Plan Review Details - Permit 21051556
Plan Review Stops For Permit 21051556
Review Stop ENG ENGINEERING CSD
Rev No 3 Status N Date 2021-09-17 Cont ID  
Sent By lcrespo Date 2021-09-17 Time 15:12 Rev Time 0.00
Received By lcrespo Date 2021-09-17 Time 15:12 Sent To  
Notes
2021-09-17 15:13:16UNIT IS BOUGHT INSIDE BUILDING AND NO ENG REVIEW
 REQUIRED.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2021-08-31 Cont ID  
Sent By rrossano Date 2021-08-31 Time   Rev Time 0.00
Received By rrossano Date 2021-08-31 Time   Sent To I
Notes
2021-08-31 13:02:52PLEASE ADDRESS BUILDING COMMENTS.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2021-06-02 Cont ID  
Sent By rrossano Date 2021-06-02 Time   Rev Time  
Received By rrossano Date 2021-06-02 Time   Sent To  
Notes
2021-06-02 12:45:49PROVIDE ENGINEERING DRAWING SHOWING PLACEMENT OF GREASE
 TRAP.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
 RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT (561) 494-1098 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-09-17 Cont ID  
Sent By lcrespo Date 2021-09-17 Time 15:12 Rev Time 0.00
Received By lcrespo Date 2021-09-16 Time 12:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-09-01 Cont ID  
Sent By lmarchan Date 2021-09-01 Time 08:44 Rev Time 0.00
Received By lmarchan Date 2021-08-13 Time 09:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-06-16 Time   Rev Time 0.00
Received By cdecoeur Date 2021-05-28 Time 08:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-09-17 Cont ID  
Sent By lcrespo Date 2021-09-17 Time 15:11 Rev Time 0.00
Received By lcrespo Date 2021-09-17 Time 15:11 Sent To  
Notes
2021-09-17 15:12:0509/17/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-08-26 Cont ID  
Sent By ccole Date 2021-08-26 Time 08:24 Rev Time 0.00
Received By ccole Date 2021-08-26 Time 07:23 Sent To  
Notes
2021-08-26 08:25:232ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21051556
 8/26/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
 THE RESUBMITTED PLAN IS INDICATING REPLACEMENT OF AN
 EXISTING INTERCEPTOR HOWEVER THERE ARE NO RECORDS IN
 THE WEST PALM BEACH BUILDING DEPARTMENT TO INDICTE A
 PERMIT WAS EVER OBTAINED TO INSTALL AN INTERCEPTOR AT
 THE PROJECT ADDRESS- 6108 S. DIXIE HWY UNIT-4. PLEASE
 CORRECT THE PLAN TO INDICATE A NEW INTERCEPTOR
 INSTALLATION AND COMPLY WITH THE 1ST REVIEW COMMENTS
 PRINTED BELOW. PLEASE NOTE THAT MANUFACTURER?S
 SPECIFICATIONS HAVE BEEN SUBMITTED FOR AN INDOOR
 INTERCEPTOR HOWEVER SHEET A2 SHOWS THE INTERCEPTOR TO
 BE LOCATED ON THE EXTERIOR OF THE BUILDING WHICH IS NOT
 IN COMPLIANCE WITH SECTION 1003.3.4 FBC P.
  
 1ST REVIEW:
 1) PROVIDE A DIMENSIONED AND DETAILED PLAN SHOWING THE
 LOCATION OF THE INTERCEPTOR AND PLUMBING PIPING
 REQUIREMENTS. SHOW THE GREASE WASTE PIPING RUNS FROM
 THE FIXTURES TO THE INTERCEPTOR AND FROM THE
 INTERCEPTOR TO POINT OF CONNECTION TO THE EXISTING
 BUILDING OR SEWER DRAIN. SHOW LOCATIONS OF ALL REQUIRED
 CLEANOUTS AND VENTS PER MANUFACTURER?S SPECIFICATIONS-
 SECTION 1003.3.5 FBC P AND SECTION 107.2.1 WPB.
  
 2) PROVIDE GREASE WASTE CALCULATIONS AND INTERCEPTOR
 EQUIPMENT SCHEDULE ON THE PLAN IN COMPLIANCE WITH
 SECTION 1003.3.5 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-06-16 Cont ID  
Sent By ccole Date 2021-06-16 Time 11:56 Rev Time 0.00
Received By ccole Date 2021-06-16 Time 11:16 Sent To  
Notes
2021-06-16 11:56:201ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21051556
 6/16/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
 A COMPREHENSIVE AND THOROUGH REVIEW OF THE INDOOR
 GREASE INTERCEPTOR CANNOT BE COMPLETED AT THIS TIME DUE
 TO A LACK OF REQUIRED COMPLIANCE INFORMATION ( SEE
 COMMENTS 1 & 2 LISTED BELOW), AND ALSO DUE TO THE FACT
 THAT NO PERMIT FOR THE TENANT SPACE BUILDOUT HAS BEEN
 ISSUE OR EVEN APPLIED FOR. GREASE INTERCEPTOR PERMITS
 ARE TYPICALLY ISSUED IN CONJUNCTION WITH PERMITS ISSUED
 FOR RESTAURANT AND OTHER OCCUPANCIES WHERE GREASE LADEN
 WASTE IS PRODUCED AS A BY-PRODUCT OF COOKING AND
 CLEANING OPERATIONS. CURRENTLY THERE IS NO PERMIT
 APPLICATION AND PLAN SUBMITTED FOR THE PROPOSED
 OCCUPANCY.
  
 1) PROVIDE A DIMENSIONED AND DETAILED PLAN SHOWING THE
 LOCATION OF THE INTERCEPTOR AND PLUMBING PIPING
 REQUIREMENTS. SHOW THE GREASE WASTE PIPING RUNS FROM
 THE FIXTURES TO THE INTERCEPTOR AND FROM THE
 INTERCEPTOR TO POINT OF CONNECTION TO THE EXISTING
 BUILDING OR SEWER DRAIN. SHOW LOCATIONS OF ALL REQUIRED
 CLEANOUTS AND VENTS PER MANUFACTURER?S SPECIFICATIONS-
 SECTION 1003.3.5 FBC P AND SECTION 107.2.1 WPB.
  
 2) PROVIDE GREASE WASTE CALCULATIONS AND INTERCEPTOR
 EQUIPMENT SCHEDULE ON THE PLAN IN COMPLIANCE WITH
 SECTION 1003.3.5 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-09-17 Cont ID  
Sent By pvalenti Date 2021-09-17 Time 07:42 Rev Time 0.00
Received By pvalenti Date 2021-09-17 Time 07:39 Sent To  
Notes
2021-09-17 07:43:54CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTI
  
 SIGNATURE REVIEW APPROVED BY PAPER SIGNED/SEALED PLAN
 SHEETS A-1 & A-2. THESE SHEETS HAVE BEEN ROUTED TO
 STORAGE.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-08-13 Cont ID  
Sent By lcrespo Date 2021-08-13 Time 18:11 Rev Time 0.00
Received By lcrespo Date 2021-08-13 Time 18:11 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-06-16 Cont ID  
Sent By ccole Date 2021-06-16 Time 12:00 Rev Time 0.00
Received By ccole Date 2021-06-16 Time 12:00 Sent To  
Notes
***NONE***