Plan Review Details - Permit 21060130
Plan Review Stops For Permit 21060130
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-07-13 Cont ID  
Sent By pvalenti Date 2021-07-13 Time 09:09 Rev Time 0.00
Received By pvalenti Date 2021-07-13 Time 09:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-07-09 Cont ID  
Sent By pvalenti Date 2021-07-09 Time 13:01 Rev Time 0.00
Received By pvalenti Date 2021-07-09 Time 13:01 Sent To  
Notes
2021-07-09 13:34:17****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW DENIED.
  
 FBC B 107, PLEASE CORRECT AND/OR CLARIFY THE FOLLOWING
 ITEMS:
  
 1) SHEET A1 (APPLICABLE CODES AND BUILDING
 CLASSIFICATION), OCCUPANCY IS INDICATING GROUP R-2. IT
 APPEARS THAT THIS SHOULD BE R-3.
 2) SHEET A1 (APPLICABLE CODES AND BUILDING
 CLASSIFICATION), CONSTRUCTION TYPE INDICATING TYPE 1.
 IT APPEARS THAT THIS SHOULD BE TYPE 5.
 3) SHEET A1 (APPLICABLE CODES AND BUILDING
 CLASSIFICATION), THE BROWARD COUNTY CODE AMENDMENTS ARE
 REFERENCED. THIS NEEDS TO BE CHANGED TO WEEST PALM
 BEACH CODE AMENDMENTS.
 4) SHEET A1 (SCOPE OF WORK), INDICATES A NEW ROOF
 SECTION BETWEEN MAIN HOUSE AND DETACHED GARAGE/BEDROOM
 CONVERSION. THERE ARE NO BUILDING PLANS TO CREATE THIS
 BREEZEWAY TYPE ROOF STRUCTURE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-07-02 Cont ID  
Sent By pvalenti Date 2021-07-02 Time 15:11 Rev Time 0.00
Received By pvalenti Date 2021-07-02 Time 15:05 Sent To  
Notes
2021-07-02 15:27:19****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW DENIED:
  
 1) FBC B 107.2.1, PLEASE PROVIDE, ON SHEET A-2, THE R
 VALUE FOR WALL INSULATION.
 2) FBC EB 811.1, PLEASE PROVIDE ENERGY CALCULATIONS
 COMPLETED ON REQUIRED FORM, SUCH AS FORM #405.
 3) FBC B 107.2.1, P-LEASE PROVIDE THE WINDOW/DOOR
 PRODUCT APPROVALS.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-07-15 Cont ID  
Sent By ppetty Date 2021-07-15 Time 12:50 Rev Time 0.00
Received By ppetty Date 2021-07-15 Time 12:49 Sent To  
Notes
2021-07-15 12:50:21CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: PROVISO, SEE COMMENTS BELOW.
  
 4.A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A
 BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE
 DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY ONE
 FEEDER OR BRANCH CIRCUIT. NEC 225.30
 5.A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE
 ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND
 CONNECTED TOGETHER. PROVIDE DETAILS ON PLAN OF
 GROUNDING ELECTRODE SYSTEM AND WIRING. NEC 250.32; FBC
 RE E3607.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 PHIL PETTY
 CHIEF ELECTRICAL INSPECTOR , ELECTRICAL PLANS EXAMINER
  
 561-805-6742
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-07-13 Cont ID  
Sent By ppetty Date 2021-07-13 Time 08:42 Rev Time 0.00
Received By ppetty Date 2021-07-13 Time 08:42 Sent To  
Notes
2021-07-13 09:00:31CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1.MINI SPLIT NOT ON ELECTRICAL PLAN
 2.PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED PER
 CODE. FBC RE R314.3, R315.1; WPB FBC 107.2.1
 3.PROVIDE WIRE AND BREAKER SIZE AND DISCONECT LOCATION
 4.A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A
 BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE
 DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY ONE
 FEEDER OR BRANCH CIRCUIT. NEC 225.30
 5.A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE
 ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND
 CONNECTED TOGETHER. PROVIDE DETAILS ON PLAN OF
 GROUNDING ELECTRODE SYSTEM AND WIRING. NEC 250.32; FBC
 RE E3607.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 PHIL PETTY
 CHIEF ELECTRICAL INSPECTOR , ELECTRICAL PLANS EXAMINER
  
 561-805-6742
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-06-09 Cont ID  
Sent By fgiaquin Date 2021-06-09 Time 21:16 Rev Time 0.00
Received By fgiaquin Date 2021-06-09 Time 19:02 Sent To  
Notes
2021-06-09 21:14:12ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. IS THIS STRUCTURE A DETACHED GARAGE? IF SO DOES THE
 STRUCTURE ALREADY HAVE ELECTRIC RAN TO IT? FBC 107.2.1
  
 2. PROVIDE RISER DIAGRAM OF EXISTING RESIDENTIAL
 SERVICE. NEC 220.16A1&2, 220.12, 220.14
 FBC RE 3602.1, FBC RE 3602.2, FBC 107.2.1
  
 3. IS THIS TWO BEDROOMS OR ONE. ON PLAN TWO BEDROOMS
 ARE SHOWN AND NO RECEPTACLES OR LIGHTING IS SHOWN IN
 BEDROOM WEST OF BATHROOM. MISLABELED PERHAPS IT IS A
 CLOSET? FBC 107.2.1
  
 4. PROVIDE LOAD CALCULATION TO INCLUDE NEW AND EXISTING
 LOADS. NEC 220
  
  
  
  
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-07-15 Cont ID  
Sent By ppetty Date 2021-07-15 Time 12:51 Rev Time 0.00
Received By ppetty Date 2021-07-15 Time 11:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-07-15 Cont ID  
Sent By aoliver Date 2021-07-15 Time 11:34 Rev Time 0.00
Received By pvalenti Date 2021-07-08 Time 07:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-07-02 Cont ID  
Sent By pvalenti Date 2021-07-02 Time 15:35 Rev Time 0.00
Received By pvalenti Date 2021-06-02 Time 15:05 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2021-07-20 Cont ID  
Sent By pvalenti Date 2021-07-20 Time 16:30 Rev Time 0.00
Received By lmarchan Date 2021-07-19 Time 11:13 Sent To  
Notes
2021-07-20 16:30:48RECEIPT MU-2021-35256 - $4304.62 PAID
2021-07-19 11:14:087/19/21 EMAILED IMPACT FOR REVIEW-AO

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2021-07-15 Cont ID  
Sent By pvalenti Date 2021-07-15 Time 13:18 Rev Time 0.00
Received By pvalenti Date 2021-07-15 Time 13:18 Sent To  
Notes
2021-07-15 13:19:53****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  
 IMPACT FEES - PAPER SUBMITTALS
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-07-02 Cont ID  
Sent By pvalenti Date 2021-07-02 Time 15:06 Rev Time 0.00
Received By pvalenti Date 2021-07-02 Time 15:05 Sent To  
Notes
2021-07-02 15:07:38IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  
 IMPACT FEES - PAPER SUBMITTALS
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-07-12 Cont ID  
Sent By hmoser Date 2021-07-12 Time 13:47 Rev Time 0.00
Received By hmoser Date 2021-07-12 Time 12:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-06-11 Cont ID  
Sent By medwards Date 2021-06-11 Time 13:11 Rev Time 0.00
Received By medwards Date 2021-06-11 Time 13:11 Sent To  
Notes
2021-06-11 13:11:351ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21060130
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE ENERGY CALCULATIONS FOR THIS
 EDITION. FBC EC R401
  
 2) PLEASE PROVIDE A MECHANICAL DRAWING SHOWING THE
 MECHANICAL WORK FOR THIS PROJECT. FBC 107.2.1
  
 3) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FOR THE CONDITIONING OF THE NEW SPACE. FBC
 EC R403.2.1
  
 4) PLEASE SHOW THE VENTILATION FOR THE NEW BATHROOM.
 FBC RES R303.3
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-06-08 Cont ID  
Sent By abelisle Date 2021-06-08 Time 19:53 Rev Time 0.00
Received By abelisle Date 2021-06-08 Time 19:42 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-07-15 Cont ID  
Sent By ppetty Date 2021-07-15 Time 12:50 Rev Time 0.00
Received By ppetty Date 2021-07-15 Time 12:50 Sent To  
Notes
2021-07-15 15:04:17ORIGINAL SIGNED AND SEALED PAPER DRAWING ROUTED TO
 STORAGE.ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-07-08 Cont ID  
Sent By medwards Date 2021-07-08 Time 15:30 Rev Time 0.00
Received By medwards Date 2021-07-08 Time 15:27 Sent To  
Notes
2021-07-08 15:30:34ORIGINAL SIGNED AND SEALED PAPER DOCUMENTS ROUTED TO
 STORAGE.ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-06-02 Cont ID  
Sent By medwards Date 2021-06-02 Time 17:02 Rev Time 0.00
Received By medwards Date 2021-06-02 Time 17:02 Sent To  
Notes
2021-06-02 17:03:00ORIGINAL SIGNED AND SEALED PAPER DRAWINGS ROUTED TO
 STORAGE.ME

Review Stop Z ZONING
Rev No 1 Status P Date 2021-07-15 Cont ID  
Sent By rthermid Date 2021-07-15 Time   Rev Time 0.00
Received By rthermid Date 2021-07-15 Time   Sent To I
Notes
***NONE***