| Plan Review Stops For Permit 21051400 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2021-09-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-09-14 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-09-14 |
Time |
14:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-07-01 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-07-01 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-07-01 |
Time |
16:26 |
Sent To |
|
|
| Notes |
| 2021-07-01 16:25:24 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. THE ADDRESS OF | | | THE PROJECT IS ALSO REQUIRED ON THE DRAWINGS. | | | | | | 2) PROVIDE STRUCTURAL FRAMING PLANS. SPECIFY THE | | | SPACING OF FRAMING MEMBERS, ATTACHMENTS, FASTENERS, | | | BRACING, THE NUMBER AND LOCATION OF ANCHORS THAT WILL | | | SECURE THE KITCHEN CABINETS TO THE SLAB, ETC. PROVIDE | | | SECTIONS AND DETAILS AS NECESSARY TO FULLY AND CLEARLY | | | DESCRIBE THE PROPOSED WORK. FBC AMEND. 107.2.1 | | | | | | 3) SPECIFY THE WIND DESIGN DATA ON THE STRUCTURAL | | | DRAWINGS. FBC-R 301 | | | | | | 4) THE SURVEY INDICATES THAT THE KITCHEN WILL BE | | | INSTALLED UNDER A PAVILION. PROVIDE DETAILS OF THE | | | PAVILION AND THE CONCRETE SLAB? WHERE THE OUTDOOR | | | KITCHEN WILL BE INSTALLED. SPECIFICALLY THE MATERIALS | | | OF THE CEILING ABOVE THE GRILL, THE CLEARANCES FROM THE | | | COOKING EQUIPMENT TO THE CEILING. SPECIFY THE FLOOR | | | MATERIAL, THICKNESS, ETC. IS THIS PAVILION AN EXISTING | | | STRUCTURE? WAS IT PERMITTED AND INSPECTED? | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2021-08-30 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2021-08-30 |
Time |
22:46 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2021-08-30 |
Time |
21:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2021-05-27 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2021-05-27 |
Time |
22:38 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2021-05-27 |
Time |
21:24 |
Sent To |
|
|
| Notes |
| 2021-05-27 22:38:37 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE SPEC SHEETS SHOWING UL OR OTHER NRTL LISTING | | | OF POP UP RECEPTACLES. NEC110.3B | | | | | | 2. RECEPTACLE OUTLET SPACING DOES NOT CONFORM WITH NEC | | | 210.52.. | | | | | | 3. SMALL APPLIANCE CIRCUITS ARE TO BE MINIMUM 20AMPS. | | | NEC 210.52B1 | | | | | | 4. PROVIDE LOAD CALCULATION SHOWING EXISTING AND NEW | | | LOADS. NEC220 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | | UILDING-PERMIT-FORMS | | | | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL:561-805-6744 | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2021-09-13 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-08-27 |
Time |
11:17 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-08-27 |
Time |
10:06 |
Sent To |
|
|
| Notes |
| 2021-08-27 11:17:42 | GAS RISER UNDER REV- 20121053 TO MASTER- 20091091. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2021-07-08 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-07-08 |
Time |
09:13 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-07-08 |
Time |
07:25 |
Sent To |
|
|
| Notes |
| 2021-07-08 09:13:53 | 1ST REVIEW FBC-2020 RES. GAS | | | PERMIT- 21051400 | | | 7/8/2021 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) GAS FOR A FUTURE BBQ WAS APPROVED UNDER REVISION | | | 21021053 TO MASTER 20091091. THE APPROVED DRAWINGS FOR | | | THOSE PERMITS SHOW A GAS LINE TERMINATING AT THE NW | | | CORNER OF THE PROPERTY HOWEVER THE PROPOSED GRILL | | | LOCATION IS SHOWN UNDER A PAVILION LOCATED FURTHER | | | SOUTH OF THE CORNER. PLEASE PROVIDE A COMPLETE GAS | | | RISER DRAWING THAT INCLUDES THE TOTAL PIPING RUN FROM | | | THE NEW TANK TO THE GRILL- SECTIONS G2412.3 & G2412.4 | | | FBC RES. PLEASE SHOW THE RISER AT THE GRILL LOCATION, | | | AND THE LOCATIONS OF THE DRIP LEG, SHUT OFF VALVE, | | | REGULATOR AND PIPE UNIONS- SECTIONS G2419, G2420, | | | G2421, G2422 FBC RES. | | | | | | 2) I RESEARCHED THE USE AND CARE MANUAL FOR THE LYNX | | | GRILL MODEL L36TR AND ON PAGE 6 THESE WARNINGS FROM THE | | | MANUFACTURER ARE LISTED- | | | 6. NEVER LOCATE THE GRILL UNDER A ROOF OR OVERHANG, IN | | | A BUILDING, GARAGE, SHED OR OTHER SUCH ENCLOSED AREA. | | | 7. NEVER LOCATE THE GRILL UNDER UNPROTECTED COMBUSTIBLE | | | CONSTRUCTION. | | | BASED ON THOSE MANUFACTURER'S WARNINGS AND SECTION | | | G2447.1 OF THE FBC RES, IT APPEARS THE GRILL MAY NOT BE | | | SAFELY LOCATED UNDER THE PAVILION. | | | SECTION G2447.1 COOKING APPLIANCES STATES: | | | COOKING APPLIANCES THAT ARE DESIGNED FOR PERMANENT | | | INSTALLATION, INCLUDING RANGES, OVENS, STOVES, | | | BROILERS, GRILLS, FRYERS, GRIDDLES, HOT PLATES AND | | | BARBECUES, SHALL BE TESTED IN ACCORDANCE WITH ANSI | | | Z21.1 OR ANSI Z21.58 AND SHALL BE INSTALLED IN | | | ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS. | | | | | | PLEASE CONSULT WITH THE MANUFACTURER FOR ADDITIONAL | | | INFORMATION AS TO WHERE THE GRILL CAN BE SAFELY | | | LOCATED. | | | | | | 3) PLEASE CLARIFY IF THE PAVILION IS AN EXISTING OR NEW | | | STRUCTURE. THE CURRENT PROPERTY APPRAISER'S MAP DOES | | | NOT APPEAR TO SHOW A PAVILION ON THE LOT. PLEASE NOTE | | | COMPLETE PLANS UNDER A SEPARATE PERMIT WOULD BE | | | REQUIRED FOR A NEW STRUCTURE- SECTION 107.2.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-09-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-09-14 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-08-19 |
Time |
14:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2021-07-08 |
Time |
|
Rev Time |
0.00 |
| Received By |
cdecoeur |
Date |
2021-05-26 |
Time |
06:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2021-08-27 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-08-27 |
Time |
13:11 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-08-27 |
Time |
13:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
2021-08-27 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-08-27 |
Time |
10:18 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-08-27 |
Time |
10:06 |
Sent To |
|
|
| Notes |
| 2021-08-27 10:20:03 | NO SINK OR PLUMBING INSTALLATIONS IN OUTDOOR KITCHEN. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2021-07-08 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-07-08 |
Time |
09:16 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-07-08 |
Time |
07:25 |
Sent To |
|
|
| Notes |
| 2021-07-08 09:17:06 | 1ST REVIEW FBC-2020 RES. PLUMBING | | | PERMIT- 21051400 | | | 7/8/2021 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE CLARIFY IF AN OUTDOOR SINK WILL BE INSTALLED | | | TO SERVICE THE NEW SUMMER KITCHEN UNDER THIS PERMIT. | | | PROVIDE EITHER PLUMBING PLANS FOR NEW FIXTURE | | | INSTALLATIONS, OR A NOTE ON THE SURVEY PLAN INDICATING | | | THAT NO PLUMBING TO BE INSTALLED- SECTION 107.2.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2021-09-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-09-14 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-09-14 |
Time |
14:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
N |
Date |
2021-07-01 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-07-01 |
Time |
16:29 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-07-01 |
Time |
16:29 |
Sent To |
|
|
| Notes |
| 2021-07-01 16:29:54 | NO ARCHITECT OR ENGINEER FOR THIS PROJECT. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2021-09-10 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2021-09-10 |
Time |
16:01 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2021-09-10 |
Time |
16:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2021-09-01 |
|
|
Cont ID |
|
| Sent By |
kalexand |
Date |
2021-09-01 |
Time |
12:18 |
Rev Time |
0.00 |
| Received By |
kalexand |
Date |
2021-09-01 |
Time |
12:17 |
Sent To |
|
|
| Notes |
| 2021-09-01 12:22:51 | ZONING PLAN REVIEW | | | ________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | PREVIOUS ZONING COMMENTS NOT FULLY ADDRESSED. | | | 1. INDICATE SETBACKS FROM PROPOSED WORKS TO ADJACENT | | | PROPERTY LINES. | | | | | | 2. PLEASE SUBMIT A WRITTEN APPROVAL FROM THE BEAR LAKES | | | ESTATE NORTH ARCHITECTURAL REVIEW BOARD (A.R.B.). | | | PURSUANT TO THE BEAR LAKES ESTATE NORTH DECLARATION OF | | | COVENANTS AND RESTRICTIONS, SECTION VII, ARCHITECTURAL | | | CONTROLS, SUBSECTION A - A.R.B. REVIEW. PRIOR TO THE | | | ISSUANCE OF A BUILDING PERMIT FOR ANY CONSTRUCTION, | | | PLANS FOR THAT CONSTRUCTION MUST BE SUBMITTED AND | | | APPROVED IN WRITING BY THE A.R.B. | | | _____________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD | | | LIKE TO RESUBMIT ELECTRONICALLY, EMAIL | | | [email protected] AND REQUEST TO HAVE YOUR | | | PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOG | | | IN INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL. | | | PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU | | | ARE FINISHED UPLOADING. | | | ________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | | | | ANGELLA JONES-VANN, PLANNING & ZONING ADMINISTRATOR | | | P: 561.822.1441 | | | E: [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2021-06-17 |
|
|
Cont ID |
|
| Sent By |
kalexand |
Date |
2021-06-17 |
Time |
13:00 |
Rev Time |
0.00 |
| Received By |
kalexand |
Date |
2021-06-17 |
Time |
13:00 |
Sent To |
I |
|
| Notes |
| 2021-06-17 13:03:21 | ZONING PLAN REVIEW | | | ________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. INDICATE THE SETBACK DIMENSIONS FROM ANY EXTERIOR | | | IMPROVEMENTS TO ALL ADJACENT PROPERTY LINES. NOTE: PER | | | SECTION 94-304 OF THE ZLDR: | | | -- ACCESSORY STRUCTURE SETBACKS FOR SINGLE FAMILY/SMALL | | | LOT (SF11) RESIDENTIAL DISTRICT IS AS FOLLOWS: | | | --FRONT: 25 FEET | | | --SIDE: FIVE FEET FROM LOT LINES. | | | --CORNER: SAME AS REQUIRED FOR PRINCIPAL STRUCTURE. | | | --REAR: FIVE FEET MINIMUM OR 15 FEET FROM THE | | | CENTERLINE OF THE ALLEY TO A GARAGE FACING THE ALLEY, | | | WHICHEVER IS GREATER. | | | | | | 2. PLEASE SUBMIT A WRITTEN APPROVAL FROM THE BEAR LAKES | | | ESTATE NORTH ARCHITECTURAL REVIEW BOARD (A.R.B.). | | | PURSUANT TO THE BEAR LAKES ESTATE NORTH DECLARATION OF | | | COVENANTS AND RESTRICTIONS, SECTION VII, ARCHITECTURAL | | | CONTROLS, SUBSECTION A - A.R.B. REVIEW. PRIOR TO THE | | | ISSUANCE OF A BUILDING PERMIT FOR ANY CONSTRUCTION, | | | PLANS FOR THAT CONSTRUCTION MUST BE SUBMITTED AND | | | APPROVED IN WRITING BY THE A.R.B. | | | _________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD | | | LIKE TO RESUBMIT ELECTRONICALLY, EMAIL | | | [email protected] AND REQUEST TO HAVE YOUR | | | PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOG | | | IN INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL. | | | PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU | | | ARE FINISHED UPLOADING. | | | ________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | KIZZI ALEXANDRE, ASSOCIATE PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | TTY: 800.955.8771 | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|