Plan Review Details - Permit 21051502
Plan Review Stops For Permit 21051502
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status N Date 2021-05-26 Cont ID  
Sent By shill Date 2021-05-26 Time 20:04 Rev Time 0.00
Received By shill Date 2021-05-26 Time 20:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-11-29 Cont ID  
Sent By pleduc Date 2021-11-29 Time   Rev Time 0.00
Received By pleduc Date 2021-11-29 Time 11:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-10-15 Cont ID  
Sent By pleduc Date 2021-10-15 Time   Rev Time 0.00
Received By pleduc Date 2021-10-15 Time 10:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-07-16 Cont ID  
Sent By pleduc Date 2021-07-16 Time   Rev Time 0.00
Received By pleduc Date 2021-07-16 Time 15:40 Sent To  
Notes
2021-07-16 16:02:14THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE INDICATIONS OF THE VENTS TERMINATING AT
 THE 2ND FLOOR LEVEL OF THE PARKING GARAGE.
  
 ADDITIONALLY, PLEASE PROVIDE DETAILS OR SPECS THAT THE
 3" PIPE SIZE IS SUFFIENCT FOR THIS TANK.
  
 PER NFPA 110
  
 7.10.2 EXHAUST SYSTEM INSTALLATION SHALL BE GASTIGHT TO
 PREVENT
 EXHAUST GAS FUMES FROM ENTERING INHABITED ROOMS OR
 BUILDINGS
 AND TERMINATE IN SUCH A MANNER THAT TOXIC FUMES CANNOT
 REENTER A BUILDING OR STRUCTURE, PARTICULARLY THROUGH
 WINDOWS,
 AIR VENTILATION INLETS, OR THE ENGINE AIR-INTAKE
 SYSTEM.
  
 PER NFPA 30
  
 22.6 VENT PIPING FOR ABOVEGROUND TANKS. PIPING FOR
 NORMAL
 AND EMERGENCY RELIEF VENTING SHALL BE CONSTRUCTED IN
 ACCORDANCE
 WITH CHAPTER 27.
  
 27.8.1 VENT PIPING FOR ABOVEGROUND STORAGE TANKS.
 27.8.1.1 WHERE THE OUTLETS OF VENT PIPES FOR TANKS
 STORING
 CLASS I LIQUIDS ARE ADJACENT TO BUILDINGS OR PUBLIC
 WAYS, THEY
 SHALL BE LOCATED SO THAT VAPORS ARE RELEASED AT A SAFE
 POINT
 OUTSIDE OF BUILDINGS AND NOT LESS THAN 12 FT (3.6 M)
 ABOVE THE
 ADJACENT GROUND LEVEL.
 27.8.1.2 VAPORS SHALL BE DISCHARGED UPWARD OR
 HORIZONTALLY
 AWAY FROM ADJACENT WALLS.
 27.8.1.3 VENT OUTLETS SHALL BE LOCATED SO THAT VAPORS
 WILL NOT BE
 TRAPPED BY EAVES OR OTHER OBSTRUCTIONS AND SHALL BE AT
 LEAST 5 FT
 (1.5 M) FROM BUILDING OPENINGS AND AT LEAST 15 FT (4.5
 M) FROM
 POWERED VENTILATION AIR INTAKE DEVICES.
  
 PLEASE REVIEW AND PROVIDE DETAILS FOR COMPLIANCE OR
 CORRECT.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
 7.10.2 EXHAUST SYSTEM INSTALLATION SHALL BE GASTIGHT TO
 PREVENT
 EXHAUST GAS FUMES FROM ENTERING INHABITED ROOMS OR
 BUILDINGS
 AND TERMINATE IN SUCH A MANNER THAT TOXIC FUMES CANNOT
 REENTER A BUILDING OR STRUCTURE, PARTICULARLY THROUGH
 WINDOWS,
 AIR VENTILATION INLETS, OR THE ENGINE AIR-INTAKE
 SYSTEM.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-11-29 Cont ID  
Sent By mpeterso Date 2021-11-29 Time 11:39 Rev Time 0.00
Received By lmarchan Date 2021-11-24 Time 11:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-11-22 Cont ID  
Sent By medwards Date 2021-11-22 Time 13:00 Rev Time 0.00
Received By medwards Date 2021-11-22 Time 13:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-10-28 Cont ID  
Sent By medwards Date 2021-10-28 Time 12:34 Rev Time 0.00
Received By medwards Date 2021-10-25 Time 09:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-10-19 Cont ID  
Sent By medwards Date 2021-10-19 Time 09:57 Rev Time 0.00
Received By medwards Date 2021-10-13 Time 07:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-07-30 Cont ID  
Sent By medwards Date 2021-07-30 Time 13:06 Rev Time 0.00
Received By medwards Date 2021-07-15 Time 10:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2021-11-29 Cont ID  
Sent By medwards Date 2021-11-29 Time 08:02 Rev Time 0.00
Received By medwards Date 2021-11-29 Time 08:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2021-11-22 Cont ID  
Sent By medwards Date 2021-11-22 Time 12:57 Rev Time 0.00
Received By medwards Date 2021-11-22 Time 12:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2021-10-28 Cont ID  
Sent By medwards Date 2021-10-28 Time 12:27 Rev Time 0.00
Received By medwards Date 2021-10-28 Time 12:27 Sent To  
Notes
2021-10-28 12:32:12PLEASE SEE PREVIOUS COMMENTS 1 AND 3 BELOW. I DO NOT
 SEE ANYTHING ON SHEET M1-01A ABOUT THE FUEL PIPING
 SYSTEM. PLEASE SHOW A DRAWING INDICATING THE PIPING
 MATERIAL, SIZE AND ROUTE FROM THE FILL LOCATION TO THE
 TANK INCLUDING ALL SHUT-OFF VALVES. FBC M 1305
  
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1.01A: PLEASE SHOW THE FUEL PIPING ON THE
 DRAWING. FBC M 1305
  
 3) THE FUEL OIL SUPPLY LINE SHALL HAVE A BUILDING SHUT
 OFF. FBC M 1307.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-10-19 Cont ID  
Sent By medwards Date 2021-10-19 Time 09:36 Rev Time 0.00
Received By medwards Date 2021-10-19 Time 09:36 Sent To  
Notes
2021-10-19 09:53:18PLEASE RESPOND TO THE 1ST CYCLE REVIEW COMMENTS LISTED
 BELOW:
  
  
 1ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21051502
  
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1.01A: PLEASE SHOW THE FUEL PIPING ON THE
 DRAWING. FBC M 1305
  
 3) THE FUEL OIL SUPPLY LINE SHALL HAVE A BUILDING SHUT
 OFF. FBC M 1307.1
  
 4) PLEASE PROVIDE INFORMATION ON THE EXHAUST SILENCER.
 FBC 107.2.1
  
 6) PLEASE PROVIDE INFORMATION ON THE FUEL TANK. FBC M
 1301.4
  
 7) PLEASE CONTACT DERM TO DETERMINE IF APPROVAL BY THEM
 IS REQUIRED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-07-30 Cont ID  
Sent By medwards Date 2021-07-30 Time 13:01 Rev Time 0.00
Received By medwards Date 2021-07-30 Time 13:01 Sent To  
Notes
2021-07-30 13:01:281ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21051502
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1.01A: PLEASE SHOW THE FUEL PIPING ON THE
 DRAWING. FBC M 1305
  
 2) VENT PIPING MUST MEET TERMINATION PROTECTION OF FBC
 M 1305.7
  
 3) THE FUEL OIL SUPPLY LINE SHALL HAVE A BUILDING SHUT
 OFF. FBC M 1307.1
  
 4) PLEASE PROVIDE INFORMATION ON THE EXHAUST SILENCER.
 FBC 107.2.1
  
 5) PLEASE PROVIDE INSTALLATION INSTRUCTIONS FOR THE
 VENTING OF THE FIRE PUMP. FBC 107.2.1
  
 6) PLEASE PROVIDE INFORMATION ON THE FUEL TANK. FBC M
 1301.4
  
 7) PLEASE CONTACT DERM TO DETERMINE IF APPROVAL BY THEM
 IS REQUIRED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2021-05-26 Cont ID  
Sent By shill Date 2021-05-26 Time 20:04 Rev Time 0.00
Received By shill Date 2021-05-26 Time 20:04 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date   Cont ID  
Sent By   Date 2021-11-24 Time   Rev Time 0.00
Received By mpeterso Date 2021-11-24 Time 11:32 Sent To  
Notes
2021-11-24 11:32:30SHEETS M1-01A AND SHEET M1-02A PASSED DIGNATURE REVIEW
 WITH DIGITAL SIGNATURE AND SEAL
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2021-11-22 Cont ID  
Sent By medwards Date 2021-11-22 Time 12:57 Rev Time 0.00
Received By medwards Date 2021-11-22 Time 12:57 Sent To  
Notes
2021-11-22 12:59:54SHEETS M1-01A AND SHEET M1-02A STILL NEED TO BEAR THE
 DIGITAL SIGNATURE OF THE DESIGNER.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-10-28 Cont ID  
Sent By medwards Date 2021-10-28 Time 12:33 Rev Time 0.00
Received By medwards Date 2021-10-28 Time 12:33 Sent To  
Notes
2021-10-28 12:34:08PLEASE SEE THE FIRST 2 CYCLE SIGNATURE REVIEW COMMENTS
 BELOW.
  
 PLEASE SEE 1ST REVIEW CYCLE COMMENTS BELOW:
  
 PLANS SUBMITTED DIGITALLY REQUIRE A DIGITAL SIGNATURE
 FROM THE DESIGNER.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-10-19 Cont ID  
Sent By medwards Date 2021-10-19 Time 09:56 Rev Time 0.00
Received By medwards Date 2021-10-19 Time 09:56 Sent To  
Notes
2021-10-19 09:57:04PLEASE SEE 1ST REVIEW CYCLE COMMENTS BELOW:
  
 PLANS SUBMITTED DIGITALLY REQUIRE A DIGITAL SIGNATURE
 FROM THE DESIGNER.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-07-30 Cont ID  
Sent By medwards Date 2021-07-30 Time 13:05 Rev Time 0.00
Received By medwards Date 2021-07-30 Time 13:05 Sent To  
Notes
2021-07-30 13:06:30PLANS SUBMITTED DIGITALLY REQUIRE A DIGITAL SIGNATURE
 FROM THE DESIGNER.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  