Plan Review Details - Permit 21051514
Plan Review Stops For Permit 21051514
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status N Date 2021-06-29 Cont ID  
Sent By rmcphers Date 2021-06-29 Time 08:56 Rev Time 0.00
Received By rmcphers Date 2021-06-29 Time 08:56 Sent To  
Notes
2021-06-29 08:56:47DEMO UNDER PERMIT 21031147

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-07-27 Cont ID  
Sent By rmcphers Date 2021-07-27 Time 11:20 Rev Time 0.00
Received By rmcphers Date 2021-07-27 Time 11:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-06-29 Cont ID  
Sent By rmcphers Date 2021-06-29 Time 08:53 Rev Time 0.00
Received By rmcphers Date 2021-06-29 Time 07:50 Sent To  
Notes
2021-06-29 08:43:58RESTAURANT RENO
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
 1) PLEASE SHOW THE PROPOSED SLOPE FOR THE SLOPE FLOOR
 AREA SHOWN ON DRAWING A1.00 FBC A405.2
 2) HAND RAILS ARE REQUIRED ON BOTH SIDES OF A RAMP FBC
 505.2 (SHOW HAND RAIL DETAILS IF HAND RAILS ARE
 REQUIRED FBC A 403.6)
 3) DOOR 04 ON THE 2ND FLOOR APPEARS TO BE BLOCKING THE
 EXIT - FBC 1005.7 ENCROACHMENT.
 ENCROACHMENTS INTO THE REQUIRED MEANS OF EGRESS WIDTH
 SHALL BE IN ACCORDANCE WITH THE PROVISIONS OF THIS
 SECTION.1005.7.1 DOORS.
 DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED
 WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN ANY
 POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE
 THAN ONE-HALF.
 4) A PICK UP COUNTER IS SHOWN - PLEASE SHOW THE
 ACCESSIBLE PICK UP COUNTER AREA (IF USED FOR CUSTOMER
 PICK UP) FLOOR SPACE - COUNTER HEIGHT ETC.. FBC A904.4
 5) PLEASE SHOW THE RESTROOM MIRROR DIMENSION TO THE
 REFLECTIVE SURFACE - FBC A603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
 6) PLEASE SHOW THE HEIGHT OF THE ORDER AND PICK UP
 COUNTER TO COMPLY WITH FBC A904.4
 7) PLEASE SHOW THE OCCUPANCY SIGNAGE THAT IS REQUIRED -
 FBC 1004.9 POSTING OF OCCUPANT LOAD.
 EVERY ROOM OR SPACE THAT IS AN ASSEMBLY OCCUPANCY SHALL
 HAVE THE OCCUPANT LOAD OF THE ROOM OR SPACE POSTED IN A
 CONSPICUOUS PLACE, NEAR THE MAIN EXIT OR EXIT ACCESS
 DOORWAY FROM THE ROOM OR SPACE, FOR THE INTENDED
 CONFIGURATIONS. POSTED SIGNS SHALL BE OF AN APPROVED
 LEGIBLE PERMANENT DESIGN AND SHALL BE MAINTAINED BY THE
 OWNER OR THE OWNER?S AUTHORIZED AGENT.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-06-10 Cont ID  
Sent By jleahy Date 2021-06-10 Time 18:39 Rev Time 0.00
Received By jleahy Date 2021-06-10 Time 18:11 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2021-06-11 Cont ID  
Sent By jleahy Date 2021-06-11 Time 15:12 Rev Time 0.00
Received By jleahy Date 2021-06-11 Time 15:12 Sent To  
Notes
2021-06-11 15:12:34VOICE, DATA, AND TV JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-07-21 Cont ID  
Sent By pleduc Date 2021-07-21 Time   Rev Time 0.00
Received By pleduc Date 2021-07-21 Time 09:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-06-04 Cont ID  
Sent By pleduc Date 2021-06-04 Time   Rev Time 0.00
Received By pleduc Date 2021-06-04 Time 11:19 Sent To  
Notes
2021-06-04 11:49:17THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET LS 00 & A100 - THERE IS AN INDICATION OF A
 DOUBLE SWING DOOR, 04, IN THE PATH OF EXIT TRAVEL.
  
 THE PROPOSED OCCUPANCY LOAD OF THE 2ND FLOOR IS
 INDICATED 50, THOUGH THERE IS OPEN STANDING SPACES
 THOUGHOUT THE FLOOR AREA THAT COULD ACCOMODATE, HIGHER
 CAPACITY.
  
 PER NFPA
  
 7.2.1.4.2* DOOR LEAF SWING DIRECTION. DOOR LEAVES
 REQUIRED TO BE OF
 THE SIDE-HINGED OR PIVOTED-SWINGING TYPE SHALL SWING IN
 THE DIRECTION
 OF EGRESS TRAVEL UNDER ANY OF THE FOLLOWING CONDITIONS:
 (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD
 OF 50 OR MORE,
 EXCEPT UNDER ANY OF THE FOLLOWING CONDITIONS:
 (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE
 REQUIRED TO SWING
 IN THE DIRECTION OF EGRESS TRAVEL WHERE PERMITTED BY
 7.2.4.3.8.1
 OR 7.2.4.3.8.2.
  
 DOOR 04 IS REQUIRED TO SWING IN THE PATH OF TRAVEL.
  
 PLEASE REVIEW AND CORRECT.
  
  
 1A) SHEET LS 00 & A100 - THERE IS AN INDICATION OF A
 DOUBLE SWING DOOR, 04, THAT OPEN IN THE PATH OF EGRES
 SAND ENCROCHES/RESTRICT THE EXIT WIDTH OF STAIR # 2.
  
 PER NFPA 101 CHAPTER 7, MEANS OF EGRESS
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL
 LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED WIDTH OF
 AN AISLE, A CORRIDOR,
 A PASSAGEWAY, OR A LANDING UNOBSTRUCTED, UNLESS BOTH OF
 THE FOLLOWING
 CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING
 BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENT OF
 7.2.1.4.3.2.
 7.2.1.4.3.2 WHEN FULLY OPEN, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL
 NOT PROJECT MORE THAN 7 IN. (180 MM) INTO THE REQUIRED
 WIDTH OF AN AISLE,
 A CORRIDOR, A PASSAGEWAY, OR A LANDING, UNLESS THE DOOR
 LEAF IS EQUIPPED
 WITH AN APPROVED SELF-CLOSING DEVICE AND IS NOT
 REQUIRED BY THE PROVISIONS
 OF 7.2.1.4.2 TO SWING IN THE DIRECTION OF EGRESS
 TRAVEL.
  
  
 PLEASE REVIEW AND CORRECT.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2021-06-21 Cont ID  
Sent By abelisle Date 2021-06-21 Time 18:33 Rev Time 0.00
Received By abelisle Date 2021-06-21 Time 18:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-07-27 Cont ID  
Sent By rmcphers Date 2021-07-27 Time 11:21 Rev Time 0.00
Received By rmcphers Date 2021-07-20 Time 09:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-06-29 Cont ID  
Sent By rmcphers Date 2021-06-29 Time 08:58 Rev Time 0.00
Received By rmcphers Date 2021-05-28 Time 08:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-07-21 Cont ID  
Sent By medwards Date 2021-07-21 Time 07:38 Rev Time 0.00
Received By medwards Date 2021-07-21 Time 07:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-06-14 Cont ID  
Sent By medwards Date 2021-06-14 Time 09:14 Rev Time 0.00
Received By medwards Date 2021-06-14 Time 09:14 Sent To  
Notes
2021-06-14 09:14:551ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21051514
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR EACH
 SPACE IN THIS TENANT SPACE BASED ON FBC M 403.3.1.1 AND
 TABLE 403.3.1.1 AND NOT THE ARCHITECTURAL OCCUPANT
 LOAD. RTU 1&5 DINING AREA OUTDOOR AIR SHOULD BE 952
 CFM; RTU?S 2,3&4 OUTDOOR AIR SHOULD BE 1452 CFM.
  
 403.3.1.1OUTDOOR AIRFLOW RATE.
 VENTILATION SYSTEMS SHALL BE DESIGNED TO HAVE THE
 CAPACITY TO SUPPLY THE MINIMUM OUTDOOR AIRFLOW RATE,
 DETERMINED IN ACCORDANCE WITH THIS SECTION. IN EACH
 OCCUPIABLE SPACE, THE VENTILATION SYSTEM SHALL BE
 DESIGNED TO DELIVER THE REQUIRED RATE OF OUTDOOR
 AIRFLOW TO THE BREATHING ZONE. THE OCCUPANT LOAD
 UTILIZED FOR DESIGN OF THE VENTILATION SYSTEM SHALL BE
 NOT LESS THAN THE NUMBER DETERMINED FROM THE ESTIMATED
 MAXIMUM OCCUPANT LOAD RATE INDICATED IN TABLE
 403.3.1.1. VENTILATION RATES FOR OCCUPANCIES NOT
 REPRESENTED IN TABLE 403.3.1.1 SHALL BE THOSE FOR A
 LISTED OCCUPANCY CLASSIFICATION THAT IS MOST SIMILAR IN
 TERMS OF OCCUPANT DENSITY, ACTIVITIES AND BUILDING
 CONSTRUCTION; OR SHALL BE DETERMINED BY AN APPROVED
 ENGINEERING ANALYSIS. THE VENTILATION SYSTEM SHALL BE
 DESIGNED TO SUPPLY THE REQUIRED RATE OF VENTILATION AIR
 CONTINUOUSLY DURING THE PERIOD THE BUILDING IS
 OCCUPIED, EXCEPT AS OTHERWISE STATED IN OTHER
 PROVISIONS OF THE CODE.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-06-21 Cont ID  
Sent By abelisle Date 2021-06-21 Time 18:32 Rev Time 0.00
Received By abelisle Date 2021-06-15 Time 19:13 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-07-21 Cont ID  
Sent By medwards Date 2021-07-21 Time 07:47 Rev Time 0.00
Received By medwards Date 2021-07-21 Time 07:42 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-06-14 Cont ID  
Sent By medwards Date 2021-06-14 Time 09:29 Rev Time 0.00
Received By medwards Date 2021-06-14 Time 09:29 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-06-09 Cont ID  
Sent By aaponte Date 2021-06-09 Time 16:56 Rev Time 0.00
Received By aaponte Date 2021-06-09 Time 16:56 Sent To  
Notes
***NONE***