| 2021-06-15 13:23:03 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 21060066 1701 S FLAGLER DR # 503 |
| | |
| | NOTE: UNIT IS ON THE 5TH FLOOR OF 19 FLOOR CONDOMINIUM. |
| | NOTE: PLEASE NOTE THAT WHEN SCANNED DRAWINGS ARE |
| | SUBMITTED WITH CONTRACTOR'S PRINTED NAME, SIGNATURE AND |
| | LICENSE NUMBER IN ACCORDANCE WITH WPB FBC 107.3.4.3, A |
| | PAPER PLAN WITH WET SIGNATURE SHALL BE PROVIDED TO THE |
| | BUILDING DEPARTMENT FOR HARD RECORD FILE PRIOR TO |
| | ISSUANCE OF A PERMIT. |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1.AS THE PLANS ARE NOT SIGNED AND SEALED BY A |
| | PROFESSIONAL ENGINEER OR ARCHITECT, A SEPARATE PLUMBING |
| | PLAN IN ACCORDANCE WITH WPB FBC 107.3.4.3 SHALL BEAR |
| | THE PRINTED NAME, THE SIGNATURE AND THE CERTIFICATION |
| | NUMBER OF THE DESIGNER WHO SHALL BE A CONTRACTOR |
| | LICENSED IN THE PLUMBING TRADE. ADDITIONALLY, THE |
| | SHOWER PAN DETAIL SHALL BEAR THE PRINTED NAME, THE |
| | SIGNATURE AND THE CERTIFICATION NUMBER OF THE DESIGNER |
| | WHO SHALL BE A CONTRACTOR LICENSED IN THE PLUMBING |
| | TRADE. |
| | |
| | 2.PER WPB FBC 104.1, A PLUMBING SUB-PERMIT APPLICATION |
| | SHALL BE SUBMITTED FOR THIS PROJECT BY A LICENSED |
| | PLUMBING CONTRACTOR. |
| | |
| | 3.SCOPE OF WORK INCLUDES REPLACEMENT OF EXISTING WATER |
| | HEATER WITH LIKE FOR LIKE. PER WPB FBC 107.2.1, PROVIDE |
| | THE FOLLOWING: |
| | A) LOCATION OF WATER HEATER |
| | B) DESCRIPTION (MANUFACTURER, MODEL #, CAPACITY (GPM |
| | FOR TANKLESS), ELECTRICAL OR GAS CHARACTERISTICS) OF |
| | THE EXISTING WATER HEATER. |
| | C) NEW WATER HEATER SCHEDULE; MANUFACTURER, MODEL #, |
| | CAPACITY (GPM FOR TANKLESS), ELECTRICAL OR GAS |
| | CHARACTERISTICS. |
| | D) WATER HEATER DETAIL- PROVIDE DETAIL OF WATER HEATER |
| | SHOWING HEATER W/STORAGE CAPACITY, PIPING INCLUDING CW, |
| | HW, VALVES (INCLUDING VACUUM RELIEF VALVE IF APPLICABLE |
| | FBC PL 504.2) , THERMAL EXPANSION CONTROL DEVICE |
| | (INCLUDING SIZE), T&P DISCHARGE (INCLUDING TERMINATION) |
| | AND WATER HEATER PAN AND DRAIN (INCLUDING TERMINATION) |
| | PER WPB FPC 107.2.1; COMPLY WITH FBC PL 607.3, 503.1, |
| | 504.1, 504.4, 504.4.1, 504.5, 504.6, 504.7, 504.7.1 AND |
| | 504.7.2. IT IS NOTED THAT PER FBC PL 504.7.2 A PAN IS |
| | NOT REQUIRED FOR A REPLACEMENT WATER HEATER IF A PAN |
| | WAS NOT PREVIOUSLY INSTALLED. |
| | |
| | 4.PER WPB FBC 107.2.1, PROVIDE A RISER DIAGRAM AND PLAN |
| | VIEW SHOWING HOW THE TUB DRAIN IS TO BE CONVERTED TO A |
| | VENTED LAVATORY DRAIN. PLEASE NOTE THAT AIR ADMITTANCE |
| | VALVES INSTALLED MORE THAN FOUR BRANCH INTERVALS BELOW |
| | THE TOP OF THE STACK ARE SUBJECT TO STRINGENT |
| | RESTRICTIONS AS NOTED IN FBC PL 918.3.1. |
| | |
| | 5.PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL WITH |
| | A NOTE STATING, "HORIZONTAL PIPE SHALL BE SUPPORTED IN |
| | ACCORDANCE WITH FBC PL TABLE 308.5.", FOR ANY NEW |
| | PIPING. |
| | |
| | 6.PER WPB FBC 107.2.1, PROVIDE FIRE RATED FLOOR |
| | DETAIL(S) FOR NEW FLOOR PENETRATIONS AND FOR THE |
| | SAFEING OF THE ABANDONED TUB BOX. COMPLY WITH FBC |
| | CHAPTER 7. PER FBC PL 315.1, ANNULAR SPACES CREATED BY |
| | PIPES PENETRATING FIRE-RESISTANCE-RATED ASSEMBLIES OR |
| | MEMBRANES OF SUCH ASSEMBLIES SHALL BE SEALED OR CLOSED |
| | IN ACCORDANCE WITH SECTION 714 OF THE FLORIDA BUILDING |
| | CODE, BUILDING. |
| | |
| | 7.PER WPB FBC 107.2.1, PROVIDE DIMENSIONS IN BATHROOMS |
| | (INCLUDE NEW SHOWER DIMENSIONS). PROVIDE CENTERLINE |
| | DIMENSION FROM WATER CLOSET TO ADJACENT SHOWER |
| | ENCLOSURE. PER FBC PL 406.3.1, A WATER CLOSET, URINAL, |
| | LAVATORY OR BIDET SHALL NOT BE SET CLOSER THAN 15 |
| | INCHES (381 MM) FROM ITS CENTER TO ANY SIDE WALL, |
| | PARTITION, VANITY OR OTHER OBSTRUCTION.405.3.1 |
| | |
| | 8.THE PLANS ARE UNCLEAR AS TO WHAT IS TO BE DONE WITH |
| | THE BATHROOM WALLS AT THE SHOWERS. PER FBC PL 421.4.1, |
| | BATHTUB FLOORS, SHOWER FLOORS, WALL AREAS ABOVE |
| | BUILT-IN TUBS THAT HAVE INSTALLED SHOWER HEADS AND |
| | WALLS IN SHOWER COMPARTMENTS SHALL BE CONSTRUCTED OF |
| | SMOOTH, CORROSION-RESISTANT AND NONABSORBENT WATERPROOF |
| | MATERIALS. WALL MATERIALS SHALL EXTEND TO A HEIGHT OF |
| | NOT LESS THAN 6 FEET (1829 MM) ABOVE THE ROOM FLOOR |
| | LEVEL, AND NOT LESS THAN 70 INCHES (1778 MM) ABOVE THE |
| | DRAIN OF THE TUB OR SHOWER. SUCH WALLS SHALL FORM A |
| | WATER-TIGHT JOINT WITH EACH OTHER AND WITH EITHER THE |
| | TUB OR SHOWER FLOOR. PER WPB FBC 107.2.1, CLARIFY. |
| | |
| | 9.THE PLANS ARE UNCLEAR AS TO WHAT IS TO BE DONE WITH |
| | THE MASTER BATH SHOWER. IS THE FLOOR TILE IN THE SHOWER |
| | TO BE REPLACED? IF SO, A TEST AND INSPECTION OF THE |
| | SHOWER PAN INSTALLATION IS REQUIRED AND THE PAN SHALL |
| | COMPLY WITH THE PROVISIONS OF FBC PL 421.5.2. PER WPB |
| | FBC 107.2.1, CLARIFY ON THE PLANS. |
| | |
| | 10.THE ELECTRICAL PLAN SEEMS TO BE REPRESENTATIVE OF |
| | EXISTING CONDITIONS. IF SO, THE WATER CLOSET APPEARS TO |
| | BE RELOCATED FROM ITS' ORIGINAL LOCATION. PER WPB FBC |
| | 107.2.1, CLARIFY. PROVIDE DRAWINGS SHOWING MODIFICATION |
| | IF APPLICABLE.. |
| | |
| | 11.WATER HAMMER ARRESTORS ARE REQUIRED AT WATER |
| | SUPPLIES TO DISHWASHER AND ICE LINE PER FPC PL 604.9. |
| | |
| | 12.PER FBC PL 409.4, THE WASTE CONNECTION OF A |
| | RESIDENTIAL DISHWASHER SHALL CONNECT DIRECTLY TO A WYE |
| | BRANCH FITTING ON THE TAILPIECE OF THE KITCHEN SINK, |
| | DIRECTLY TO THE DISHWASHER CONNECTION OF A FOOD WASTE |
| | DISPOSER, OR THROUGH AN AIR BREAK TO A STANDPIPE. THE |
| | WASTE LINE OF A RESIDENTIAL DISHWASHER SHALL RISE AND |
| | BE SECURELY FASTENED TO THE UNDERSIDE OF THE SINK RIM |
| | OR COUNTER TOP. |
| | |
| | 13.A ROUGH IN PLUMBING INSPECTION IS REQUIRED FOR |
| | SHOWER VALVE REPLACEMENT. NEW SHOWER CONTROL VALVES TO |
| | COMPLY WITH FBC PL 412.3, WHICH SHALL BE PRESSURE |
| | BALANCED PB, THERMOSTATIC MIXING (TM) OR COMBINATION |
| | PB/TM VALVE TYPES WITH HIGH TEMPERATURE LIMITING STOP |
| | THAT CONFORM TO THE REQUIREMENTS OF ASSE 1016/ASME |
| | A112.1016/CSA B125.16 OR ASME A112.18.1/CSA B125.1 AND |
| | SHALL BE INSTALLED AT THE POINT OF USE. |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT |
| | THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A |
| | RESPONSE NARRATIVE ADDRESSING THE GAS/PLUMBING COMMENTS |
| | FROM THE PRIOR REVIEW. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |
| | |
| | 21060066 1701 S FLAGLER DR # 503 |