Plan Review Details - Permit 21051441
Plan Review Stops For Permit 21051441
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-06-02 Cont ID  
Sent By cpuell Date 2021-06-02 Time 09:29 Rev Time 0.00
Received By cpuell Date 2021-06-02 Time 09:29 Sent To  
Notes
2021-06-02 09:30:56FULL FLOOR PLAN GIVEN FOR THE WHOLE BUILDING, UPDATED
 IN ALL DATABASES.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-05-28 Cont ID  
Sent By cpuell Date 2021-05-28 Time 09:17 Rev Time 0.00
Received By cpuell Date 2021-05-28 Time 09:17 Sent To  
Notes
2021-05-28 09:29:09SUITE 400 IS NOT CURRENTLY IN OUR SYSTEM, PLEASE A
 FLOOR PLAN FOR THE WHOLE FLOOR INCLUDING ANY OTHER
 SUITES ON THE FLOOR, PLEASE PROVIDE THE SUITE NUMBERS
 FOR THE OTHER SUITES ON THAT FLOOR. WHICH FLOOR LEVEL
 IS THIS SUITE ON? PLEASE EMAIL [email protected] WITH
 RESPONSES.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2021-06-09 Cont ID  
Sent By rmcphers Date 2021-06-09 Time 08:07 Rev Time 0.00
Received By rmcphers Date 2021-06-09 Time 08:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-06-24 Cont ID  
Sent By rmcphers Date 2021-06-24 Time 09:24 Rev Time 0.00
Received By rmcphers Date 2021-06-24 Time 09:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-06-09 Cont ID  
Sent By rmcphers Date 2021-06-09 Time 08:07 Rev Time 0.00
Received By rmcphers Date 2021-06-08 Time 11:51 Sent To  
Notes
2021-06-09 08:05:39OFFICE RENO
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DOOR MARKED 101 DOES NOT SHOW ON THE DOOR SCHEDULE
 CORRECTLY.
 2) DOOR 101 AND 117 - PLEASE SHOW THE HOURLY FIRE
 RATING PER FBC 716.5
 3) PLEASE SHOW FIRE RATED DOOR TO SELF CLOSE AND LATCH
 PER FBC 716.5.9
 4) PLEASE SHOW GLAZING IN FIRE RATED DOORS TO COMPLY
 WITH FBC 716.5.8
 5) PLEASE SHOW FLOORING (CARPET) TO COMPLY WITH FBC
 804.4
 6) PLEASE SHOW THE ACCESSIBLE DINING AREA TO COMPLY
 WITH FBC 902 (COUNTER HEIGHT - KNEE AND TOE CLEARANCES
 - CLEAR FLOOR SPACE ETC.)
 7) PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE KITCHEN
 APPLIANCES TO COMPLY WITH FBC 804.6
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-06-07 Cont ID  
Sent By jleahy Date 2021-06-07 Time 17:28 Rev Time 0.00
Received By jleahy Date 2021-06-07 Time 17:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-06-22 Cont ID  
Sent By pleduc Date 2021-06-22 Time   Rev Time 0.00
Received By pleduc Date 2021-06-22 Time 10:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-06-04 Cont ID  
Sent By pleduc Date 2021-06-04 Time   Rev Time 0.00
Received By pleduc Date 2021-06-04 Time 10:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-07-26 Cont ID  
Sent By lcrespo Date 2021-07-26 Time 09:07 Rev Time 0.00
Received By lcrespo Date 2021-07-21 Time 14:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-06-25 Cont ID  
Sent By rmcdouga Date 2021-06-25 Time 08:00 Rev Time 0.00
Received By rmcdouga Date 2021-06-21 Time 16:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-06-09 Cont ID  
Sent By rmcphers Date 2021-06-09 Time 08:11 Rev Time 0.00
Received By rmcphers Date 2021-05-27 Time 12:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-06-08 Cont ID  
Sent By medwards Date 2021-06-08 Time 08:49 Rev Time 0.00
Received By medwards Date 2021-06-08 Time 08:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-07-26 Cont ID  
Sent By lcrespo Date 2021-07-26 Time 09:06 Rev Time 0.00
Received By lcrespo Date 2021-07-26 Time 08:37 Sent To  
Notes
2021-07-26 09:07:2707/26/21 REVIEWED FOR CODE COMPLIANCE
 (PLUMBING/BACKFLOW)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-06-24 Cont ID  
Sent By jesmith Date 2021-06-24 Time 11:37 Rev Time 0.00
Received By jesmith Date 2021-06-24 Time 09:14 Sent To  
Notes
2021-06-24 11:30:462ND REVIEW
 PLUMBING COMMENTS: DENIED
 1.PER WPB FBC 107.2.1, PROVIDE INVERT ELEVATIONS IN
 FEET AND INCHES ABOVE THE THIRD FLOOR FINISH FLOOR OF
 NEW HORIZONTAL SANITARY BRANCH AT NEW SINK AND AT
 CONNECTION TO EXISTING SANITARY. PROVIDE DEVELOPED
 LENGTH OF THE SAME (IT APPEARS TO BE APPROXIMATELY 100
 FEET). AT 1/4 INCH PER FOOT FALL/2% SLOPE AS REQUIRED
 BY FBC PL 704.1 AND TABLE 704.1 FOR 2 INCH HORIZONTAL
 DRAINAGE PIPE, THIS WOULD AMOUNT TO TWO (2) FEET OF
 UNIFORM SLOPE.
 RESPONSE PROVIDED INDICATES ONE (1) FOOT OF UNIFORM
 SLOPE WHICH AMOUNTS TO 1/8 INCH PER FOOT FALL/1% SLOPE.
 PER FBC PL 704.1 AND TABLE 704.1, HORIZONTAL DRAINAGE
 PIPE SHALL BE 3 INCH SIZE.
  
 2. PER WPB FBC 107.2.1, PROVIDE A UL ASSEMBLY FOR NEW
 WALL PENETRATION(S) FROM COMMON AREA(S) TO TENANT
 SPACE(S). COMPLY WITH FBC CHAPTER 7.
 RESPONDED: THE UL ASSEMBLY PROVIDED FOR THE FOR NEW
 WALL PENETRATION(S) FROM COMMON AREA(S) TO TENANT
 SPACE(S) ON P4.2 IS FOR A CONCRETE WALL.
 AD1.1 DEMO PLAN KEY-NOTE 3 DESCRIPTION OF DEMO
 INDICATES THE WALL IN QUESTION IS A FRAMED WALL.
 A5.1 DETAIL 1 PROVIDES FOR A FRAMED 1 HOUR RATED WALL.
 DETAIL 4 INDICATES AN EXISTING CMU WALL.
 PER WPB FBC 107.2.1, CLARIFY AND PROVIDE THE ASSEMBLY
 THAT ADDRESSES THE WALL IN QUESTION.
  
 3.P2.1; NOTE 2: PER WPB FBC 107.2.1,
 A) PROVIDE MANUFACTURER SPECIFICATION/INSTALLATION
 MANUAL FOR THE ICE MAKER, FILTRATION SYSTEM, COFFEE
 MAKER WHICH WOULD INDICATE THEY ARE PROVIDED WITH
 INTERNAL BACKFLOW PREVENTION DEVICES. IF EQUIPMENT DOES
 NOT MEET THE CRITERIA NOTED, THEN PROVIDE LEAD FREE
 BACKFLOW PREVENTION DEVICES TO COMPLY WITH FBC PL
 SECTION 608. ADDITIONALLY, IF ANY OF THE EQUIPMENT
 REQUIRES DRAINS THEN PROVISION COMPLYING WITH FBC PL
 CHAPTERS 7,8,9 AND 10 SHALL BE MADE AND DETAILS
 PROVIDED.
 B) COMPLIED
  
 4. NOT REQUIRED; SEE IBC PLUMBING COMMENTARY DOWN-FEED
 PIPES 606.1(5) PROVIDED BY DESIGNER. ALSO SEE FBC PL
 CHAPTER 2 DEFINITIONS "WATER PIPE; RISER"
  
  
 5.COMPLIED
  
 6. PER FBC PL 606.2, PROVIDE SEPARATE SHUT OFF VALVE
 FOR HOT AND COLD TO FIXTURE AND TO THE TANKLESS WATER
 HEATER
 RESPONDED: NOT COMPLIANT; SEE REDLINED P4.1 FOR
 CLARIFICATION
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-06-08 Cont ID  
Sent By jesmith Date 2021-06-08 Time 12:25 Rev Time 0.00
Received By jesmith Date 2021-06-08 Time 08:28 Sent To  
Notes
2021-06-08 12:24:10CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 1.PER WPB FBC 107.2.1, PROVIDE INVERT ELEVATIONS IN
 FEET AND INCHES ABOVE THE THIRD FLOOR FINISH FLOOR OF
 NEW HORIZONTAL SANITARY BRANCH AT NEW SINK AND AT
 CONNECTION TO EXISTING SANITARY. PROVIDE DEVELOPED
 LENGTH OF THE SAME (IT APPEARS TO BE APPROXIMATELY 100
 FEET). AT 1/4 INCH PER FOOT FALL/2% SLOPE AS REQUIRED
 BY FBC PL 704.1 AND TABLE 704.1 FOR 2 INCH HORIZONTAL
 DRAINAGE PIPE, THIS WOULD AMOUNT TO TWO (2) FEET OF
 UNIFORM SLOPE.
  
 2. PER WPB FBC 107.2.1, PROVIDE A UL ASSEMBLY FOR NEW
 WALL PENETRATION(S) FROM COMMON AREA(S) TO TENANT
 SPACE(S). COMPLY WITH FBC CHAPTER 7.
  
 3.P2.1; NOTE 2: PER WPB FBC 107.2.1,
 A) PROVIDE MANUFACTURER SPECIFICATION/INSTALLATION
 MANUAL FOR THE ICE MAKER, FILTRATION SYSTEM, COFFEE
 MAKER WHICH WOULD INDICATE THEY ARE PROVIDED WITH
 INTERNAL BACKFLOW PREVENTION DEVICES. IF EQUIPMENT DOES
 NOT MEET THE CRITERIA NOTED, THEN PROVIDE LEAD FREE
 BACKFLOW PREVENTION DEVICES TO COMPLY WITH FBC PL
 SECTION 608. ADDITIONALLY, IF ANY OF THE EQUIPMENT
 REQUIRES DRAINS THEN PROVISION COMPLYING WITH FBC PL
 CHAPTERS 7,8,9 AND 10 SHALL BE MADE AND DETAILS
 PROVIDED.
 B) PROVIDE A SCHEMATIC TO CLEARLY SHOW THE COLD WATER
 FLOW TO ALL OF THE DEVICES, EQUIPMENT AND FIXTURES.
 SHOW PLACEMENT OF BACKFLOW PREVENTER, VALVES AND WATER
 FILTER AS THEY RELATE TO ALL OF THE DEVICES, EQUIPMENT
 AND FIXTURES.
  
 4.PER FBC PL 606.1(5), PROVIDE FULL OPEN VALVES AT THE
 TOP OF THE WATER DOWN FEED PIPES.
  
 5.PER FBC PL 606.1(2), PROVIDE FULL OPEN VALVE UPSTREAM
 OF COMMON/TENANT WALL PENETRATION TO BE ACCESSIBLE TO
 BUILDING MAINTENANCE AT ANYTIME.
  
 6.PER FBC PL 606.2, PROVIDE SEPARATE SHUT OFF VALVE FOR
 HOT AND COLD TO FIXTURE AND TO THE TANKLESS WATER
 HEATER
  
 7.P4.1; PLUMBING FIXTURE CONNECTION SCHEDULE: PER FBC
 PL TABLE 709.1, FIXTURE DRAINS AND TRAP SIZE FOR SINKS
 SHALL BE 1-1/2 INCH MINIMUM.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21051441 205 DATURA ST # 400
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-07-26 Cont ID  
Sent By lcrespo Date 2021-07-26 Time 09:07 Rev Time 0.00
Received By lcrespo Date 2021-07-26 Time 09:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-06-24 Cont ID  
Sent By rmcphers Date 2021-06-24 Time 09:25 Rev Time 0.00
Received By rmcphers Date 2021-06-24 Time 09:25 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-06-09 Cont ID  
Sent By rmcphers Date 2021-06-09 Time 08:11 Rev Time 0.00
Received By rmcphers Date 2021-06-09 Time 08:11 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2021-06-03 Cont ID  
Sent By ajones Date 2021-06-03 Time 15:39 Rev Time 0.00
Received By ajones Date 2021-06-03 Time 15:39 Sent To  
Notes
***NONE***