| 2021-06-19 11:19:32 | PLAN REVIEW BUILDING |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER PX3169 1&2 FAMILY - SFP306 |
| | INSPECTOR BN4338 |
| | BUILDING OFFICIAL BU1635 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | 2017 NEC |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. PROVIDE SCHEDULE FOR INSTALLATION OF OPENING |
| | PROTECTIVE DEVICES OR ASSEMBLIES. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | NOTICE: I HAVE UPLOADED THE CITY'S SHUTTER SCHEDULE FOR |
| | YOUR REVIEW AND USE. |
| | |
| | 2. PROVIDE DESIGN PRESSURES FOR EACH OPENING, |
| | R301.2.1 WIND DESIGN CRITERIA. |
| | BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN |
| | ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING |
| | THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED |
| | FROM FIGURE R301.2(4). |
| | |
| | PROVIDE SCHEDULE WITH THE FOLLOWING INFORMATION. |
| | 1. LOCATION REFERENCE TO OPENING NUMBER ON PLAN. |
| | 2. DEVICE TYPE WINDOW/DOOR/SHUTTER |
| | 3. ROUGH OPENING WXH (AREA SF) |
| | 4. DESIGN PRESSURES TABLE R301.1.(2) OR ASCE 7-16 |
| | 5. NOA OR FL NUMBER |
| | 6. MAX DESIGN PRESSURE FROM NOA OR FL |
| | 7. IDENTIFY EGRESS OPENINGS |
| | |
| | NOTICE: SEPERATE SHUTTER AND DOOR PRODUCT APPROVALS. |
| | UPLOAD SEPERATELY TO PROJECT DOX. USE APPROPRIATE |
| | NAMING CONVENTION. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |
| | |
| | |
| | |