Plan Review Details - Permit 21060057
Plan Review Stops For Permit 21060057
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2021-10-15 Cont ID  
Sent By shill Date 2021-10-15 Time 18:33 Rev Time 0.00
Received By shill Date 2021-10-15 Time 18:33 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2021-08-17 Cont ID  
Sent By pvalenti Date 2021-08-17 Time 10:12 Rev Time 0.00
Received By pvalenti Date 2021-08-17 Time 07:54 Sent To  
Notes
2021-08-17 10:13:50****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 ASBESTOS REQUIREMENTS:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-06-30 Cont ID  
Sent By jwitmer Date 2021-06-30 Time 11:17 Rev Time 0.00
Received By jwitmer Date 2021-06-30 Time 11:01 Sent To  
Notes
2021-06-30 11:17:24TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-10-12 Cont ID  
Sent By cthroop Date 2021-10-12 Time 18:28 Rev Time 0.00
Received By shill Date 2021-10-12 Time 18:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-08-17 Cont ID  
Sent By pvalenti Date 2021-08-17 Time 10:34 Rev Time 0.00
Received By jesmith Date 2022-02-01 Time 15:08 Sent To  
Notes
2021-08-17 10:35:46****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW DENIED:
  
 1) WPB AMENDMENTS TO FBC B 109.3, THE CONTRACT VALUE IS
 SHOWN AS $15,000.00 DOLLARS.
 PLEASE PROVIDE A SIGNED COPY OF THE CONTRACT BY THE
 OWNER.
 THE VALUE IS TO INCLUDE THE NEW FLOORING AND
 UNDERLAYMENT MATERIAL , LABOR REMOVAL OF OLD FLOOR AND
 DUMP FEES OVERHEAD AND PROFIT FOR THE WHOLE APARTMENT.
 PROVIDE COST BREAK DOWN FOR THE REMODELING OF THE 2
 BATHROOMS, TO INCLUDE LABOR REMOVAL OF OLD FLOOR AND
 DUMP FEES OVERHEAD AND PROFIT.
 2) IT APPEARS THE TUBS ARE BEING CHANGED INTO SHOWERS
 FOR BOTH BATHROOMS.
 2A) POST TENSION SLAB/ NEW HOLES. THE PLAN IS SILENT AS
 IF THE LOCATION OF THE EXISTING TUB DRAIN IS GOING TO
 BE REUSED IN THE SAME LOCATION. IF NOT, THEN THE FLOOR
 SLAB WILL NEED TO BE X?RAYED TO FIND THE POST TENSION
 CHORD LOCATIONS. 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 2B) THROUGH?PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL
 ASSEMBLIES). IF A NEW FLOOR PENETRATION IS MADE FOR THE
 FUTURE SHOWER DRAIN, THEN YOU NEED TO SHOW COMPLIANCE
 WITH THE 2020 FBC?B SECTION 714.5.1.2.
 THROUGH?PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL
 ASSEMBLIES). THROUGH PENETRATIONS SHALL BE PROTECTED BY
 A THROUGH PENETRATION FIRESTOP SYSTEM INSTALLED IN
 ACCORDANCE WITH ASTM E814 OR UL 1479. THE SYSTEM SHALL
 HAVE AN F RATING / T RATING OF NOT LESS THAN 1 HOUR BUT
 NOT LESS THAN THE REQUIRED RATING OF THE FLOOR
 PENETRATED.
  
 3) THE PROPOSED FLOOR PLAN STATES FOR ALL NEW FLOORING
 JUST CHANGE FLOOR, THE FLOOR FINISH IS NOT PROVIDED.
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 4) FLOOR INSULATION/ UNDERLAYMENT (FBC?B 2020) FOR
 TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL NEED
 TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 4A) FBC?B 2020 1207.3 STRUCTURE?BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E?492.
  
 4B) FBC?B 2020 1207.2 AIR?BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR?BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 4C) FLAME SPREAD? FBC?B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 LVT & LPT LUXURY VINYL TILE. FLOOR FINISH
 CLASSIFICATION AS REQUIRED IN SECTION 804.2
 CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF
 THE 2020 FBC?B.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-06-30 Cont ID  
Sent By jwitmer Date 2021-06-30 Time 11:31 Rev Time 0.00
Received By jwitmer Date 2021-06-30 Time 11:01 Sent To  
Notes
2021-06-30 11:31:28WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21060057
 ADD: 600 S. DIXIE HWY. # 819
 CONT: RETOS SERVICE PLUS LLC
 TEL: 954-588-8468
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JUNE 30TH/ 2021
 ACTION: DENIED
 1) THE CONTRACT VALUE IS SHOWN AS $15,000.00 DOLLARS.
 PLEASE PROVIDE A SIGNED COPY OF THE CONTRACT BY THE
 OWNER.
 THE VALUE IS TO INCLUDE THE NEW FLOORING AND
 UNDERLAYMENT MATERIAL , LABOR REMOVAL OF OLD FLOOR AND
 DUMP FEES OVERHEAD AND PROFIT FOR THE WHOLE APARTMENT.
 PROVIDE COST BREAK DOWN FOR THE REMODELING OF THE 2
 BATHROOMS, TO INCLUDE LABOR REMOVAL OF OLD FLOOR AND
 DUMP FEES OVERHEAD AND PROFIT.
  
 109.3 BUILDING PERMIT VALUATION. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL,
 PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD
 AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION
 REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) IT APPEARS THE TUBS ARE BEING CHANGED INTO SHOWERS
 FOR BOTH BATHROOMS.
 2A) POST TENSION SLAB/ NEW HOLES. THE PLAN IS SILENT AS
 IF THE LOCATION OF THE EXISTING TUB DRAIN IS GOING TO
 BE REUSED IN THE SAME LOCATION. IF NOT, THEN THE FLOOR
 SLAB WILL NEED TO BE X-RAYED TO FIND THE POST TENSION
 CHORD LOCATIONS. 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 2B) THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL
 ASSEMBLIES). IF A NEW FLOOR PENETRATION IS MADE FOR THE
 FUTURE SHOWER DRAIN, THEN YOU NEED TO SHOW COMPLIANCE
 WITH THE 2020 FBC-B SECTION 714.5.1.2.
 THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL
 ASSEMBLIES). THROUGH PENETRATIONS SHALL BE PROTECTED BY
 A THROUGH PENETRATION FIRESTOP SYSTEM INSTALLED IN
 ACCORDANCE WITH ASTM E814 OR UL 1479. THE SYSTEM SHALL
 HAVE AN F RATING / T RATING OF NOT LESS THAN 1 HOUR BUT
 NOT LESS THAN THE REQUIRED RATING OF THE FLOOR
 PENETRATED.
  
 3) THE PROPOSED FLOOR PLAN STATES FOR ALL NEW FLOORING
 JUST CHANGE FLOOR, THE FLOOR FINISH IS NOT PROVIDED.
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 4) FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR
 TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL NEED
 TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 4A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 4B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 4C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 LVT & LPT LUXURY VINYL TILE. FLOOR FINISH
 CLASSIFICATION AS REQUIRED IN SECTION 804.2
 CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF
 THE 2020 FBC-B.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-06-07 Cont ID  
Sent By pleduc Date 2021-06-07 Time   Rev Time 0.00
Received By pleduc Date 2021-06-07 Time 14:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-08-17 Cont ID  
Sent By pvalenti Date 2021-08-17 Time 13:07 Rev Time 0.00
Received By pvalenti Date 2021-08-02 Time 07:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-06-30 Time 11:30 Rev Time 0.00
Received By cdecoeur Date 2021-06-03 Time 09:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-09-13 Cont ID  
Sent By lcrespo Date 2021-09-13 Time 16:25 Rev Time 0.00
Received By lcrespo Date 2021-09-13 Time 16:25 Sent To  
Notes
2021-09-13 16:26:1209/13/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-08-05 Cont ID  
Sent By pvalenti Date 2021-08-05 Time 16:30 Rev Time 0.00
Received By jesmith Date 2022-02-01 Time 15:11 Sent To  
Notes
2021-08-05 16:31:47CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
 1.THIS UNIT WAS BUILT UNDER THE FAIR HOUSING ACT OF
 MARCH 6, 1991, AND SHALL COMPLY WITH FAIR HOUSING ACT
 CHAPTER 7
 A) SECOND REQUEST: PER WPB FBC 107.2.1, IDENTIFY THE
 COMPLIANT BATHROOM(S) AND IDENTIFY IT/THEM AS TYPE A
 AND/OR TYPE B (PLANS ARE NOT CLEAR IN THIS REGARD).
 PLEASE SHOW THE CLEAR FLOOR SPACES FOR THE FIXTURES.
 NOT SHOWN, PLEASE REFER TO THE FAIR HOUSING ACT DESIGN
 MANUAL CHAPTER 7 PART B FOR CLARIFICATION.
 B) SECOND REQUEST: PER WPB FBC 107.2.1, PLEASE SHOW THE
 CLEAR FLOOR SPACES FOR THE KITCHEN SINK AND APPLIANCES
 IN THE KITCHEN. NOT SHOWN, PLEASE REFER TO THE FAIR
 HOUSING ACT DESIGN MANUAL CHAPTER 7 PART A FOR
 CLARIFICATION.
 C) COMPLIED
  
 2.SECOND REQUEST: FBC 2020 R307.2 IS NOT THE PREVAILING
 CODE. NOTE PERTAINING TO SHOWER/BATHTUB COMPARTMENT
 SHALL REFERENCE FBC PL 421.4.1: PLEASE NOTE THAT PER
 WPB FBC 101.2 AND 101.4.3 REQUIRES COMPLIANCE WITH THE
 FBC PL (FLORIDA PLUMBING CODE) UNLESS THE STRUCTURE IS
 A DETACHED ONE AND TWO FAMILY DWELLING AND MULTIPLE
 SINGLE FAMILY DWELLINGS (TOWNHOUSES0 NOT MORE THAN
 THREE STORIES ABOVE GRADE PLANE IN HEIGHT WITH A
 SEPARATE MEANS OF EGRESS AND THEIR ACCESSORY STRUCTURES
 SHALL COMPLY WITH THE FLORIDA BUILDING CODE,
 RESIDENTIAL.
  
 3.COMPLIED
  
 4.MASTER BATH:
 ?.A-1) IT WOULD APPEAR THAT THE LAVATORY IN EXISTING
 CONDITIONS IS AN INDIVIDUALLY VENTED FIXTURE DRAIN AND
 THE FLOOR PENETRATION WILL NOT BE RELOCATED. PER WPB
 FBC 107.2.1, CLARIFY/CONFIRM ON THE PLANS. IF THIS IS
 THE CASE PROVIDE NOTE ON PROPOSED FLOOR PLAN STATING
 "MODIFY EXISTING IN-WALL SANITARY WASTE AND VENT PIPING
 BY PROVIDING COMMON VENTING OF TWO (2) LAVATORIES;
 COMPLY WITH FBC PL SECTION 909.1, TABLE 909.1 AND
 SECTION 911." THIS IS IN LIEU OF REQUIRING A SANITARY
 RISER DIAGRAM FOR THIS CONDITION. IF THIS NOT THE
 CONDITION, A SANITARY RISER DIAGRAM WILL BE REQUIRED
 SHOWING HOW THIS PIPING WILL BE ACCOMPLISHED IN A
 MANNER THAT COMPLIES WITH THE REQUIREMENTS OF FBC PL
 CHAPTERS 7 AND 9.
 COMPLIED
 ?.A-2)SECOND REQUEST: ADDITIONALLY INDICATE TYPE OF
 MATERIAL (I.E. CAST IRON, PVC) OF DRAIN PIPE
 PENETRATING THROUGH THE FLOOR AND THE HORIZONTAL BRANCH
 BELOW. PROVIDE ASSEMBLY HAVING A FIRE-RESISTANCE RATING
 OF NOT LESS THAN 1 HOUR TO BE USED FOR DEALING WITH THE
 SHOWER FLOOR PENETRATION AS REQUIRED BY FBC 714.4.1
 THROUGH 714.4.4.1.2 PER WPB FPC 107.2.1. SHOW HOW
 ABANDONED PENETRATION WILL BE REMEDIATED.
 ?.B) COMPLIED
  
 5. COMPLIED
  
 6.SECOND REQUEST: PROVIDE ASSEMBLY HAVING A
 FIRE-RESISTANCE RATING OF NOT LESS THAN 1 HOUR TO BE
 USED FOR DEALING WITH THE SHOWER FLOOR PENETRATION AS
 REQUIRED BY FBC 714.4.1 THROUGH 714.4.4.1.2 PER WPB FPC
 107.2.1. SHOW HOW ABANDONED PENETRATION WILL BE
 REMEDIATED.
  
 7. COMPLIED
  
 8. COMPLIED
  
 9. COMPLIED
  
 10. NEW COMMENT: PER WPB FBC 107.2.1, RECONCILE A-1
 WITH P-1. BATHTUBS ARE STILL SHOWN ON A-1 PROPOSED
 FLOOR PLAN.
  
 11.NEW COMMENT: REGARDING NEW SHOWERS;
 -POST TENSION SLAB/ NEW HOLES. AS PREVIOUSLY NOTED BY
 THE BUILDING PLANS EXAMINER, THE PLAN IS SILENT AS IF
 THE LOCATION OF THE EXISTING TUB DRAIN IS GOING TO BE
 REUSED IN THE SAME LOCATION. IF NOT, THEN THE FLOOR
 SLAB WILL NEED TO BE X-RAYED TO FIND THE POST TENSION
 CHORD LOCATIONS. WPB FBC 107.2.1.2. ADDITIONAL
 INFORMATION IS REQUIRED.
 -THE PLAN INDICATES A RECTANGULAR TRENCH DRAIN WHICH
 WILL REQUIRE CUTTING OF THE ELEVATED STRUCTURAL SLAB TO
 INSTALL. PER WPB FBC 107.2.1, SPECIFY THE DRAIN TO BE
 INCORPORATED AND PROVIDE MANUFACTURER?S
 SPECIFICATION/INSTALLATION SHEETS. SAID DRAIN SHALL
 INCLUDE A MEMBRANE CLAMPING RING FOR USE WITH A SHOWER
 LINER.
 -IF CUTTING OF SLAB IS REQUIRED TO ACCOMMODATE SAID
 DRAIN IS REQUIRED, PROVIDE A DETAIL SHOWING THE DETAILS
 FOR CUTTING THE SLAB: SHOW THE DIMENSIONS OF THE
 OPENING, THE DIMENSIONS OF THE DRAIN, IMBED
 INFORMATION, THE MINIMUM THICKNESS OF THE CONCRETE TO
 BE REPLACED, AND THE PSI OF THE CONCRETE. SHOW THE SIZE
 AND LENGTH OF THE DOWELS, THE MINIMUM EMBEDMENT INTO
 THE EXISTING SLAB, THE ANCHORING MATERIAL FOR THE
 DOWELS AND THE SPACING OF THE DOWELS ON CENTER.
 -AS NEW FLOOR PENETRATIONS ARE TO BE MADE FOR THE
 FUTURE SHOWER DRAINS AND AS PREVIOUSLY NOTED BY THE
 BUILDING PLANS EXAMINER, PER WPB FBC 107.2.1, SHOW
 COMPLIANCE WITH THE 2020 FBC-B SECTION 714.5.1.2.
 THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL
 ASSEMBLIES). THROUGH PENETRATIONS SHALL BE PROTECTED BY
 A THROUGH PENETRATION FIRESTOP SYSTEM INSTALLED IN
 ACCORDANCE WITH ASTM E814 OR UL 1479. THE SYSTEM SHALL
 HAVE AN F RATING / T RATING OF NOT LESS THAN 1 HOUR BUT
 NOT LESS THAN THE REQUIRED RATING OF THE FLOOR
 PENETRATED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
 PLEASE NOTE THAT WHEN SCANNED DRAWINGS ARE SUBMITTED
 WITH CONTRACTOR'S PRINTED NAME, SIGNATURE AND LICENSE
 NUMBER IN ACCORDANCE WITH WPB FBC 107.2.1, A PAPER PLAN
 WITH WET SIGNATURE SHALL BE PROVIDED TO THE BUILDING
 DEPARTMENT FOR HARD RECORD FILE PRIOR TO ISSUANCE OF A
 PERMIT.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-06-17 Cont ID  
Sent By jesmith Date 2021-06-17 Time 15:19 Rev Time 0.00
Received By jesmith Date 2021-06-17 Time 10:30 Sent To  
Notes
2021-06-17 15:17:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 1. THIS UNIT WAS BUILT UNDER THE FAIR HOUSING ACT OF
 MARCH 6, 1991, AND SHALL COMPLY WITH FAIR HOUSING ACT
 CHAPTER 7.
 ....A)PER WPB FBC 107.2.1, IDENTIFY THE COMPLIANT
 BATHROOM(S) AND IDENTIFY IT/THEM AS TYPE A AND/OR TYPE
 B. PLEASE SHOW THE CLEAR FLOOR SPACES FOR THE FIXTURES.
 ....B) PER WPB FBC 107.2.1, PLEASE SHOW THE CLEAR FLOOR
 SPACES FOR THE KITCHEN SINK AND APPLIANCES IN THE
 KITCHEN
 ....C)THE BATHROOM CABINET MUST BE A MAXIMUM OF 34"
 UNDER THE FAIR HOUSING ACT DESIGN MANUAL PAGE 7.52. YOU
 MAY CHOOSE TO OMIT THIS CHANGE. THE CITY OF WEST PALM
 BEACH BUILDING DEPARTMENT PROVIDES AN OPTION FOR
 CHANGING AN FHA COMPLIANCE STRUCTURE. THE OWNER AND
 DESIGNER OF RECORD ACKNOWLEDGE THAT THE PROPOSED
 BATHROOM DESIGN DOES NOT MEET THE REQUIREMENTS OF THE
 FAIR HOUSING ACCESSIBILITY GUIDELINES. THE OWNER AGREES
 TO REVERT THE UNIT BACK TO COMPLIANCE AT THE TIME OF
 SALE IF REQUESTED BY THE BUYER. THIS WILL BE IN A
 LETTER-TYPE FORMAT SIGNED AND NOTARIZED BY THE OWNER.
 WE PROVIDE A SAMPLE LETTER, AND IT MUST BE SUBMITTED TO
 THE BUILDING DEPARTMENT OF THE CITY OF WPB. IF THIS
 OPTION IS CHOSEN, PLEASE SEND AN EMAIL TO
 [email protected], AND I WILL SEND A COPY OF THE FAIR
 HOUSING AFFIDAVIT.
  
 2. FBC 2004 R307.2 IS NOT THE PREVAILING CODE. NOTE
 PERTAINING TO SHOWER/BATHTUB COMPARTMENT SHALL
 REFERENCE FBC PL 421.4.1: BATHTUB FLOORS, SHOWER
 FLOORS, WALL AREAS ABOVE BUILT-IN TUBS THAT HAVE
 INSTALLED SHOWER HEADS AND WALLS IN SHOWER COMPARTMENTS
 SHALL BE CONSTRUCTED OF SMOOTH, CORROSION-RESISTANT AND
 NONABSORBENT WATERPROOF MATERIALS. WALL MATERIALS SHALL
 EXTEND TO A HEIGHT OF NOT LESS THAN 6 FEET ABOVE THE
 ROOM FLOOR LEVEL, AND NOT LESS THAN 70 INCHES ABOVE THE
 DRAIN OF THE TUB OR SHOWER. SUCH WALLS SHALL FORM A
 WATER-TIGHT JOINT WITH EACH OTHER AND WITH EITHER THE
 TUB OR SHOWER FLOOR.
  
 3. SHOWER INSTALLATION DETAIL SHALL SHOW THE ADDITIONAL
 FOLLOWING INFORMATION TO COMPLY WITH FBC PL 421.5.2:
 LINER SHALL TURN UP ON ALL SIDES NOT LESS THAN 2 INCHES
 ABOVE THE FINISHED THRESHOLD LEVEL. LINER SHALL NOT BE
 NAILED OR PERFORATED AT ANY POINT LESS THAN 1 INCH (25
 MM) ABOVE THE FINISHED THRESHOLD. LINER SHALL BE
 PITCHED ONE-FOURTH UNIT VERTICAL IN 12 UNITS HORIZONTAL
 (2-PERCENT SLOPE) AND SHALL BE SLOPED TOWARD THE
 FIXTURE DRAINS.
  
 4. MASTER BATH:
 ....A) IT WOULD APPEAR THAT THE LAVATORY IN EXISTING
 CONDITIONS IS AN INDIVIDUALLY VENTED FIXTURE DRAIN AND
 THE FLOOR PENETRATION WILL NOT BE RELOCATED. PER WPB
 FBC 107.2.1, CLARIFY/CONFIRM ON THE PLANS. IF THIS IS
 THE CASE PROVIDE NOTE ON PROPOSED FLOOR PLAN STATING
 "MODIFY EXISTING IN-WALL SANITARY WASTE AND VENT PIPING
 BY PROVIDING COMMON VENTING OF TWO (2) LAVATORIES;
 COMPLY WITH FBC PL SECTION 909.1, TABLE 909.1 AND
 SECTION 911." THIS IS IN LIEU OF REQUIRING A SANITARY
 RISER DIAGRAM FOR THIS CONDITION. IF THIS NOT THE
 CONDITION, A SANITARY RISER DIAGRAM WILL BE REQUIRED
 SHOWING HOW THIS PIPING WILL BE ACCOMPLISHED IN A
 MANNER THAT COMPLIES WITH THE REQUIREMENTS OF FBC PL
 CHAPTERS 7 AND 9. ADDITIONALLY INDICATE TYPE OF
 MATERIAL (I.E. CAST IRON, PVC) OF DRAIN PIPE
 PENETRATING THROUGH THE FLOOR AND THE HORIZONTAL BRANCH
 BELOW. PROVIDE ASSEMBLY HAVING A FIRE-RESISTANCE RATING
 OF NOT LESS THAN 1 HOUR TO BE USED FOR DEALING WITH THE
 SHOWER FLOOR PENETRATION AS REQUIRED BY FBC 714.4.1
 THROUGH 714.4.4.1.2 PER WPB FPC 107.2.1. SHOW HOW
 ABANDONED PENETRATION WILL BE REMEDIATED.
 .... B) PER WPB FBC 107.2.1, PROVIDE NOTE ON PROPOSED
 FLOOR PLAN STATING "MODIFY EXISTING IN-WALL WATER
 PIPING TO ACCOMMODATE TWO (2) NEW LAVATORIES WHICH ARE
 REPLACING ORIGINAL SINGLE LAVATORY; COMPLY WITH
 REQUIREMENTS OF FBC PL CHAPTER 6 INCLUDING BUT NOT
 LIMITED TO SECTIONS 604 (SIZING), 605.2.1 (LEAD
 CONTENT) AND 607.4 (HOT WATER ON THE LEFT)"
  
 5. REPLACE EXISTING BATHTUBS WITH SHOWERS: THE SHOWER
 DRAIN PENETRATION WILL BE RELOCATED FROM EXISTING
 CONDITIONS. PROVIDE NOTE "MODIFY EXISTING FIXTURE DRAIN
 TO ACCOMMODATE NEW DRAIN LOCATION, COMPLY WITH FBC PL
 SECTION 909.1 AND TABLE 909.1." THIS IS IN LIEU OF
 REQUIRING A SANITARY RISER DIAGRAM FOR THIS CONDITION.
  
 6. PROVIDE ASSEMBLY HAVING A FIRE-RESISTANCE RATING OF
 NOT LESS THAN 1 HOUR TO BE USED FOR DEALING WITH THE
 SHOWER FLOOR PENETRATION AS REQUIRED BY FBC 714.4.1
 THROUGH 714.4.4.1.2 PER WPB FPC 107.2.1. SHOW HOW
 ABANDONED PENETRATION WILL BE REMEDIATED.
  
 7. PER WPB FBC 107.2.1, PROVIDE NOTE, ?PER FBC PL
 412.3, INDIVIDUAL SHOWER AND TUB-SHOWER COMBINATION
 VALVES SHALL BE BALANCED-PRESSURE, THERMOSTATIC OR
 COMBINATION BALANCED-PRESSURE/THERMOSTATIC VALVES THAT
 CONFORM TO THE REQUIREMENTS OF ASSE 1016/ASME
 A112.1016/CSA B125.16 OR ASME A112.18.1/CSA B125.1 AND
 SHALL BE INSTALLED AT THE POINT OF USE. SHOWER AND
 TUB-SHOWER COMBINATION VALVES REQUIRED BY THIS SECTION
 SHALL BE EQUIPPED WITH A MEANS TO LIMIT THE MAXIMUM
 SETTING OF THE VALVE TO 120?F, WHICH SHALL BE FIELD
 ADJUSTED IN ACCORDANCE WITH THE MANUFACTURER?S
 INSTRUCTIONS. IN-LINE THERMOSTATIC VALVES SHALL NOT BE
 UTILIZED FOR COMPLIANCE WITH THIS SECTION?
  
 8. PER WPB FBC 107.2.1, SHOW THE PROPOSED SHOWERS AS
 SHOWERS, NOT BATHTUBS.
  
 9. PER WPB FBC 107.2.1, SHOW THE KITCHEN SINK AND
 DISHWASHER.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21060057 600 S DIXIE HWY # 819

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-10-22 Cont ID  
Sent By shill Date 2021-10-22 Time 11:04 Rev Time 0.00
Received By shill Date 2021-10-22 Time 11:04 Sent To  
Notes
2021-10-22 11:05:08ROUTED ORIGINAL TO STORAGE
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-08-17 Cont ID  
Sent By pvalenti Date 2021-08-17 Time 12:58 Rev Time 0.00
Received By pvalenti Date 2021-08-17 Time 12:58 Sent To  
Notes
2021-08-17 13:03:48****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 SIGNATURE REVIEW DENIED:
  
  
 FS 471/FS 481 DOCUMENTS PREPARED BY AN
 ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE
 TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A
 SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL.
 UPLOAD OR EMAIL A DIGITALLY SIGNED (THIRD PARTY
 VERIFIED) PLAN OR YOU CAN DELIVER AN ORIGINAL
 SIGNED/SEALED PAPER ORIGINAL TO:
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER II
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 FEEL FREE TO CONTACT ME AT 561 805 6673.
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-06-17 Cont ID  
Sent By jesmith Date 2021-06-17 Time 10:31 Rev Time 0.00
Received By jesmith Date 2021-06-17 Time 10:31 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy