMS CONTAINING 55 POUNDS OR MORE OF REFRIGERANT TO
 THE INSPECTOR. FBC M 1108.4
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-06-23 Cont ID  
Sent By ccole Date 2021-06-23 Time 07:42 Rev Time 0.00
Received By ccole Date 2021-06-23 Time 07:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-06-04 Cont ID  
Sent By ccole Date 2021-06-04 Time 10:53 Rev Time 0.00
Received By ccole Date 2021-06-04 Time 10:53 Sent To  
Notes
2021-06-04 10:53:231ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21060214
 6/4/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1.0: THE CONDENSATE FROM THE REFRIGERATION
 SYSTEMS SHALL NOT DRAIN INTO THE SANITARY SYSTEM IN
 ACCORDANCE WITH SEC. 90-126 CITY OF WEST PALM BEACH
 CODE OF ORDINANCES. PLEASE PROVIDE AN APPROVED PLACE OF
 DISPOSAL SUCH AS THE STORM DRAIN OR A DRYWELL- SECTION
 314.2.1 FBC P. THIS ISSUE WAS ALSO ADDRESSED UNDER
 REVISION 21050388. PLEASE CORRECT THE PLANS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-06-21 Cont ID  
Sent By medwards Date 2021-06-21 Time 11:29 Rev Time 0.00
Received By medwards Date 2021-06-21 Time 11:29 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-06-03 Cont ID  
Sent By medwards Date 2021-06-03 Time 13:33 Rev Time 0.00
Received By medwards Date 2021-06-03 Time 13:33 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved