| 2021-07-15 13:31:41 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THERE IS AN INDICATIONOF A TIKI HUT OVER AN ASSEMBLY |
| | OCCUPANCY, TIKI HUTS ARE CONSTRUCTED OF COMBUSTIBLE |
| | VEGITATION |
| | |
| | PER NFPA 1 |
| | |
| | 3.3.56 COMBUSTIBLE (MATERIAL). A MATERIAL THAT, IN THE |
| | FORM IN |
| | WHICH IT IS USED AND UNDER THE CONDITIONS ANTICIPATED, |
| | WILL |
| | IGNITE AND BURN; A MATERIAL THAT DOES NOT MEET THE |
| | DEFINITION |
| | OF NONCOMBUSTIBLE OR LIMITED-COMBUSTIBLE. |
| | |
| | CHAPTER 10 GENERAL SAFETY REQUIREMENTS |
| | |
| | 10.1 FUNDAMENTAL REQUIREMENTS. |
| | |
| | 10.1.1 EVERY NEW AND EXISTING BUILDING OR STRUCTURE |
| | SHALL BE |
| | CONSTRUCTED, ARRANGED, EQUIPPED, MAINTAINED, AND |
| | OPERATED |
| | IN ACCORDANCE WITH THIS CODE SO AS TO PROVIDE A |
| | REASONABLE LEVEL |
| | OF LIFE SAFETY, PROPERTY PROTECTION, AND PUBLIC WELFARE |
| | FROM THE |
| | ACTUAL AND POTENTIAL HAZARDS CREATED BY FIRE, |
| | EXPLOSION, AND |
| | OTHER HAZARDOUS CONDITIONS. |
| | |
| | 10.13 COMBUSTIBLE VEGETATION. |
| | |
| | 10.13.1 COMBUSTIBLE VEGETATION, INCLUDING NATURAL CUT |
| | CHRISTMAS TREES, SHALL BE IN ACCORDANCE WITH SECTION |
| | 10.13. |
| | |
| | 10.13.3* PROVISIONS FOR FIRE RETARDANCE FOR ARTIFICIAL |
| | VEGETATION. |
| | |
| | 10.13.3.1 ARTIFICIAL VEGETATION AND ARTIFICIAL |
| | CHRISTMAS TREES |
| | SHALL BE LABELED OR OTHERWISE IDENTIFIED OR CERTIFIED |
| | BY THE |
| | MANUFACTURER AS BEING FIRE RETARDANT. |
| | |
| | 10.13.3.2 SUCH FIRE RETARDANCE SHALL BE DEMONSTRATED BY |
| | EACH |
| | INDIVIDUAL DECORATIVE VEGETATION ITEM, INCLUDING ANY |
| | DECORATIVE |
| | LIGHTING, IN AN APPROVED MANNER. |
| | |
| | CHAPTER 20 OCCUPANCY FIRE SAFETY |
| | |
| | 20.1 ASSEMBLY OCCUPANCIES. |
| | 20.1.1 APPLICATION. NEW AND EXISTING ASSEMBLY |
| | OCCUPANCIES |
| | SHALL COMPLY WITH SECTION 20.1 AND NFPA 101. |
| | 20.1.1.1 PERMITS. PERMITS, WHERE REQUIRED, SHALL COMPLY |
| | WITH |
| | SECTION 1.12. |
| | 20.1.1.2 INDOOR CHILDREN?S PLAYGROUND STRUCTURES SHALL |
| | ALSO |
| | COMPLY WITH SECTION 10.19. |
| | 20.1.2 FLAME-RETARDANT REQUIREMENTS. |
| | 20.1.2.1 COMBUSTIBLE SCENERY OF CLOTH, FILM, VEGETATION |
| | (DRY), |
| | AND SIMILAR MATERIALS SHALL COMPLY WITH ONE OF THE |
| | FOLLOWING: |
| | (1) THEY SHALL MEET THE FLAME PROPAGATION PERFORMANCE |
| | CRITERIA |
| | CONTAINED IN TEST METHOD 1 OR TEST METHOD 2, AS |
| | APPROPRIATE, OF NFPA 701, STANDARD METHODS OF FIRE |
| | TESTS FOR |
| | FLAME PROPAGATION OF TEXTILES AND FILMS. |
| | (2) THEY SHALL EXHIBIT A HEAT RELEASE RATE NOT |
| | EXCEEDING 100 KW |
| | WHEN TESTED IN ACCORDANCE WITH NFPA 289, STANDARD |
| | METHOD |
| | OF FIRE TEST FOR INDIVIDUAL FUEL PACKAGES, USING THE 20 |
| | KW IGNITION |
| | SOURCE. [101: 12.4.6.11.1; 101: 13.4.6.11.1] |
| | |
| | PLEASE PROVIDE FIRE RETARDANCE CERTIFICATION DETAILS |
| | PER THE REQUIRED ZCODE REFERENCES. |
| | |
| | |
| | |
| | 2) THERE ARE EXISTING EXIT DOOR LEADING OUT TO UNDER |
| | THE PROPOSED TIKI. |
| | |
| | THERE ARE NO INDICATIONS OF LIGHTING, EXIT ACCESS |
| | ILLUMINATION OR EMERGENCY LIGHTING UNDER THE TIKI. |
| | |
| | 10.13.5 ONLY LISTED ELECTRICAL LIGHTS AND WIRING SHALL |
| | BE USED |
| | ON NATURAL OR ARTIFICIAL COMBUSTIBLE VEGETATION, |
| | NATURAL OR ARTIFICIAL |
| | CHRISTMAS TREES, AND OTHER SIMILAR DECORATIONS. |
| | |
| | NFPA 101 |
| | |
| | 7.8 ILLUMINATION OF MEANS OF EGRESS |
| | |
| | 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE |
| | PROVIDED IN ACCORDANCE |
| | WITH SECTION 7.8 FOR EVERY BUILDING AND STRUCTURE WHERE |
| | REQUIRED IN |
| | CHAPTERS 11 THROUGH 43. FOR THE PURPOSES OF THIS |
| | REQUIREMENT, EXIT ACCESS |
| | SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES, |
| | CORRIDORS, RAMPS, ESCALATORS, |
| | AND PASSAGEWAYS LEADING TO AN EXIT. FOR THE PURPOSES OF |
| | THIS REQUIREMENT, |
| | EXIT DISCHARGE SHALL INCLUDE ONLY DESIGNATED STAIRS, |
| | AISLES, CORRIDORS, |
| | RAMPS, ESCALATORS, WALKWAYS, AND PASSAGEWAYS LEADING TO |
| | A PUBLIC WAY. |
| | |
| | 7.9 EMERGENCY LIGHTING |
| | |
| | 7.9.1.1* EMERGENCY LIGHTING FACILITIES FOR MEANS OF |
| | EGRESS SHALL BE |
| | PROVIDED IN ACCORDANCE WITH SECTION 7.9 FOR THE |
| | FOLLOWING: |
| | (1) BUILDINGS OR STRUCTURES WHERE REQUIRED IN CHAPTERS |
| | 11 THROUGH 43 |
| | |
| | |
| | PLEASE REVIEW AND PROVIDE LIGHTING THAT MEETS THE |
| | REQUIREMENTS OF THE CODE |
| | |
| | |
| | |
| | 3) FOR INFORMATIONAL PURPOSES PLEASE BE ADVISED OF THE |
| | RESTRICTIONS UNDER THE TIKI HUT |
| | |
| | 10.13.7 OPEN FLAMES SUCH AS FROM CANDLES, LANTERNS, |
| | KEROSENE |
| | HEATERS, AND GAS-FIRED HEATERS SHALL NOT BE LOCATED ON |
| | OR |
| | NEAR COMBUSTIBLE VEGETATION, CHRISTMAS TREES, OR OTHER |
| | SIMILAR |
| | COMBUSTIBLE MATERIALS. |
| | 10.13.8 COMBUSTIBLE VEGETATION AND NATURAL CUT |
| | CHRISTMAS |
| | TREES SHALL NOT BE LOCATED NEAR HEATING VENTS OR OTHER |
| | FIXED OR |
| | PORTABLE HEATING DEVICES THAT COULD CAUSE IT TO DRY OUT |
| | PREMATURELY |
| | OR TO BE IGNITED. |
| | |
| | |
| | |
| | |
| | 4) THERE ARE NO TABLES OR CHAIRS INDICATED. |
| | |
| | PLEASE PROVIDE A PROPOSED SEATING PLAN OR PROOVIDE A |
| | COMMENTS STATING THE INTENTION OF THE OUTDOOR AREA. |
| | |
| | |
| | |
| | 5) THERE ARE INDICATIONS OF AN EXISTING AWNING FRAME |
| | WITH A VINYL REPLACEMNT. |
| | |
| | PLEASE CLARIFY THE LOCATION OF THE EXISTING FRAME AND |
| | PROVIDE A FLAME SPREAD CERTIFICATE OF THE REPLACEMENT |
| | VINYL. |
| | |
| | |
| | |
| | |
| | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |