Plan Review Details - Permit 21060066
Plan Review Stops For Permit 21060066
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-08-18 Cont ID  
Sent By pvalenti Date 2021-08-18 Time 08:50 Rev Time 0.00
Received By pvalenti Date 2021-08-18 Time 08:37 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-06-15 Cont ID  
Sent By jwitmer Date 2021-06-15 Time 17:05 Rev Time 0.00
Received By jwitmer Date 2021-06-15 Time 16:42 Sent To  
Notes
2021-06-15 17:05:03COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-08-18 Cont ID  
Sent By pvalenti Date 2021-08-18 Time 10:27 Rev Time 0.00
Received By pvalenti Date 2021-08-18 Time 08:54 Sent To  
Notes
2021-08-18 10:29:46 
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW APPROVED WITH PROVISO:
  
 1) SAME DRAIN OPENING IS TO BE USED FOR CHANGE AT TUB
 TO SINK.
 2) PROFLEX SUPER SIM 90 IS TO BE USED AS FLOORING
 UNDERLAYMENT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-06-15 Cont ID  
Sent By jwitmer Date 2021-06-15 Time 17:27 Rev Time 0.00
Received By jwitmer Date 2021-06-15 Time 16:43 Sent To  
Notes
2021-06-15 17:23:51WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21060066
 ADD: 1701 S. FLAGLER DR. # 503
 CONT: CONRAD CONSTRUCTION CGC1521014/ FL01684
 TEL: 561-512-7637
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JUNE 15, 2021
 ACTION: DENIED
  
 1) CERTIFICATION BY CONTRACTOR. 107.3.4.3. THE
 CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET OF
 PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF
 THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND
 LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN AND
 PLANS DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
  
 2) THE SUBMITTED TEST REPORTS FOR PROFLEX MSC MEGA
 SOUND CONTROL. TO DATE WE HAVE NOT APPROVED THIS
 PRODUCT AND PLACED IT ON F DRIVE AT CITY HALL. THE
 SUBMITTED TEST REPORTS ARE FOR AN 8 INCH CONCRETE SLAB.
 THE TEST REPORT FOR THE IIC RATING STATES ON THE COVER
 IT IS WITH A SUSPENDED CEILING STUFFED WITH 3 ? INCH
 INSULATION. THE OTHER IS FOR STC RATING AND STILL A 8
 INCH CONCRETE SLAB. FLOOR INSULATION (FBC-B 2020) FOR
 TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL NEED
 TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 2A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 2B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 2C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL
 723.
  
 3) THE SHOWER PAN DETAIL STATES ? INCH WATERPROOF
 BOARD, PLEASE SHOW COMPLIANCE WITH 2020 FBC-B 2509.2
 BASE FOR TILE. MATERIALS USED AS A BASE FOR WALL TILE
 IN TUB AND SHOWER AREAS AND WALLS AND CEILING PANELS IN
 SHOWER AREAS SHALL BE OF MATERIALS LISTED IN TABLE
 2509.2 AND INSTALLED IN ACCORDANCE WITH MANUFACTURER?S
 RECOMMENDATIONS. WATER RESISTANT GYPSUM BACKING BOARD
 SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET
 COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH
 GA-216 OR ASTM C840 AND THE MANUFACTURE?S
 RECOMMENDATIONS.
  
 4) POST TENSION SLAB/ NEW HOLES. THE PLAN IS SILENT AS
 IF THE LOCATION OF THE EXISTING TUB DRAIN IS GOING TO
 BE REUSED IN THE SAME LOCATION. IF NOT, THEN THE FLOOR
 SLAB WILL NEED TO BE X-RAYED TO FIND THE POST TENSION
 CHORD LOCATIONS. 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 5) THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL
 ASSEMBLIES). IF A NEW FLOOR PENETRATION IS MADE FOR THE
 FUTURE SHOWER DRAIN, THEN YOU NEED TO SHOW COMPLIANCE
 WITH THE 2020 FBC-B SECTION 714.5.1.2.
 THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL
 ASSEMBLIES). THROUGH PENETRATIONS SHALL BE PROTECTED BY
 A THROUGH PENETRATION FIRESTOP SYSTEM INSTALLED IN
 ACCORDANCE WITH ASTM E814 OR UL 1479. THE SYSTEM SHALL
 HAVE AN F RATING / T RATING OF NOT LESS THAN 1 HOUR BUT
 NOT LESS THAN THE REQUIRED RATING OF THE FLOOR
 PENETRATED.
  
 6) 2020 FBC-B SHOWERS & TUBS 1210.3. SHOWER
 COMPARTMENTS AND BATHTUBS WITH INSTALLED SHOWER HEADS
 SHALL BE FINISHED WITH A NONABSORBENT SURFACE TO A
 HEIGHT NOT LESS THAN 72 INCHES ABOVE THE DRAIN INLET.
  
 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-06-11 Cont ID  
Sent By fgiaquin Date 2021-06-11 Time 22:36 Rev Time 0.00
Received By fgiaquin Date 2021-06-11 Time 21:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-06-03 Cont ID  
Sent By cwalker Date 2021-06-03 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-08-20 Cont ID  
Sent By medwards Date 2021-08-20 Time 13:40 Rev Time 0.00
Received By medwards Date 2021-08-09 Time 15:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-06-15 Time 17:28 Rev Time 0.00
Received By cdecoeur Date 2021-06-02 Time 05:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-08-20 Cont ID  
Sent By medwards Date 2021-08-20 Time 13:39 Rev Time 0.00
Received By medwards Date 2021-08-20 Time 13:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-06-14 Cont ID  
Sent By medwards Date 2021-06-14 Time 16:50 Rev Time 0.00
Received By medwards Date 2021-06-14 Time 16:50 Sent To  
Notes
2021-06-14 16:50:531ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21060066
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE COMPLETED LIKE FOR LIKE A/C
 CHANGE OUT FORM.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-08-19 Cont ID  
Sent By pvalenti Date 2021-08-19 Time 12:55 Rev Time 0.00
Received By jesmith Date 2022-02-01 Time 15:07 Sent To  
Notes
2021-08-19 12:56:12PLUMBING COMMENTS: APPROVED
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 NOTE: PLEASE NOTE THAT WHEN SCANNED DRAWINGS ARE
 SUBMITTED WITH THE DESIGN PROFESSIONAL'S OFFICIAL SEAL
 IN ACCORDANCE WITH WPB FBC 107.1, A PAPER PLAN WITH
 ORIGINAL SEAL SHALL BE PROVIDED TO THE BUILDING
 DEPARTMENT FOR HARD RECORD FILE PRIOR TO ISSUANCE OF A
 PERMIT.
  
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21060066 1701 S FLAGLER DR # 503

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-06-15 Cont ID  
Sent By jesmith Date 2021-06-15 Time 13:26 Rev Time 0.00
Received By jesmith Date 2021-06-15 Time 10:08 Sent To  
Notes
2021-06-15 13:23:03CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21060066 1701 S FLAGLER DR # 503
  
 NOTE: UNIT IS ON THE 5TH FLOOR OF 19 FLOOR CONDOMINIUM.
 NOTE: PLEASE NOTE THAT WHEN SCANNED DRAWINGS ARE
 SUBMITTED WITH CONTRACTOR'S PRINTED NAME, SIGNATURE AND
 LICENSE NUMBER IN ACCORDANCE WITH WPB FBC 107.3.4.3, A
 PAPER PLAN WITH WET SIGNATURE SHALL BE PROVIDED TO THE
 BUILDING DEPARTMENT FOR HARD RECORD FILE PRIOR TO
 ISSUANCE OF A PERMIT.
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 1.AS THE PLANS ARE NOT SIGNED AND SEALED BY A
 PROFESSIONAL ENGINEER OR ARCHITECT, A SEPARATE PLUMBING
 PLAN IN ACCORDANCE WITH WPB FBC 107.3.4.3 SHALL BEAR
 THE PRINTED NAME, THE SIGNATURE AND THE CERTIFICATION
 NUMBER OF THE DESIGNER WHO SHALL BE A CONTRACTOR
 LICENSED IN THE PLUMBING TRADE. ADDITIONALLY, THE
 SHOWER PAN DETAIL SHALL BEAR THE PRINTED NAME, THE
 SIGNATURE AND THE CERTIFICATION NUMBER OF THE DESIGNER
 WHO SHALL BE A CONTRACTOR LICENSED IN THE PLUMBING
 TRADE.
  
 2.PER WPB FBC 104.1, A PLUMBING SUB-PERMIT APPLICATION
 SHALL BE SUBMITTED FOR THIS PROJECT BY A LICENSED
 PLUMBING CONTRACTOR.
  
 3.SCOPE OF WORK INCLUDES REPLACEMENT OF EXISTING WATER
 HEATER WITH LIKE FOR LIKE. PER WPB FBC 107.2.1, PROVIDE
 THE FOLLOWING:
 A) LOCATION OF WATER HEATER
 B) DESCRIPTION (MANUFACTURER, MODEL #, CAPACITY (GPM
 FOR TANKLESS), ELECTRICAL OR GAS CHARACTERISTICS) OF
 THE EXISTING WATER HEATER.
 C) NEW WATER HEATER SCHEDULE; MANUFACTURER, MODEL #,
 CAPACITY (GPM FOR TANKLESS), ELECTRICAL OR GAS
 CHARACTERISTICS.
 D) WATER HEATER DETAIL- PROVIDE DETAIL OF WATER HEATER
 SHOWING HEATER W/STORAGE CAPACITY, PIPING INCLUDING CW,
 HW, VALVES (INCLUDING VACUUM RELIEF VALVE IF APPLICABLE
 FBC PL 504.2) , THERMAL EXPANSION CONTROL DEVICE
 (INCLUDING SIZE), T&P DISCHARGE (INCLUDING TERMINATION)
 AND WATER HEATER PAN AND DRAIN (INCLUDING TERMINATION)
 PER WPB FPC 107.2.1; COMPLY WITH FBC PL 607.3, 503.1,
 504.1, 504.4, 504.4.1, 504.5, 504.6, 504.7, 504.7.1 AND
 504.7.2. IT IS NOTED THAT PER FBC PL 504.7.2 A PAN IS
 NOT REQUIRED FOR A REPLACEMENT WATER HEATER IF A PAN
 WAS NOT PREVIOUSLY INSTALLED.
  
 4.PER WPB FBC 107.2.1, PROVIDE A RISER DIAGRAM AND PLAN
 VIEW SHOWING HOW THE TUB DRAIN IS TO BE CONVERTED TO A
 VENTED LAVATORY DRAIN. PLEASE NOTE THAT AIR ADMITTANCE
 VALVES INSTALLED MORE THAN FOUR BRANCH INTERVALS BELOW
 THE TOP OF THE STACK ARE SUBJECT TO STRINGENT
 RESTRICTIONS AS NOTED IN FBC PL 918.3.1.
  
 5.PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL WITH
 A NOTE STATING, "HORIZONTAL PIPE SHALL BE SUPPORTED IN
 ACCORDANCE WITH FBC PL TABLE 308.5.", FOR ANY NEW
 PIPING.
  
 6.PER WPB FBC 107.2.1, PROVIDE FIRE RATED FLOOR
 DETAIL(S) FOR NEW FLOOR PENETRATIONS AND FOR THE
 SAFEING OF THE ABANDONED TUB BOX. COMPLY WITH FBC
 CHAPTER 7. PER FBC PL 315.1, ANNULAR SPACES CREATED BY
 PIPES PENETRATING FIRE-RESISTANCE-RATED ASSEMBLIES OR
 MEMBRANES OF SUCH ASSEMBLIES SHALL BE SEALED OR CLOSED
 IN ACCORDANCE WITH SECTION 714 OF THE FLORIDA BUILDING
 CODE, BUILDING.
  
 7.PER WPB FBC 107.2.1, PROVIDE DIMENSIONS IN BATHROOMS
 (INCLUDE NEW SHOWER DIMENSIONS). PROVIDE CENTERLINE
 DIMENSION FROM WATER CLOSET TO ADJACENT SHOWER
 ENCLOSURE. PER FBC PL 406.3.1, A WATER CLOSET, URINAL,
 LAVATORY OR BIDET SHALL NOT BE SET CLOSER THAN 15
 INCHES (381 MM) FROM ITS CENTER TO ANY SIDE WALL,
 PARTITION, VANITY OR OTHER OBSTRUCTION.405.3.1
  
 8.THE PLANS ARE UNCLEAR AS TO WHAT IS TO BE DONE WITH
 THE BATHROOM WALLS AT THE SHOWERS. PER FBC PL 421.4.1,
 BATHTUB FLOORS, SHOWER FLOORS, WALL AREAS ABOVE
 BUILT-IN TUBS THAT HAVE INSTALLED SHOWER HEADS AND
 WALLS IN SHOWER COMPARTMENTS SHALL BE CONSTRUCTED OF
 SMOOTH, CORROSION-RESISTANT AND NONABSORBENT WATERPROOF
 MATERIALS. WALL MATERIALS SHALL EXTEND TO A HEIGHT OF
 NOT LESS THAN 6 FEET (1829 MM) ABOVE THE ROOM FLOOR
 LEVEL, AND NOT LESS THAN 70 INCHES (1778 MM) ABOVE THE
 DRAIN OF THE TUB OR SHOWER. SUCH WALLS SHALL FORM A
 WATER-TIGHT JOINT WITH EACH OTHER AND WITH EITHER THE
 TUB OR SHOWER FLOOR. PER WPB FBC 107.2.1, CLARIFY.
  
 9.THE PLANS ARE UNCLEAR AS TO WHAT IS TO BE DONE WITH
 THE MASTER BATH SHOWER. IS THE FLOOR TILE IN THE SHOWER
 TO BE REPLACED? IF SO, A TEST AND INSPECTION OF THE
 SHOWER PAN INSTALLATION IS REQUIRED AND THE PAN SHALL
 COMPLY WITH THE PROVISIONS OF FBC PL 421.5.2. PER WPB
 FBC 107.2.1, CLARIFY ON THE PLANS.
  
 10.THE ELECTRICAL PLAN SEEMS TO BE REPRESENTATIVE OF
 EXISTING CONDITIONS. IF SO, THE WATER CLOSET APPEARS TO
 BE RELOCATED FROM ITS' ORIGINAL LOCATION. PER WPB FBC
 107.2.1, CLARIFY. PROVIDE DRAWINGS SHOWING MODIFICATION
 IF APPLICABLE..
  
 11.WATER HAMMER ARRESTORS ARE REQUIRED AT WATER
 SUPPLIES TO DISHWASHER AND ICE LINE PER FPC PL 604.9.
  
 12.PER FBC PL 409.4, THE WASTE CONNECTION OF A
 RESIDENTIAL DISHWASHER SHALL CONNECT DIRECTLY TO A WYE
 BRANCH FITTING ON THE TAILPIECE OF THE KITCHEN SINK,
 DIRECTLY TO THE DISHWASHER CONNECTION OF A FOOD WASTE
 DISPOSER, OR THROUGH AN AIR BREAK TO A STANDPIPE. THE
 WASTE LINE OF A RESIDENTIAL DISHWASHER SHALL RISE AND
 BE SECURELY FASTENED TO THE UNDERSIDE OF THE SINK RIM
 OR COUNTER TOP.
  
 13.A ROUGH IN PLUMBING INSPECTION IS REQUIRED FOR
 SHOWER VALVE REPLACEMENT. NEW SHOWER CONTROL VALVES TO
 COMPLY WITH FBC PL 412.3, WHICH SHALL BE PRESSURE
 BALANCED PB, THERMOSTATIC MIXING (TM) OR COMBINATION
 PB/TM VALVE TYPES WITH HIGH TEMPERATURE LIMITING STOP
 THAT CONFORM TO THE REQUIREMENTS OF ASSE 1016/ASME
 A112.1016/CSA B125.16 OR ASME A112.18.1/CSA B125.1 AND
 SHALL BE INSTALLED AT THE POINT OF USE.
  
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A
 RESPONSE NARRATIVE ADDRESSING THE GAS/PLUMBING COMMENTS
 FROM THE PRIOR REVIEW.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21060066 1701 S FLAGLER DR # 503

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2021-09-14 17:31:55PRIVATE PROVIDER INSPECTIONS ONLY
 TEW AND TAYLOR
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-08-26 Cont ID  
Sent By jgomez Date 2021-08-26 Time 11:15 Rev Time 0.00
Received By jgomez Date 2021-08-26 Time 11:11 Sent To  
Notes
2021-08-26 11:16:10DRAWING S-1 WAS SUBMITTED WITH THE ENGINEER'S ORIGINAL
 SEAL AND SIGNATURE.
 SENT TO STORAGE. JG.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-08-09 Cont ID  
Sent By lcrespo Date 2021-08-09 Time 16:12 Rev Time 0.00
Received By lcrespo Date 2021-08-09 Time 16:12 Sent To  
Notes
2021-08-09 16:21:28P-1 AND P-2 HAVE BEEN APPORVED.
  
 S-1 DID NOT HAVE A SIGNITURE PER THE REQIRMENTS BELOW;
  
 SIGNED AND SEALED DRAWINGS NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER TO BE
 USED IN ELECTRONIC PLAN REVIEW. THE ORIGINAL DROOPED
 OFF SIGNED AND SEALED DOCUMENT DID NOT HAVE A WET SEAL.
  
 PLANS SUBMITTED IN PAPER FORM ARE REQUIRED TO BE SEALED
 AND WET SIGNED BY THE DESIGN PROFESSIONAL.
 61G15-23.001.
  
 IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF THE ORIGINAL SIGNED AND
 SEALED DOCUMENT ALONG WITH A "PLAN REVIEW REQUEST FORM"
 EXPLAINING THE REASON FOR SUBMITTING THE DOCUMENT OR
 DRAWINGS. THE PLAN REVIEW REQUEST FORM CAN BE OBTAINED
 BY EMAILING [email protected] AND ASKING FOR THE FORM.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-06-15 Cont ID  
Sent By jwitmer Date 2021-06-15 Time 17:27 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2021-06-15 17:22:23CERTIFICATION BY CONTRACTOR. 107.3.4.3. THE CONTRACTOR
 (QUALIFIER) THAT CREATED / DREW THE SET OF PLANS WILL
 NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS.
 PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE
 NUMBER FOR THE TRADE YOU ARE LICENSED IN AND PLANS
 DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
  