Plan Review Details - Permit 21051484
Plan Review Stops For Permit 21051484
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2021-06-18 Cont ID  
Sent By cpuell Date 2021-06-18 Time 08:57 Rev Time 0.00
Received By cpuell Date 2021-06-18 Time 08:57 Sent To  
Notes
2021-06-18 08:58:36NORTH BUILDING IS WHERE THE WORK IS BEING DONE, HALD
 ADDRESS HAS BEEN READDRESSED AT 124 ROOSEVELT PL

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2021-06-18 Cont ID  
Sent By cpuell Date 2021-06-18 Time 07:43 Rev Time 0.00
Received By cpuell Date 2021-06-18 Time 07:42 Sent To  
Notes
2021-06-18 07:44:54RESPONCE THAT WORK IS GOING TO BE DONE ON THE NORTH
 BUILDING, HOWEVER THE HALF ADDRESS SOUTH PROPERTY NEEDS
 TO BE READDRESSED, PLEASE HAVE OWNER CONTACT
 [email protected]

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-05-26 Cont ID  
Sent By cpuell Date 2021-05-26 Time 14:46 Rev Time 0.00
Received By cpuell Date 2021-05-26 Time 14:46 Sent To  
Notes
2021-05-26 14:47:43TWO BUILDINGS ON PARCEL, IS THE WORK FOR THE NORTH OR
 SOUTH BUILDING? SOUTH BUILDING HAS A HALF ADDRESS WHICH
 WILL NEED TO BE READDRESSED, PLEASE HAVE OWNER REACH
 OUT TO [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-08-06 Cont ID  
Sent By shill Date 2021-08-06 Time 07:18 Rev Time 0.00
Received By shill Date 2021-08-06 Time 07:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-07-14 Cont ID  
Sent By shill Date 2021-07-14 Time 16:51 Rev Time 0.00
Received By shill Date 2021-07-14 Time 16:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2021-06-18 Cont ID  
Sent By shill Date 2021-06-18 Time 12:14 Rev Time 0.00
Received By shill Date 2021-06-18 Time 12:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-07-13 Cont ID  
Sent By jleahy Date 2021-07-13 Time 16:06 Rev Time 0.00
Received By jleahy Date 2021-07-13 Time 15:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-06-09 Cont ID  
Sent By jleahy Date 2021-06-09 Time 11:25 Rev Time 0.00
Received By jleahy Date 2021-06-09 Time 11:08 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2021-06-03 Cont ID  
Sent By cwalker Date 2021-06-03 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-08-06 Cont ID  
Sent By shill Date 2021-08-06 Time 07:18 Rev Time 0.00
Received By shill Date 2021-07-28 Time 08:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-07-14 Cont ID  
Sent By shill Date 2021-07-14 Time 16:51 Rev Time 0.00
Received By shill Date 2021-07-08 Time 12:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-06-18 Cont ID  
Sent By shill Date 2021-06-18 Time 12:14 Rev Time 0.00
Received By shill Date 2021-05-27 Time 13:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-08-02 Cont ID  
Sent By medwards Date 2021-08-02 Time 13:26 Rev Time 0.00
Received By medwards Date 2021-08-02 Time 13:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-07-12 Cont ID  
Sent By hmoser Date 2021-07-12 Time 14:46 Rev Time 0.00
Received By hmoser Date 2021-07-12 Time 14:04 Sent To  
Notes
2021-07-12 14:45:24PLAN DENIED
 PAGE D-01 WAS NOT SUBMITTED WITH RE-SUB.
 PLEASE PROVIDE THE AIR CONDITIONING DUCT DRAWING
 AND EQUIPMENT SCHEDULE IF REQUIRED. FBC 107.2.1
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-06-11 Cont ID  
Sent By medwards Date 2021-06-11 Time 07:49 Rev Time 0.00
Received By medwards Date 2021-06-11 Time 07:49 Sent To  
Notes
2021-06-11 07:49:281ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21051484
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SHOW THE DRYER HAS MAKE UP AIR. FBC M 504.6
  
 2) PLEASE SHOW ANY NEW DUCTWORK FOR THIS NEW AREA. FBC
 107.2.1
  
 3) PLEASE SHOW THE BATH EXHAUST FAN AND DUCTWORK
 TERMINATION LOCATION. FBC RES R303.3
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-07-14 Cont ID  
Sent By abelisle Date 2021-07-14 Time 14:54 Rev Time 0.00
Received By abelisle Date 2021-07-14 Time 14:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-06-10 Cont ID  
Sent By lcrespo Date 2021-06-10 Time 09:44 Rev Time 0.00
Received By lcrespo Date 2021-06-10 Time 09:26 Sent To  
Notes
2021-06-10 09:44:3006/10/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE PROVIDE A PLUMBING ISOMETRIC RISER DIAGRAM
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12)
 RESIDENTIAL PLUMBING.
  
 2. PLEASE PROVIDE A SOURCE OF HOT WATER AND THE
 LOCATION OF CONNECTION PER THE 2020 FBC SEC. FBC R
 2722.2.
  
 3. SIGNED AND SEALED DRAWINGS NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR -
 IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF THE ORIGINAL SIGNED AND
 SEALED DOCUMENT ALONG WITH A "PLAN REVIEW REQUEST FORM"
 EXPLAINING THE REASON FOR SUBMITTING THE DOCUMENT OR
 DRAWINGS. THE PLAN REVIEW REQUEST FORM CAN BE OBTAINED
 BY EMAILING [email protected] AND ASKING FOR THE FORM.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-08-06 Cont ID  
Sent By shill Date 2021-08-06 Time 07:18 Rev Time 0.00
Received By shill Date 2021-08-06 Time 07:18 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2021-07-14 Time   Rev Time 0.00
Received By   Date 2021-07-14 Time   Sent To  
Notes
2021-07-14 16:50:57PLEASE PROVIDE ORIGINAL DIGITALLY SIGNED DRAWINGS FROM
 THE DESIGNER OR BRING ORIGINAL SIGNED AND SEALED PAPER
 DRAWINGS TO OUR OFFICE.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-06-11 Cont ID  
Sent By medwards Date 2021-06-11 Time 07:50 Rev Time 0.00
Received By medwards Date 2021-06-11 Time 07:50 Sent To  
Notes
2021-06-11 07:58:55PLEASE PROVIDE ORIGINAL DIGITALLY SIGNED DRAWINGS FROM
 THE DESIGNER OR BRING ORIGINAL SIGNED AND SEALED PAPER
 DRAWINGS TO OUR OFFICE.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  