| Plan Review Stops For Permit 21060033 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2021-09-16 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-09-16 |
Time |
08:57 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-09-16 |
Time |
08:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2021-06-24 |
|
|
Cont ID |
|
| Sent By |
mcphers |
Date |
2021-06-24 |
Time |
08:38 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-06-24 |
Time |
08:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2021-11-09 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-11-09 |
Time |
16:48 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-10-26 |
Time |
12:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2021-10-25 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2021-10-25 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2021-10-05 |
Time |
10:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-09-28 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2021-09-28 |
Time |
08:25 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2021-08-25 |
Time |
09:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-06-24 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-06-24 |
Time |
08:44 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-06-09 |
Time |
16:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2021-11-09 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-11-09 |
Time |
16:44 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-11-09 |
Time |
16:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2021-10-25 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-10-25 |
Time |
15:40 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-10-25 |
Time |
15:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2021-09-16 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-09-16 |
Time |
08:58 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-09-16 |
Time |
08:58 |
Sent To |
|
|
| Notes |
| 2021-09-16 09:00:26 | SIGNATURE REVIEW | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED = | | | 1) DRAWING (LI-1) AND (FP-1) NEEDS TO BE SIGNED AND | | | SEALED BY THE DESIGNER FBC WPB 107.1 | | | | | | DRAWINGS DO NOT SHOW AS ELECTRONICALLY SIGNED IN ADOBE | | | READER - SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED | | | TO BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER | | | OR ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. - OR | | | - IF YOUR ARCHITECT OR ENGINEER DOES NOT HAVE AN | | | ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN DROP OFF THE | | | ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE | | | FRONT DESK IN THE BUILDING DIVISION AT THE CITY HALL. | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2021-06-24 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-06-24 |
Time |
08:39 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-06-24 |
Time |
08:39 |
Sent To |
|
|
| Notes |
| 2021-06-24 08:43:49 | SIGNATURE REVIEW | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED = | | | 1) DRAWING (LI-1) NEEDS TO BE SIGNED BY THE DESIGNER | | | FBC WPB 107.1 | | | DRAWINGS DO NOT SHOW AS ELECTRONICALLY SIGNED IN ADOBE | | | READER - SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED | | | TO BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER | | | OR ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. - OR | | | - IF YOUR ARCHITECT OR ENGINEER DOES NOT HAVE AN | | | ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN DROP OFF THE | | | ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE | | | FRONT DESK IN THE BUILDING DIVISION AT THE CITY HALL. | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2021-11-09 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2021-11-09 |
Time |
14:47 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2021-11-09 |
Time |
14:47 |
Sent To |
|
|
| Notes |
| 2021-11-09 14:49:07 | 11/9/21- PASSED WITH THE PROVISO THAT A SEPERATE | | | LANDSCAPE PERMIT MUST BE SUBMITTED, APPROVED AND | | | INSTALLED PRIOR TO COC BEING ISSUED. SEPERATE PERMIT | | | ALSO REQUIRED FOR ANY FENCING/WALL ON THE SITE | | | | | | ANGELLA VANN, AICP | | | 561-822-1441 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2021-10-25 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2021-10-25 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2021-10-25 |
Time |
15:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2021-09-27 |
|
|
Cont ID |
|
| Sent By |
rthermid |
Date |
2021-09-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
rthermid |
Date |
2021-09-27 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2021-06-22 |
|
|
Cont ID |
|
| Sent By |
rthermid |
Date |
2021-06-22 |
Time |
|
Rev Time |
|
| Received By |
rthermid |
Date |
2021-06-22 |
Time |
|
Sent To |
I |
|
| Notes |
|
|